This document was ed by and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this report form. Report 3l3c15
SET NON-COMPLIANT
P/WORD NOT-NERC BY
MODIFIED
CHANGED BY
ENTRY BLOCKED
BLOCKED ON
ENTRY UNBLOCKED
P/WORD UNBLOCKED ON
INVALID ENTERED
INV P/W ENTERED ON
EXPIRED
P/WORD EXPIRED ON
ENTERED WHILE BLOCKED
P/W ENT WHEN BLK ON
RECOVERY ENTERED
RCVY P/W ENTERED ON
IED SECURITY CODE READ
IED SEC CODE RD ON
IED SECURITY CODE TIMER EXPIRED
IED SEC CODE EXP -
PORT DISABLED
PORT DISABLED BY
PORT ENABLED
PORT ENABLED BY
DEF. DISPLAY NOT NERC COMPLIANT
DEF DSP NOT-NERC
PSL SETTINGS ED
PSL STNG D/LOAD BY
488
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 11 - Cyber-Security
Event Value
Display
DNP SETTINGS ED
DNP STNG D/LOAD BY
TRACE DATA ED
TRACE DAT D/LOAD BY
IEC61850 CONFIG ED
IED CONFG D/LOAD BY
CURVES ED
CRV D/LOAD BY
PSL CONFIG ED
PSL CONFG D/LOAD BY
SETTINGS ED
SETTINGS D/LOAD BY
PSL SETTINGS ED
PSL STNG BY
DNP SETTINGS ED
DNP STNG BY
TRACE DATA ED
TRACE DAT BY
IEC61850 CONFIG ED
IED CONFG BY
CURVES ED
CRV BY
PSL CONFIG ED
PSL CONFG BY
SETTINGS ED
SETTINGS BY
EVENTS HAVE BEEN EXTRACTED
EVENTS EXTRACTED BY
ACTIVE GROUP CHANGED
ACTIVE GRP CHNGE BY
CS SETTINGS CHANGED
C & S CHANGED BY
DR SETTINGS CHANGED
DR CHANGED BY
SETTING GROUP CHANGED
SETTINGS CHANGED BY
POWER ON
POWER ON -
SOFTWARE_ED
S/W ED -
Where: ● ● ● ●
int is the interface definition (UI, FP, RP1, RP2, TNL, T) prt is the port ID (FP, RP1, RP2, TNL, DNP3, IEC, ETHR) grp is the group number (1, 2, 3, 4) crv is the Curve group number (1, 2, 3, 4)
P14D-B/G/L/Z-TM-EN-1
489
Chapter 11 - Cyber-Security
P14D
● n is the new access level (0, 1, 2, 3) ● p is the level (1, 2, 3) ● nov is the number of events (1 – nnn) Each event is identified with a unique number that is incremented for each new event so that it is possible to detect missing events as there will be a ‘gap’ in the sequence of unique identifiers. The unique identifier forms part of the event record that is read or ed from the IED. Note: It is no longer possible to clear Event, Fault, Maintenance, and Disturbance Records
4.8
LOGGING OUT
If you have been configuring the IED, you should 'log out'. Do this by going up to the top of the menu tree. When you are at the Column Heading level and you press the Up button, you may be prompted to log out with the following display: DO YOU WANT TO LOG OUT?
You will only be asked this question if your level is higher than the fallback level. If you confirm, the following message is displayed for 2 seconds: LOGGED OUT Access Level <x>
Where x is the current fallback level. If you decide not to log out (i.e. you cancel), the following message is displayed for 2 seconds. CANCELLED Access Level <x>
Where x is the current access level.
490
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 11 - Cyber-Security
5
CYBER-SECURITY SETTINGS
The cyber-security settings are contained in the HMI database under the SECURITY CONFIGURATION. A summary of the relevant settings is shown below. Security cells summary Parameter
Cell col row
Default Setting
Interface Applicability
Available Setting
00 02
ASCII 33 to 122
Access Level
00 D0
0 = Read Some, 1 = Read All, All 2 = Read All + Write Some, 3 = Read All + Write All
Yes, Not Settable
Level 1
00 D2
ASCII 33 to 122
All
Yes
Level 2
00 D3
ASCII 33 to 122
All
Yes
Level 3
00 D4
ASCII 33 to 122
All
Yes
Security Feature
00 DF
1
All
Yes, Not Settable
SECURITY CONFIG
25 00
All
Yes
Use Banner
25 01
ACCESS ONLY FOR AUTHORISED S
ASCII 32 to 163
All
Yes
Attempts Limit
25 02
3
0 to 3 step 1
All
Yes
Attempts Timer
25 03
2
1 to 3 step 1
All
Yes
Blocking Timer
25 04
5
1 to 30 step 1
All
Yes
Front Port
25 05
Enabled
0 = Disabled or 1 = Enabled
All
No
Rear Port 1
25 06
Enabled
0 = Disabled or 1 = Enabled
All
No
Rear Port 2
25 07
Enabled
0 = Disabled or 1 = Enabled
All
No
Ethernet Port*
25 08
Enabled
0 = Disabled or 1 = Enabled
All
No
Courier Tunnel*†
25 09
Enabled
0 = Disabled or 1 = Enabled
All
No
IEC61850*†
25 0A
Enabled
0 = Disabled or 1 = Enabled
All
No
DNP3 OE*†
25 0B
Enabled
0 = Disabled or 1 = Enabled
All
No
Attempts Remain
25 11
All
Yes, Not Settable
Blk Time Remain
25 12
All
Yes, Not Settable
All
Yes, Not Settable
Yes
Fallbck PW Level
25 20
Security Code
25 FF
UI Only
No
Evt Unique Id (Normal Extraction)
01 FE
All
No
P14D-B/G/L/Z-TM-EN-1
0
0 = Level 0, 1 = Level 1, 2 = Level 2, 3 = Level 3
All
In Setting file?
491
Chapter 11 - Cyber-Security
Parameter Evt Iface Source ± (Bits 0 – 7 of Event State)
Cell col row
P14D
Default Setting
Interface Applicability
Available Setting
In Setting file?
01 FA
All
No
Evt Access Level ± (Bits 15 – 01 FB 8 of Event State)
All
No
Evt Extra Info 1 ± (Bits 23 – 16 of Event State)
01 FC
All
No
Evt Extra Info 2 ±Ω (Bits 31 – 01 FD 24 of Event State)
All
No
Where: * - These cells will not be present in a non-Ethernet product †- These cells will be invisible if the Ethernet port is disabled. ± - These cells invisible if event is not a Security event Ω – This cell is invisible in current phase as it does not contain any data. It is reserved for future use.
492
P14D-B/G/L/Z-TM-EN-1
SETTINGS APPLICATION SOFTWARE CHAPTER 12
Chapter 12 - Settings Application Software
494
P14D
P14D-B/G/L/Z-TM-EN-1
P14D
1
Chapter 12 - Settings Application Software
CHAPTER OVERVIEW
The settings application software used in this range of IEDs is called MiCOM S1 Agile. It is a collection of software tools, which is used for managing all aspects of the IEDs. This chapter provides a brief description of each software tool. Further information is available in the Help system. This chapter contains the following sections: Chapter Overview Introduction Interface Getting Started PSL Editor IEC 61850 IED Configurator DNP3 Configurator Curve Tool S&R Courier AEDR2 WinAEDR2 Wavewin Device (Menu) Text Editor
495 496 497 499 502 510 527 529 535 537 544 545 547
P14D-B/G/L/Z-TM-EN-1
495
Chapter 12 - Settings Application Software
2
P14D
INTRODUCTION
This software allows you to edit device settings and commands for Alstom Grid's range of IEDs. It is compatible with Windows XP, Windows Vista and Windows 7 operating systems. It also enables you to manage the MiCOM devices in your system. You can build a list of devices and organise them in the same way as they physically exist in a system. Parameters can be created and ed for each device, and devices can be supervised directly. It also includes a Product Selector tool. This is an interactive product catalogue, which makes it easier to choose the right device for each application.
496
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 12 - Settings Application Software
3
INTERFACE
3.1
TILE STRUCTURE P74x File Merger
Dynamic Synoptic Distibuted Busbar Tools
P746 Remote HMI Tool Menu Text Editor Open File View, Change and Save Settings
PSL File
GOOSE Editor
Select IED
Auxiliary & Test Devices
Events File
Settings File Conversion
DNP3.0 Settings File
MCL 61850 File
Disturbance Record File
Bay Template Configurator Files
Px40/K/L Px20 (Courier)
Open File MCL61850 File Open File Open File
Events File
Open File
Quick Connect
WinAEDR2
Disturbance Record File
Settings File Open File
System Explorer Disturbance Record Viewer
Ethernet Configuration
Import System Importing SCL Wavewin
IEC 61850 IED Configurator
Px20, K-Series to Rapide Settings Conversion Tool
Export System Open System
S1 Agile
AEDR2
Settings File conversion
Delete System
Device Configuration
Px30, Px30C, CX30, PG88, PG89
Log Record File S&R Modbus Tool
New System Smart Grid
Px10, Px20, PX20C, M720, Modulex
Settings File
Disturbance Recording and Monitoring
Phasor Terminal
S&R-103 Tool
Bay Template Configurator (BTC)
Measurement Centres
Px20, K Series to Agile Settings Convertor
Select IED
Motor Protection Generator Protection
Open File Settings File
Open File
Transducers Product Selector
Overcurrent & Voltage Feeder Protection
View, Change and Save Settings
IEC 61850 IED Configurator
Phase Comparison Protection
Phasor Measurement & GPS
UCA2 GOOSE File
Disturbance Record File
Autoreclose & Breaker Fail
Busbar Protection
PSL Editor
Device Text File
Line & Cable Differential
Transformer Protection
S&R Courier Tool
Centralised Busbar Tools
Distance Protection
Advanced Feeder Management
Switch Manager
PRP Configurator
RSTP Configurator
Open File
V01800
Figure 138: Tile structure
P14D-B/G/L/Z-TM-EN-1
497
Chapter 12 - Settings Application Software
3.2
P14D
MENU STRUCTURE MCL 61850 File
PSL File Px40
BTC File Px30
Settings File
Settings File Events File
Device Text File Px40
DNP3 File Px40
Open Default File
UCA2 GOOSE file Px40
Close System New System
Disturbance Record File
Px10, Px20, PX20C, M720, Modulex Settings File
Delete System
Compact System
Px40/K/L Px20 (Courier)
Open System Export System
Log Record File
Open File Import System
MCL 61850 File
Bay Template Configurator File
File
Import SCL
Disturbance Record File
Settings File
Recent Systems
UCA2 GOOSE File
S1 Studio Exit
Search Results
Preferences
Px30, Px30C, CX30, PG88, PG89
Start Page View
Device Text File
Options
Properties
Language
System Explorer
DNP3.0 settings File
Help
PSL File Events File
Disturbance Record File
Print IEC 61850 IED Configurator
Print Print Prieview
PSL Editor Px40
MCL 61850 File
Page Setup DR Viewer: Wavewin
Text Editor Tools S&R Courier
Device Text Editor Px40
V01804
Figure 139: Menu structure
498
P14D-B/G/L/Z-TM-EN-1
P14D
4
Chapter 12 - Settings Application Software
GETTING STARTED
Start Start Data Model Manager data models Start S1 Agile
Click System Explorer tile then New System tile or Open System tile From menu bar Select View > System Explorer In System Explorer pane, right click system and add Substation, Voltage Level, Bay, and Device Right click Device Connections subfolder to create new connections
Yes
Open system
Offline Open system or open file? Open file
Click Device Configuration tile then Px40 tile
Select tile depending on file type: settings, PSL, 61850, DNP3, disturbance record, Courier, UCA2 GOOSE or events
Right click Device type subfolders to view properties and add or extract files
Online Connect correct cable between PC and IED front . Click Quick Connect tile Open system or create new system Select IED type
Need new connections? No
Online or offline?
Open existing file or Open default file
Edit and Save
Select front, rear or Ethernet port Check connection parameters then click Finish
No Setting complete? Yes Stop
V01802
Figure 140: Flowchart showing how S1 Agile can be used to set up and save a protection system offline or online.
P14D-B/G/L/Z-TM-EN-1
499
Chapter 12 - Settings Application Software
4.1
P14D
QUICK SYSTEM GUIDE
You can create a system to mimic your real world system of devices. A system provides a root node in the System Explorer from which all subsequent nodes are created. You can add substations, bays, voltage levels and devices to the system. You can either Create a new system or Open an existing system. If there is no default system, use Quick Connect to automatically create one. If a system is no longer needed, right-click it and select Delete to permanently delete it. Systems are not opened automatically. To change this, select Options > Preferences then check the checkbox Reopen last System at start-up.
4.2 1. 2.
4.3 1. 2. 3. 4.
4.4 1. 2. 3. 4. 5.
4.5 1. 2. 3. 4. 5.
4.6
DATA MODELS Close S1 Agile and run the Data Model Manager. Follow the on-screen instructions.
SET UP A SYSTEM Click the System Explorer tile then the New System tile or Open System tile. From the menu bar select View > System Explorer. In the System Explorer pane, right click System and select New Substation, New Voltage Level, New Bay, and New Device. Right-click the Device subfolders to view properties and add or extract files.
CONNECTING TO AN IED FRONT PORT Connect the cable between the PC and IED. From the main screen, click Quick Connect. Select the product range. Select connection to the Front Port. Set the connection parameters and click Finish.
CONNECTING TO AN IED IN A SYSTEM Make sure that the correct serial rear port or Ethernet cables are in place. From the main screen, click Quick Connect. Select the product range. Select connection to the Rear Port or Ethernet Port. Set the connection parameters and click Finish.
SEND SETTINGS TO A DEVICE
To send settings to a device there must be at least one setting file in a settings folder for a device. 1. 2. 3.
500
Right-click the device name in System Explorer and select Send. In the Send To dialog select the setting files and click Send. Click Close to close the Send To dialog.
P14D-B/G/L/Z-TM-EN-1
P14D
4.7 1. 2. 3.
4.8 1. 2. 3.
Chapter 12 - Settings Application Software
EXTRACT SETTINGS FROM A DEVICE Using System Explorer, find the device. Right-click the device's Settings folder and select Extract Settings or Extract Full Settings. Once the settings file is retrieved, click Close.
EXTRACT A PSL FILE FROM A DEVICE Using System Explorer, find the Px4x device. Right-click the device's PSL folder and select Extract. Once the file is retrieved, click Close.
Note: If you extract a PSL file from a device that does not store the position information of the PSL scheme elements, the layout of the scheme may not be the same as originally drawn. Also the Original and Logic Only CRC values may not match the original scheme. However, the scheme will be logically correct.
4.9 1. 2. 3.
4.10 1. 2. 3.
4.11 1. 2. 3. 4. 5. 6.
EXTRACT A DNP3 FILE FROM A DEVICE Using System Explorer, find the device. Right-click the device's DNP3 folder and select Extract. Once the file is retrieved, click Close.
EXTRACT AN EVENTS FILE FROM A DEVICE Using System Explorer, find the device. Right-click the device's Events folder and select Extract Events. Once the file is retrieved, click Close.
EXTRACT A DISTURBANCE RECORD FROM A DEVICE Using System Explorer, find the device. Right-click the device's Disturbance Records folder and select Extract Disturbances. Select a disturbance record to extract. Choose a COMTRADE format, 1991 or 2001. Click Extract or Save. Save leaves the record in the device, Extract deletes it. Once the disturbance records file is retrieved, click Close.
P14D-B/G/L/Z-TM-EN-1
501
Chapter 12 - Settings Application Software
5
P14D
PSL EDITOR
The Programmable Scheme Logic (PSL) is a module of programmable logic gates and timers in the IED, which can be used to create customised internal logic. This is done by mapping the IED's digital inputs, combining these inputs with internally generated digital signals using logic gates and timers, and mapping the resultant signals to the IED's digital outputs and LEDs. The Programmable Scheme Logic (PSL) Editor allows you to create and edit scheme logic diagrams to suit your own particular application. Before a scheme logic diagram can be created, the Editor must have a ‘template’ configuration that allows it to determine various IED-specific parameters such as the number of opto-inputs and output relays, as well as signal names and types. Because there are many different product variants, it is not possible for the Editor to provide a common default scheme. Instead, you need to load a configuration from a file. The PSL uses the concept of a digital data bus (DDB). The DDB is a parallel data bus containing all of the digital signals (inputs, outputs, and internal signals), which are available for use in the PSL. The PSL's software logic gates and timers can be used to combine and condition the DDB signals. The logic gates can be programmed to perform a range of different logic functions and can accept any number of inputs. The timers are used either to create a programmable delay or to condition the logic outputs. Inputs to the PSL include: ● ● ● ●
Optically-isolated digital inputs (opto-inputs) IEC 61850 GOOSE inputs Control inputs Function keys
Outputs from the PSL include: ● ● ● ●
Relay outputs LEDs IEC 61850 GOOSE outputs Trigger signals
Internal signals include: ● Inputs to the PSL originating from internal functions. These are signals generated within the device and can be used to affect the operation of the scheme logic. ● Outputs from the PSL. These are signals that can be driven from the PSL to activate specific functions. An example of an internal input and output are: ● I>1 Trip. This is an output from the Stage 1 overcurrent protection function, which can be input into the PSL to create further functionality. This is therefore a PSL input. ● V>1 Trip. This is an output from the overvoltage protection function, which can be input into the PSL to create further functionality. This is therefore a PSL input. ● Reset Relays/LED. This is a PSL output, which can be asserted to reset the output relays and LEDs. The PSL logic is event driven. Only the part of the PSL logic that is affected by the particular input change that has occurred is processed. This reduces the amount of processing time used by the PSL when compared to some competition devices. The PSL editor lets you: ● Start a new PSL diagram ● Extract a PSL file from an IED
502
P14D-B/G/L/Z-TM-EN-1
P14D
● ● ● ● ● ● ● ●
Chapter 12 - Settings Application Software
a PSL file to an IED Open a diagram from a PSL file Add logic components to a PSL file Move components in a PSL file Edit links in a PSL file Add links to a PSL file Highlight a path in a PSL file Use a conditioner output to control logic
● Print PSL files For further information on the PSL editor, see the online help built into the settings application software.
5.1
LOADING SCHEMES FROM FILES
The product is shipped with default scheme files. These can be used as a starting point for changes to a scheme. To create a new blank scheme, select File > New > 'Blank scheme... to open the default file for the appropriate IED. This deletes the diagram components from the default file to leave an empty diagram but with the correct configuration information loaded.
5.2
PSL EDITOR TOOLBAR
There are a number of toolbars available to help with navigating and editing the PSL. Toolbar
Description Standard tools: For file management and printing. Alignment tools: To snap logic elements into horizontally or vertically aligned groupings. Drawing tools : To add text comments and other annotations, for easier reading of PSL schemes. Nudge tools: To move logic elements. Rotation tools: Tools to spin, mirror and flip. Structure tools: To change the stacking order of logic components. Zoom and pan tools: For scaling the displayed screen size, viewing the entire PSL, or zooming to a selection.
5.2.1
LOGIC SYMBOLS
The logic symbol toolbar provides icons to place each type of logic element into the scheme diagram. Not all elements are available in all devices. Icons are only displayed for elements available in the selected device. Function
Symbol Link
P14D-B/G/L/Z-TM-EN-1
Explanation Create a link between two logic symbols.
503
Chapter 12 - Settings Application Software
Symbol
5.3 1. 2. 3.
Function
P14D
Explanation
Opto Signal
Create an opto-input signal.
Input Signal
Create an input signal.
Output Signal
Create an output signal.
GOOSE In
Create an input signal to logic to receive a GOOSE message transmitted from another IED. Used in either UCA2.0 or IEC 61850 GOOSE applications only.
GOOSE Out
Create an output signal from logic to transmit a GOOSE message to another IED. Used in either UCA2.0 or IEC 61850 GOOSE applications only.
Control In
Create an input signal to logic that can be operated from an external command.
InterMiCOM In
Create an input signal to logic to receive an InterMiCOM command transmitted from another IED.
InterMiCOM Out
Create an output signal from logic to transmit an InterMiCOM command to another IED.
Function Key
Create a function key input signal.
Trigger Signal
Create a fault record trigger.
LED Signal
Create an LED input signal that repeats the status of tri-colour LED.
Signal
Create a signal.
LED Conditioner
Create an LED conditioner.
Conditioner
Create a conditioner.
Timer
Create a timer.
AND Gate
Create an AND Gate.
OR Gate
Create an OR Gate.
Programmable Gate
Create a programmable gate.
LOGIC SIGNAL PROPERTIES Use the logic toolbar to select logic signals. This is enabled by default but to hide or show it, select View > Logic Toolbar. Zoom in or out of a logic diagram using the toolbar icon or select View > Zoom Percent. Right-click any logic signal and a context-sensitive menu appears.
Certain logic elements show the Properties option. If you select this, a Component Properties window appears. The contents of this window and the signals listed will vary according to the logic symbol selected. The actual DDB numbers are dependent on the model.
504
P14D-B/G/L/Z-TM-EN-1
P14D
5.3.1
Chapter 12 - Settings Application Software
LINK PROPERTIES
Links form the logical link between the output of a signal, gate or condition and the input to any element. Any link connected to the input of a gate can be inverted. To do this: 1. Right-click the input 2. Select Properties…. The Link Properties window appears. 3. Check the box to invert the link. Or uncheck for a non-inverted link An inverted link is shown with a small circle on the input to a gate. A link must be connected to the input of a gate to be inverted. Links can only be started from the output of a signal, gate, or conditioner, and must end at an input to any element. Signals can only be an input or an output. To follow the convention for gates and conditioners, input signals are connected from the left and output signals to the right. The Editor automatically enforces this convention. A link is refused for the following reasons: ● There has been an attempt to connect to a signal that is already driven. The reason for the refusal may not be obvious because the signal symbol may appear elsewhere in the diagram. In this case you can right-click the link and select Highlight to find the other signal. Click anywhere on the diagram to disable the highlight. ● An attempt has been made to repeat a link between two symbols. The reason for the refusal may not be obvious because the existing link may be represented elsewhere in the diagram.
5.3.2
OPTO SIGNAL PROPERTIES Input # DDB #
E02030
Each opto-input can be selected and used for programming in PSL. Activation of the opto-input drives an associated DDB signal.
5.3.3
INPUT SIGNAL PROPERTIES NIC Link Fail # DDB #
E02031
IED logic functions provide logic output signals that can be used for programming in PSL. Depending on the IED functionality, operation of an active IED function drives an associated DDB signal in PSL.
5.3.4
OUTPUT SIGNAL PROPERTIES Inhibit VTS DDB #
E02032
Logic functions provide logic input signals that can be used for programming in PSL. Depending on the functionality of the output relay, when the output signal is activated, it drives an associated DDB signal in PSL. This causes an associated response to the function of the output relay.
5.3.5
GOOSE INPUT SIGNAL PROPERTIES Virtual Input # DDB #
E02033
P14D-B/G/L/Z-TM-EN-1
505
Chapter 12 - Settings Application Software
P14D
The Programmable Scheme Logic interfaces with the GOOSE Scheme Logic through 32 Virtual Inputs. The Virtual Inputs can be used in much the same way as the opto-input signals. The logic that drives each of the Virtual Inputs is contained in the GOOSE Scheme Logic file. You can map any number of bit-pairs from any subscribed device using logic gates onto a Virtual Input.
5.3.6
GOOSE OUTPUT SIGNAL PROPERTIES Virtual Output # DDB #
E02034
The Programmable Scheme Logic interfaces with the GOOSE Scheme Logic through 32 Virtual Outputs. You can map Virtual Outputs to bit-pairs for transmitting to any subscribed devices.
5.3.7
CONTROL INPUT SIGNAL PROPERTIES Control Input # DDB #
E02035
There are 32 control inputs which can be activated using the menu, the hotkeys or through courier communications. Depending on the programmed setting that is latched or pulsed, when a control input is operated an associated DDB signal is activated in PSL.
5.3.8
INTERMICOM INPUT PROPERTIES IM64 Ch # Input # DDB #
E02036
There are 16 InterMiCOM inputs that can be used for teleprotection and remote commands. InterMiCOM In is a signal which is received from the remote end. It can be mapped to a selected output relay or logic input. IED End B Clear Statistics DDB #
E02037
At end B, InterMiCOM Input 1 is mapped to the command Clear Statistics.
5.3.9
INTERMICOM OUTPUT PROPERTIES IM64 Ch # Output # DDB #
E02038
There are 16 InterMiCOM outputs that can be used for teleprotection and remote commands. InterMiCOM Out is a send command to a remote end that can be mapped to any logic output or opto-input. This is transmitted to the remote end as a corresponding InterMiCOM In command. IED End A Clear Stats command DDB #
E02039
At end A, InterMiCOM Output 1 is mapped to the command indication Clear Statistics issued at end A.
506
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 12 - Settings Application Software
5.3.10
FUNCTION KEY PROPERTIES Function Key # DDB #
E02040
Each function key can be selected and used for programming in PSL. Activation of the function key drives an associated DDB signal. The DDB signal remains active according to the programmed setting (toggled or normal). Toggled mode means the DDB signal remains in the new state until the function key is pressed again. In Normal mode, the DDB is only active while the key is pressed.
5.3.11
FAULT RECORDER TRIGGER PROPERTIES Fault REC TRIG DDB #
E02041
The fault recording facility can be activated by driving the fault recorder trigger DDB signal.
5.3.12
LED SIGNAL PROPERTIES LED # DDB #
E02042
All programmable LEDs drive associated DDB signals when the LED is activated.
5.3.13
SIGNAL PROPERTIES Output # DDB #
E02043
All output relay s drive associated DDB signal when the output is activated.
5.3.14
LED CONDITIONER PROPERTIES 1
Non Latching
Non Latching 1
1
Non Latching
FnKey LED1 Red DDB #
Red LED
FnKey LEDGm DDB #
FnKey LED1 Red DDB #1040 FnKey LEDGm DDB #
FnKey LED1 Red DDB #1040 FnKey LEDGm DDB #
Green LED
Yellow LED
E02044
Figure 141: Examples of how to set Red, Green and Yellow LEDs
P14D-B/G/L/Z-TM-EN-1
507
Chapter 12 - Settings Application Software
P14D
To set LED conditioner properties, 1. 2. 3. 4. 5. 6.
Select the LED name from the list (only shown when inserting a new symbol). Configure the LED output to be Red, Yellow or Green. Configure a Green LED by driving the Green DDB input. Configure a RED LED by driving the RED DDB input. Configure a Yellow LED by driving the RED and GREEN DDB inputs simultaneously. Configure the LED output to be latching or non-latching.
5.3.15
CONDITIONER PROPERTIES
Each can be conditioned with an associated timer that can be selected for pick up, drop off, dwell, pulse, pick-up/drop-off, straight-through, or latching operation. Straight-through means it is not conditioned at all whereas Latching is used to create a sealed-in or lockout type function. To set properties, 1. 2. 3.
Select the name from the Name list (only shown when inserting a new symbol). Choose the conditioner type required in the Mode tick list. Set the Pick-up Value (in milliseconds), if required.
4.
Set the Drop-off Value (in milliseconds), if required.
5.3.16
TIMER PROPERTIES
Each timer can be selected for pick-up, drop-off, dwell, pulse or pick-up/drop-off operation. To set timer properties, 1. 2. 3. 4.
From the Timer Mode tick list, choose the mode. Set the Pick-up Value (in milliseconds), if required. Set the Drop-off Value (in milliseconds), if required. Click OK.
5.3.17
GATE PROPERTIES
A gate can be an AND, OR, or programmable gate. ● An AND Gate requires that all inputs are TRUE for the output to be TRUE. ● An OR Gate requires that one or more input is TRUE for the output to be TRUE. ● A Programmable Gate requires that the number of inputs that are TRUE is equal to or greater than its Inputs to Trigger setting for the output to be TRUE. To set gate properties, 1. 2. 3. 4.
Select the gate type: AND Gate, OR Gate, or Programmable Gate. If you select Programmable Gate, set the number of Inputs to Trigger. If you want the output of the gate to be inverted, check the Invert Output check box. An inverted output appears as a "bubble" on the gate output. Click OK.
5.3.18
SR PROGRAMMABLE GATE PROPERTIES
A Programmable SR gate can be selected to operate with the following three latch properties:
508
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 12 - Settings Application Software
Set
Q0 (Previous Output State)
Reset
Q1 Reset Dominant
Q1 Set Dominant
Q1 No Dominance
0
0
0
0
0
0
0
0
1
1
1
1
0
1
1
0
0
0
0
1
0
0
0
0
1
1
0
1
0
0
1
1
1
1
0
1
1
0
1
1
1
1
1
0
0
1
1
1
Q0 is the previous output state of the latch before the inputs change. Q1 is the output of the latch after the inputs change. The Set dominant latch ignores the Reset if the Set is on. The Reset Dominant latch ignores the Set if the Reset is on. When both Set and Reset are on, the output of the non-dominant latch depends on its previous output Q0. Therefore if Set and Reset are energised simultaneously, the output state does not change. Note: Use a set or reset dominant latch. Do not use a non-dominant latch unless this type of operation is required.
SR latch properties In the Component Properties dialog, you can select S-R latches as Standard (no input dominant), Set input dominant or Reset input dominant. If you want the output to be inverted, check the Invert Output check box. An inverted output appears as a "bubble" on the gate output.
P14D-B/G/L/Z-TM-EN-1
509
Chapter 12 - Settings Application Software
6
P14D
IEC 61850 IED CONFIGURATOR
IEC 61850 is a substation communications standard. It standardizes the way data is transferred to and from IEC 61850 compliant IEDs, making the communication independent of the manufacturer. This makes it easier to connect different manufacturers’ products together and simplifies wiring and network changes. The IEC 61850 IED Configurator tool is used to configure the IEC 61850 settings of MiCOM IEDs, not the protection settings. It also allows you to extract a configuration file so you can view, check and modify the IEC 61850 settings during precommissioning.
6.1
IEC 61850 IED CONFIGURATOR TOOL FEATURES
The IEC 61850 IED configurator allows you to: ● ● ● ● ● ● ●
●
● ● ●
6.2
Configure basic IEC 61850 communication parameters of the IED. Configure IED time synchronisation using SNTP. Define datasets for inclusion in report and GOOSE control blocks. Configure GOOSE control blocks for publishing (outgoing) messages. Configure virtual inputs, mapping them onto subscribed (incoming) GOOSE messages. Configure report control blocks. Configure the operation of control objects (circuit breaker trip and close): ▪ The control mode (such as Direct, Select Before Operate) ▪ Uniqueness of control (to ensure only one control in the system can operate at any one time). Configure measurements: ▪ Scaling (multiplier unit such as kA, MV). ▪ Range (minimum and maximum measurement values). ▪ Deadband (percentage change of measurement range for reporting). Transfer IEC 61850 configuration information to and from an IED. Import SCL files for any IEC 61850 device (including devices from other manufacturers) to simplify configuration of GOOSE messaging between IEDs. Generate SCL files to provide IED configuration data to other manufacturers' tools, allowing them to use published GOOSE Messages and reports.
IEC 61850 IED CONFIGURATOR LANGUAGES
The IEC 61850 IED Configurator uses the following languages. MiCOM Configuration Language (MCL) This is a proprietary language file which contains a MiCOM device's IEC 61850 configuration information. This file is used for transferring data to or from a MiCOM IED. Substation Configuration Language (SCL) This is an XML-based standard language used to configure IEC 61850 IEDs in substations. It allows common substation files to be exchanged between all devices and between different manufacturers' toolsets. This helps to reduce inconsistencies in system configurations. s can specify and provide their own SCL files to ensure that IEDs are configured according to their requirements. SCL also allows IEC 61850 applications to be configured off-line without needing a network connection to the IED. Off-line system development tools can be used to generate the files needed for IED configuration automatically from the power system design. This significantly reduces the cost of IED configuration by eliminating most of the manual configuration tasks.
510
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 12 - Settings Application Software
SCL specifies a hierarchy of configuration files, which enable the various levels of the system to be described: SSD, SCD, ICD, CID and IID files.
6.3
IEC 61850 SUBSTATION CONFIGURATION FILES
These files all use the standard Substation Configuration Language (SCL). They have the same construction but differ depending on the application. System Specification Description (SSD) This contains the complete specification of a substation automation system including a single line diagram for the substation and its functionalities, or logical nodes. The SSD contains SCD and ICD files. Substation Configuration Description (SCD) This contains information about the substation, all IEDs, data types and communications configuration. When engineering a system from the top down, an SCD file is produced and imported into the IED Configurator. To ensure consistency with the configuration of other IEDs in the system, this SCD file normally should not be edited. If there is no SCD file available, and you need to manually configure a MiCOM IED for precommissioning tests, you can open an ICD file and edit this to suit the IED application. The ICD file can be preinstalled as a template in the IED Configurator and opened directly, or it can be provided separately. IED Capability Description file (ICD) This describes the IED's capabilities, including information on its data model (Logical Devices or Logical Node instances) and GOOSE . The IEC 61850 IED Configurator can be used before commissioning an IED to create a blank configuration ICD file. The IEC 61850 IED Configurator can also extract an ICD file for viewing or modification and error checking a MiCOM IED. Configured IED Description File (CID) or Individual IED Description File (IID) This describes a single IED in the system, including communications parameters.
Figure 142: IEC 61850 project configuration
P14D-B/G/L/Z-TM-EN-1
511
Chapter 12 - Settings Application Software
6.4
P14D
OPENING A PRECONFIGURED SCL FILE
An SCL configuration file contains the information for the MiCOM IED that is to be configured. To open an SCL configuration file for the system 1. Select File > Import SCL. A search dialog box appears. 2. Select the required SCL file and click Open. 3. The SCL Explorer window appears, showing an icon for each IED present in the SCL file. IEDs which can be configured using the IED Configurator are shown in a bold typeface and an icon with a green tick. IEDs which cannot be configured using the IED Configurator are shown with greyed text and an icon with a red X. The left hand side of the window shows information on the SCL file and any selected IED tasks that can be performed on the selected IED(s). Alternatively right-click an IED to list tasks that can be performed on that particular IED.
6.5
OPENING A TEMPLATE ICD FILE
If there is no SCD configuration file available, open an ICD template file for the MiCOM IED type that is to be configured. 1. 2. 3.
6.5.1
Select File > New. The Template window appears. Select the IED model number from the list. The list shows information about the IED's associated ICD template file, the SCL header details and the IEC 61850 features ed by the IED. Use the Model Number filter at the top of the window to filter product variants.
TEMPLATE INSTALLED FOR REQUIRED IED TYPE
If you can find the IED type or ICD template, highlight it and click the Select button. The configuration opens in manual editing mode so it can be customised for the application.
6.5.2 1. 2. 3. 4. 5. 6. 7.
6.6 1. 2.
512
TEMPLATE NOT INSTALLED FOR REQUIRED IED TYPE If there is no installed ICD file for the IED type that is to be configured, but there is one available from your supplier, click Browse for External. A search dialog box appears. When you have found the required ICD file, click Open. If the selected ICD Template file is already available as an installed template, a message appears and a new IED Configuration is created from the installed file. If the selected ICD Template file has additional ed model numbers, a message appears asking if the additional model numbers should be merged into the installed template. Select Yes to merge the new model numbers into the installed ICD Template file. This makes it available the next time the Template window appears. If the selected ICD Template file is not installed, a message asks if it should be added to the application template library. Select Yes to copy the selected ICD template file into the application library. This makes it available the next time the Template window appears.
OPENING AN EXISTING MCL CONFIGURATION FILE Select File > Open. A search dialog box appears. Select the required MCL file and click Open.
P14D-B/G/L/Z-TM-EN-1
P14D
3. 4.
5.
6.7
Chapter 12 - Settings Application Software
The IED Configurator tool tries to automatically match the MCL data to an installed ICD Template file and then display the configuration data in a read-only mode. If it cannot automatically match the MCL data to an ICD Template file, the Template window appears. This allows you to manually assign the MCL data to an ICD Template file. If there is no suitable template available, click Cancel. A message asks if the configuration is to be opened with Restricted Editing. Select Yes to display the configuration data in a read-only mode.
CONFIGURING A MICOM IED
Working offline: 1. Click the icon New MiCOM Configuration from an Installed ICD File. 2. Double-click the product variant. 3. Double-click TEMPLATE to expand it. Or working online: 1. 2. 3.
Select Device > Manage IED. Select the IED type and click Next. Select the IED address and click Next. The IED 61850 Configurator tool reads information from the IED and shows them in the Summary view.
The aspects of a MiCOM IED that can be configured come from its ICD Template file. These are shown in the main area of the IED Configurator tool, in the left hand side of the Editor window. The right hand side of the Editor window shows the configuration page of the selected category. Each configurable item of the MiCOM IED is categorised into one of the following groups in the Editor window. IED Details Displays general configuration and data about the IED and the selected ICD template file. Communications Displays configuration of the communications Subnetwork. SNTP Displays configuration of the client/server SNTP time synchronisation. Dataset Definitions Displays dataset definitions used by the IED's GOOSE and report control blocks. GOOSE Publishing Displays configuration for the GOOSE control blocks and associated messages to be published. GOOSE Subscribing Displays configuration of virtual inputs that are subscribed to published GOOSE messages. Report Control Blocks Displays configuration for the report control blocks in the IED data model. Controls Displays configuration of control objects and uniqueness of control parameters (for larger control systems). Measurements Displays configuration of measurement objects in the IED data model. Configurable Data Attributes Displays parameter values for the configurable data attributes in the IED data model. Each configurable item is either read-only or editable in manual mode. If it is read-only it is always noneditable. If it is editable in manual mode, some items may not be configurable if opened from a configured SCL file. If a configured SCL file or MCL file was opened, and it is necessary to edit the configuration, select View > Enter Manual Editing Mode or click the toolbar icon. If an ICD file is opened, these items are automatically displayed in manual editing mode.
P14D-B/G/L/Z-TM-EN-1
513
Chapter 12 - Settings Application Software
6.8
P14D
READING OR EDITING IED DETAILS
Working offline: 1. Click the icon New MiCOM Configuration from an Installed ICD File. 2. Double-click the product variant. 3. Double-click the IED Details item. Or working online: 1. 2. 3. 4.
Select Device > Manage IED. Select the IED type device number. Select the IED address and click Next. The IED 61850 Configurator tool reads information from the IED and shows them in the Summary view. Click the IED Details tab to show more information and edit the settings.
The following IED details can be edited. SCL File ID The identification name, taken from the header section of an SCL file. Editable in Manual Editing Mode. SCL File Version The version number, taken from the header section of an SCL file. Editable in Manual Editing Mode. Name The IED name, taken from the IED section of an SCL file. This should be unique for all IEDs on the IEC 61850 network and is an Object Reference type so can be up to 65 characters long. However, it is recommended to restrict IED names to 8 characters or less. Editable in Manual Editing Mode. ICD Template The ICD Template filename associated with the device's IEC 61850 configuration (MCL data). Read-only. Description A basic description of the MiCOM IED type. It is taken from the IED section of the ICD template file and is not stored in MCL data or sent to the MiCOM IED. Read-only. Type The MiCOM IED type. It is taken from the IED section of the ICD template file and is not stored in MCL data or sent to the MiCOM IED. Read-only. Configuration Revision The software version of the target MiCOM IED. It is taken from the IED section of the ICD template file and is not stored in MCL data or sent to the MiCOM IED. Read-only. ed Models The specific MiCOM IED models ed by the ICD template file. If an ICD file is opened, these models are ed directly. If a configured SCL file is opened, these models are derived from the ICD file which is used to create a configured SCL file. It is not stored in MCL data nor sent to the MiCOM IED. Read-only.
6.9
COMMUNICATIONS SETUP
Before the IEC 61850 IED Configurator tool can manage an IED's configuration, you must first configure the communication parameters. Select Tools > Options, then select the tab according to the protocol used. IEC 870-5-103 Communications tab. Communication is through a serial connection from a COM port of the PC to the front port of the IED. If ed by the IED, you can also use the rear port. The Ethernet connection is not used, because the MiCOM IED does not have an IP address until it has been configured. This is also used for Px30 products. Courier Communications tab. Communication is through a serial connection from a COM port of the PC to the front port of the IED. If ed by the IED, you can also use the rear port. The Ethernet connection is
514
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 12 - Settings Application Software
not used, because the MiCOM IED does not have an IP address until it has been configured. This is typically used for Px40 products. 1.
In the Default Configurations field, if using the front port, select MiCOM P*40 Front Port (COM *), if using the rear port, select Courier (COM *). 2. Set the Connection Values and Transaction Parameters as required or leave them at the default values. 3. Click OK. FTP communications tab. Communication is over Ethernet to the FTP server of a MiCOM IED. The IP Address settings for both the PC and MiCOM IED must be for the same SubNetwork, especially if a direct connection is used with a cross-over network lead. If there is no valid or active IEC 61850 configuration in the IED, configure a default IP Address for the IED. This is also used for Mx70 products.
6.10
EDITING COMMUNICATIONS SETTINGS
Working offline: 1. Click the icon New MiCOM Configuration from an Installed ICD File. 2. Double-click the product variant. 3. Double-click the Communications item. Or working online: 1. 2. 3. 4.
Select Device > Manage IED. Select the IED type device number. Select the IED address and click Next. The IED 61850 Configurator tool reads information from the IED and shows them in the Summary view. Click the Communications tab to read and edit the settings.
The following communications settings can be edited. Connected Subnetwork This is the subnetwork name to which the IED is connected. It is particularly important for subscribing to GOOSE messages because an IED can only subscribe to publishers that are connected to the same subnetwork. The subnetwork name is taken from the Communications section of an SCL file. Normally editable in Manual Editing Mode, except if opened from a configured SCL file. Access Point The Access Point (physical port) name for the MiCOM IED. This is taken from the IED Access Point section of the ICD template file. It is not stored in MCL data or sent to the MiCOM IED. Read-only. IP Address Used to configure the unique network IP address of the MiCOM IED. It is taken from the ConnectedAP Address section of the configured SCL file. Editable in Manual Editing Mode. SubNet Mask Used to configure the IP subnet mask for the network to which the MiCOM IED will be connected. It is taken from the ConnectedAP Address section of the configured SCL file. Editable in Manual Editing Mode. Gateway Address Used to configure the IP address of any gateway (proxy) device, to which the MiCOM IED is connected. It is taken from the ConnectedAP Address section of the configured SCL file. If there is no gateway (proxy) in the system, leave this at its default unconfigured value of 0.0.0.0. Editable in Manual Editing Mode. Default Media Used to set whether a copper or fibre optic Ethernet interface is used for communication between clients and peers, and the MiCOM IED. It is taken from the ConnectedAP/PhysConn section of the configured SCL file. Editable in Manual Editing Mode. T Keepalive Used to set the frequency at which the MiCOM IED sends a T Keepalive message to keep open an association with a connected client. This setting is not taken from SCL. It is specific to MCL with a setting range of 1 to 20 seconds. Editable in Manual Editing Mode.
P14D-B/G/L/Z-TM-EN-1
515
Chapter 12 - Settings Application Software
P14D
Database Lock Timeout Used to set how long the MiCOM IED waits without receiving any messages on the active link before it reverts to its default state. This includes resetting any access that was enabled. It is taken from the IED/AccessPoint/Server section of the configured SCL file and has a valid setting range of 60 to 1800 seconds (1 to 30 minutes). Only applicable to MiCOM IEDs that setting changes over IEC 61850. Editable in Manual Editing Mode.
6.11
SIMPLE NETWORK TIME PROTOCOL (SNTP)
Simple Network Time Protocol (SNTP) is used to synchronize the clocks of computer systems over packetswitched, variable-latency data networks, such as IP. A jitter buffer is used to reduce the effects of variable latency introduced by queuing, ensuring a continuous data stream over the network. SNTP is ed by both the IED and the switch in the redundant Ethernet board. Both the IED and the redundant Ethernet board have their own IP address. Using the IP address of each device it can be synchronised to the SNTP server. For the IED this is done by entering the IP address of the SNTP server into the IED using the IEC 61850 IED Configurator software. For the redundant Ethernet board, this is done depending on the redundant Ethernet protocol being used. For PRP use the PRP Configurator. For RSTP use the RSTP Configurator. For SHP and DHP use Switch Manager.
6.11.1
CONFIGURING SNTP IN THE IED
These settings allow you to configure a MiCOM IED for SNTP. Working offline: 1. Click the icon New MiCOM Configuration from an Installed ICD File. 2. Double-click the product variant. 3. Double-click the SNTP item. Or working online: 1. 2. 3. 4.
Select Device > Manage IED. Select the IED type device number. Select the IED address and click Next. The IED 61850 Configurator tool reads information from the IED and shows them in the Summary view. Click the SNTP tab. Expand the tab and select General Config (configuring the IED for SNTP).
The following settings can be edited. Poll Rate Use this to configure the interval at which the MiCOM IED requests time synchronisation from the selected SNTP server(s). This setting is not taken from SCL. It is specific to MCL with a setting range of 64 to 1024 seconds and is editable in Manual Editing Mode. Accepted Stratum level SNTP uses a hierarchical system of clock sources. Each level is known as a stratum and is assigned a layer number starting with zero at the top, which is the reference time signal. The Accepted Stratum level setting specifies the stratum range for all configured SNTP servers. It defines the range MiCOM IEDs need to be able to accept time synchronisation responses. Any server response outside the specified range is discarded. You cannot edit this setting. Time server This configures whether or not the IED acts as a time server in the system. If this option is enabled, other devices can synchronise their clocks to this IED. The value for this setting is taken from the IED/AccessPoint section of the configured SCL file. This setting is editable in Manual Editing Mode.
516
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 12 - Settings Application Software
6.11.2
CONFIGURING THE SNTP SERVER
These settings allow you to configure external SNTP time servers with which the IED tries to synchronise its clock and connect. Working offline: 1. Click the icon New MiCOM Configuration from an Installed ICD File. 2. Double-click the product variant. 3. Double-click the SNTP item. Or working online: 1. 2. 3. 4.
Select Device > Manage IED. Select the IED type device number. Select the IED address and click Next. The IED 61850 Configurator tool reads information from the IED and shows them in the Summary view. Click the SNTP tab. Expand the tab and select External Server (configuring external SNTP time servers to which the IED connects).
The following details can be edited. Server Name If opened from a configured SCL file, this shows the name of the device with which the MiCOM IED attempts to synchronise its clock. If you need to change the device, click the drop-down list to see all time-server devices in the configured SCL file. This is Read-only, is not stored in MCL data and is not sent to the MiCOM IED. Access Point If opened from a configured SCL file, this shows the connected Access Point of the device with which the MiCOM IED attempts to synchronise its clock. This is Read-only, is not stored in MCL data and is not sent to the MiCOM IED. Sub Network Name If opened from a configured SCL file, this shows the Sub Network name with which the device is connected. This is Read-only, is not stored in MCL data and is not sent to the MiCOM IED. IP Address This is the IP Address of the device that provides SNTP Time synchronisation services. Devices are assigned to SNTP servers based on the contents of a configured SCL file. The IED/Access Point section of the SCL fil lists devices ing SNTP time synchronisation. This setting is editable in Manual Editing Mode. Use Anycast button This button automatically sets the SNTP Server IP address to the broadcast address of the Sub Network to which the MiCOM IED is connected. Using the SubNet broadcast address forces the IED to use the Anycast SNTP Mode of operation. This button is only enabled when the IED has a valid IP Address and SubNet Mask. This setting is editable in Manual Editing Mode.
6.12
EDITING DATASET DEFINITIONS
To edit a dataset definition, working offline: 1. Click the icon New MiCOM Configuration from an Installed ICD File. 2. Double-click the product variant. 3. Double-click the Dataset Definitions item. Or working online: 1. 2. 3. 4.
Select Device > Manage IED. Select the IED type device number. Select the IED address and click Next. The IED 61850 Configurator tool reads information from the IED and shows them in the Summary view. Click the Dataset Definitions tab.
P14D-B/G/L/Z-TM-EN-1
517
Chapter 12 - Settings Application Software
P14D
If ed by the IED, datasets can be dynamically defined. 1. 2. 3.
Right-click the Dataset Definitions icon and select Add New Dataset. or on the Dataset Definitions Summary page, in the Task pane, click Add Dataset. Find the dataset to be specified and click Set. A dataset can be created in any logical node of the IED's data model. The Dataset Definition appears listing Name, Location, Contents and GOOSE Capacity.
The following settings can be edited. Name The name of the dataset. This value is derived from the Dataset section of the selected logical node location in the configured SCL file. The initial character must be an alphabetic character (a-z, A-Z) while the remainder of the name can be either alphanumeric or the underscore symbol. The dataset name must be unique in the logical node where it is contained. Editable in Manual Editing Mode. Location The location of the dataset in the IED data model. The location is always read-only. To change the read-only status, click >>. Specify a new location for the dataset. Editable in Manual Editing Mode. Contents This shows the Functionally Constrained Data Attributes (FCDA) contained in the dataset. The ordering of these FCDA items in this list shows how values are seen over MMS communications. Using the following icons on the toolbar, FCDA items can be moved around, deleted or added. Toolbar Icon
Definition
Up & down arrows icon
These toolbar buttons move the selected FCDA up and down in the dataset definition.
Plus symbol
This toolbar button launches a dialog that allows you to select multiple FCDA items which can be added to the dataset definition. Items that can be selected have an outline tick symbol. Items that have been selected have a green tick symbol and are shown in the selection summary at the bottom of the dialog.
Minus symbol
This toolbar button removes the selected FCDA items from the dataset definition.
Square dot icon
For convenience a dataset can be defined from a ed Functional Constraint. This toolbar button expands the selected Functional Constraint into a list of Data Objects it contains. A dataset cannot contain both Data Objects and a Functional Constraint.
Rotating arrows icon
If the dataset is assigned to one or more control blocks (GOOSE), clicking this toolbar button automatically increments each control block's Configuration Revision. The Configuration Revision is used to identify changes to data, therefore this toolbar button is only enabled when the dataset definition is modified. If you change the selected configuration page and this toolbar button is enabled, you are asked if associated Configuration Revisions should be updated. Editable in Manual Editing Mode.
GOOSE Capacity. The size (in bytes) of a GOOSE message has an upper restriction. It can not be any larger than the maximum allowable size of an Ethernet frame. This restriction limits the maximum number of items that can be included in a dataset. The GOOSE Capacity gauge shows how large a dataset definition is with respect to GOOSE. If a dataset that is too large for transmission in a GOOSE message is assigned to a GOOSE Control Block, a validation warning appears. Read-only. To delete Dataset definitions, 1. 2.
518
Right-click the dataset definition icon. Select Delete Dataset.
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 12 - Settings Application Software
or 1. 2.
In the Dataset Definitions Summary page, select a dataset. In the task pane, click Delete Dataset.
To delete every dataset definition in the configuration data, click Delete All Datasets. Any references in GOOSE or Reporting Control Blocks to the deleted dataset remain unchanged. However, a validation warning appears stating that the dataset definition does not exist.
6.13
GOOSE PUBLISHING CONFIGURATION
Working offline: 1. Click the icon New MicOM Configuration from an Installed ICD File. 2. Double-click the product variant. 3. Double-click the GOOSE Publishing item. Or working online: 1. 2. 3.
Select Device > Manage IED, then select the IED type device number. Select the IED address and click Next. The IED 61850 Configurator tool reads information from the IED and shows them in the Summary view. Click the GOOSE Publishing tab. Then select a GOOSE Control Block (GoCB).
The following details can be edited. Multicast MAC Address Configures the multicast MAC address to that which the GoCB publishes GOOSE messages. The first four octets (01 – 0C – CD – 01) are defined by the IEC 61850 standard; leave these at their default values. The multicast MAC address is taken from the ConnectedAP/GSE section of the configured SCL file. Editable in Manual Editing Mode. Application ID Configures the AppID to that which the GoCB publishes GOOSE messages. The AppID is specified as a hexadecimal value with a setting range of 0 to 3FFF and is taken from the ConnectedAP/GSE section of the configured SCL file. Editable in Manual Editing Mode. VLAN Identifier Configures the VLAN (Virtual LAN) on to which the GOOSE messages are published. The VLAN Identifier has a setting range of 0 to 4095 and is taken from the ConnectedAP/GSE section of the configured SCL file. If no VLAN is used, leave this setting at its default value. Editable in Manual Editing Mode. VLAN Priority Configures the VLAN Priority of published GOOSE messages on the VLAN. The VLAN priority has a setting range of 0 to 7 and is taken from the ConnectedAP/GSE section of the configured SCL file. If no VLAN is used, leave this setting at its default value. Editable in Manual Editing Mode. Minimum Cycle Time Configures the Minimum Cycle Time between the first change-driven message being transmitted and its first repeat retransmission. The Minimum Cycle Time has a setting range of 1 to 50 milliseconds and is taken from the ConnectedAP/GSE/MinTime section of the configured SCL file. Editable in Manual Editing Mode. Maximum Cycle Time Configures the Maximum Cycle Time between repeat message transmissions under a quiescent 'no change' state. The Maximum Cycle Time has a setting range of 1 to 60 seconds and is taken from the ConnectedAP/GSE/MaxTime section of the configured SCL file. Editable in Manual Editing Mode. Increment Determines the rate at which the repeat message transmission intervals step up from the Minimum Cycle Time to the Maximum Cycle Time. The higher the number, the fewer the repeat messages (and therefore time) it takes to reach the Maximum Cycle Time. This setting is not taken from SCL. It is specific to MCL with a setting range of 0 to 999 and has no units. Editable in Manual Editing Mode.
P14D-B/G/L/Z-TM-EN-1
519
Chapter 12 - Settings Application Software
P14D
GOOSE Identifier Configures the 64 character GOOSE Identifier (GoID) of the published GOOSE message that is configured in the SCL file. The initial character must be alphabetic (a to z or A to Z) while the rest of the name can be either alphanumeric or the underscore symbol. The GOOSE Identifier must be unique for the entire system. This setting is taken from the LN0/GSEControl section of the configured SCL file. Editable in Manual Editing Mode. Dataset Reference Configures the dataset which is to be included in the GoCB's published messages. Only datasets that belong to the same logical node as the GoCB can be selected for inclusion in the GOOSE messages. If the dataset definition does not exist or is too large for publishing in a GOOSE message, a warning appears. This setting is taken from the LN0/GSEControl section of the configured SCL file. Right-click the Dataset Reference control to perform the following operations: ● Create and assign a new dataset definition. Only if the current dataset assignment is empty. ● Delete the current dataset assignment. Only if there is an assigned dataset. ● Edit the currently assigned datasets definition. Only if there is an assigned dataset. Editable in Manual Editing Mode. Configuration Revision Displays the Configuration Revision of the published GOOSE message. If the dataset reference or dataset contents are changed, the Configuration Revision must be incremented to allow other peers listening to the published GOOSE messages to identify the change in configuration. This setting has a range of 0 to 4294967295 and is taken from the LN0/GSEControl section of the configured SCL file. Editable in Manual Editing Mode. Any other IED in the system that needs to subscribe to the published GOOSE messages of the MiCOM IEDs must use the same value in its GOOSE subscription configuration.
6.14
GOOSE SUBRICRIPTION CONFIGURATION
Working offline: 1. Click the icon New MiCOM Configuration from an Installed ICD File. 2. Double-click the product variant. 3. Double-click the GOOSE Subscribing item. Or working online: 1. 2. 3. 4.
Select Device > Manage IED. Select the IED type device number. Select the IED address and click Next. The IED 61850 Configurator tool reads information from the IED and shows them in the Summary view. Click the GOOSE Subscribing tab.
Configuration of the GOOSE Subscription depends on whether the IED configuration has been compiled from a configured SCL file, from an MCL file or manually created. GOOSE Subscription is also based on two concepts. Mapped Inputs Applicable in all instances. A Mapped Input is an External Binding between two IEDs that is assigned to a valid Data Attribute in the IED data model (the internal Data Attribute s binding to an external value). For example, on a MiCOM Px40 device, a Mapped Input is an External Binding that has been assigned to a Virtual Input for use in Programmable Scheme Logic. Unmapped Inputs Primarily applicable to configured SCL files. An Unmapped Input is similar to the Mapped Input. It is an External Binding between two IEDs but the binding has not yet been assigned to a ing Data Attribute in the IED data model.
520
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 12 - Settings Application Software
For example, on a MiCOM Px40 device, an Unmapped Input is an External Binding that has been identified as necessary for the IED configuration but has not yet been assigned to a Virtual Input for use in Programmable Scheme Logic.
6.15
REPORT CONTROL BLOCK CONFIGURATION
Working offline: 1. Click the icon New MiCOM Configuration from an Installed ICD File. 2. Double-click the product variant. 3. Double-click the Report Control Blocks item. Or working online: 1. 2. 3. 4.
Select Device > Manage IED. Select the IED type device number. Select the IED address and click Next. The IED 61850 Configurator tool reads information from the IED and shows them in the Summary view. Click the Report Control Blocks tab. Then select a Report Control Block (RCB).
The following details can be edited. Report Type Displays the type of the selected RCB. Read-only. Report ID Configures the default Report ID of the RCB. Any clients wanting to use the RCB can override this default value if required. The initial character of the Report ID must be alphabetic (a to z or A to Z) while the rest of the name can be either alphanumeric or the underscore symbol. This setting is taken from the LN(0)/ ReportControl section of the required RCB in the configured SCL file. Editable in Manual Editing Mode. Dataset Reference Configures the dataset which is to be included in the generated reports from the RCB. Only datasets that belong to the same logical node as the RCB can be included in the reports. This setting is taken from the LN(0)/ReportControl section of the required RCB in the configured SCL file. Editable in Manual Editing Mode. Configuration Revision Displays the Configuration Revision of the RCB. If there are any changes to dataset reference or dataset contents, the Configuration Revision must be incremented to allow clients receiving the reports to identify the change in configuration. This setting is taken from the LN(0)/ ReportControl section of the required RCB in the configured SCL file. Editable in Manual Editing Mode.
6.16
CONTROLS CONFIGURATION
Working offline: 1. Click the icon New MiCOM Configuration from an Installed ICD File. 2. Double-click the product variant. 3. Double-click the Control Objects item. Or working online: 1. 2. 3. 4.
Select Device > Manage IED. Select the IED type device number. Select the IED address and click Next. The IED 61850 Configurator tool reads information from the IED and shows them in the Summary view. Click the Controls tab.
P14D-B/G/L/Z-TM-EN-1
521
Chapter 12 - Settings Application Software
P14D
The following details can be edited. ● Control Objects is the configuration of each Cotrol Object (Circuit Breaker Trip/Close control) in the IED's data model, for example its Control Model Direct Operate, Select Before Operate. This breaks down into: ▪ ctlModel This configures the control model (ctlModel) of the Control Object to one of the following predefined options and is is taken from the LN(0)/DOI/DAI/Val section of the ctlModel in the configured SCL file. Editable in Manual Editing Mode. Status Only DOns (Direct Operate - Normal Security) SBOns (Select-Before-Operate - Normal Security) DOes (Direct Operate - Enhanced Security) SBOes (Select-Before-Operate - Enhanced Security) ▪ sboTimeout If ed by the Control Object, this configures the Select Before Operate timeout. A client has the configured number of milliseconds to operate the control following the select command. If the Control Object is not operated in this time period, it is reset back to an unselected state. This setting is taken from the LN(0)/DOI/DAI/Val section of sboTimeout in the configured SCL file. Editable in Manual Editing Mode. ● Uniqueness of Control This adds a layer of security onto control operations by allowing only one Control Object to operate at any time in the whole system. Uniqueness of Control checks are performed using GOOSE, making it simple and reliable without any server redundancy.
6.17
EDITING MEASUREMENT CONFIGURATIONS
Working offline: 1. Click the icon New MiCOM Configuration from an Installed ICD File. 2. Double-click the product variant. 3. Double-click the Measurements item. Or working online: 1. 2. 3. 4.
Select Device > Manage IED. Select the IED type device number. Select the IED address and click Next. The IED 61850 Configurator tool reads information from the IED and shows them in the Summary view. Click the Measurements tab. Then Select a measurement object.
The following details can be edited. Unit multiplier If ed by the IED, this configures how the measurement value will be scaled when read by or reported to a client. The multiplier is shown in the following table. Value
Multiplier
Name
Symbol
-24
10–24
Yocto
y
-21
10–21
Zepto
z
-18
10–18
Atto
a
-15
10–15
Femto
f
-12
10–12
Pico
p
-9
10–9
Nano
n
-6
10–6
Micro
?
-3
10–3
Milli
m
-2
10–2
Centi
c
522
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 12 - Settings Application Software
Value
Multiplier
-1
10–1
0
1
1
Name
Symbol
Deci
d
10
Deca
da
2
102
Hecto
h
3
103
Kilo
k
6
106
Mega
M
9
109
Giga
G
12
1012
Tera
T
15
1015
Petra
P
18
1018
Exa
E
21
1021
Zetta
Z
24
1024
Yotta
Y
For example, if the phase A current is 1250 amps and the multiplier is kilo (k), the relay measures 1.250 (kA). Editable in Manual Editing Mode. Scaled Measurement Range Min/Max If ed by the IED, this configures the minimum and maximum values of a measurement object. The min and max values are used with the deadband value to calculate how much a measurement must change to be updated or reported to a client. Editable in Manual Editing Mode. Deadband This configures the deadband, which is a percentage change based on the measurements range in units of 0.001% (giving a range of 0 to 100000). A deadband of 0 means the measurement is updated instantaneously. To simplify the calculation process, click the >> button. Specify the deadband as a percentage change (such as 5%) or as an absolute change (such as 0.1 Hz). Editable in Manual Editing Mode. The deadband can be specified at any level in the Measurements tab. The range, including the multiplier, can only be specified at a level where all measurement objects are of the same type. For example, all phase current measurements.
6.18 1. 2. 3.
EDITING CONFIGURABLE DATA ATTRIBUTES
4.
Select Device > Manage IED. Select the IED type. Select the IED address and click Next. The IED 61850 Configurator tool reads information from the IED and shows them in the Summary view. Click the Configurable Data Attributes tab.
5.
Select a Data Attribute.
The following details can be edited. Data Type This shows the SCL Data type of the Data Attribute. The data type influences the type of control used to represent the Data Attributes value. ● Integer based types use a numeric up-down control to specifiy the value. ● Enumerated types use a combo box to specify the available setting values. ● String types use a text box to allow text entry. Read-only. Value This is the value to assign to the Data Attribute and is taken from the LN(0)/DOI/DAI/Val section of the required Data Attribute in the configured SCL file. Editable in Manual Editing Mode.
P14D-B/G/L/Z-TM-EN-1
523
Chapter 12 - Settings Application Software
6.19
P14D
FULL VALIDATION OF IED CONFIGURATION
The IED Configurator can be used to validate configured SCL files against the SCL schema when they are opened. It can also validate an IED's MCL configuration at any time. 1. 2.
3.
6.20
In the SCL Explorer workspace, right-click a MiCOM IED and click Validate. The selected MiCOM IED is validated and the results appear in a Validation Log window. The log shows three levels of classification: ▪ Information. No actions required. ▪ Warning. Some consideration may be required. ▪ Error. IED may not function as expected with current configuration. Double-click a warning or error item. The configuration page that generated the log entry appears. Double clicking information entries has no effect.
VALIDATION SUMMARIES
1. 2. 3.
Select Device > Manage IED. Select the IED type device number. Select the IED address and click Next. The IED 61850 Configurator tool reads details from the IED and shows them in the Summary view. 4. Select a category tab. A summary of each the configuration appears in the Summary pane. Doubleclick an item and a list of log entries appears in the Validation Report pane. The following log entries can be edited. SNTP Summary. This shows all the server sources available for configuration in the IED. If a server source is configured, it is shown in bold. Also the IP address of the external time synchronisation server is shown. If a server source is unconfigured, it is shown greyed. Dataset Definitions Summary. This shows all the datasets defined throughout the IED's data model. For each defined dataset, its number of Functionally Constrained Data Attributes is also shown. The summary page includes a common set of tasks to manage the dataset definitions. GOOSE Publishing Summary. This shows all of the GOOSE Control Blocks (GoCB) available in the IED. If a GoCB is fully configured, it is shown in bold. A partially configured GoCB is shown in normal typeface. If a GoCB is unconfigured, it is shown greyed. GOOSE Subscribing Summary. This shows all of the Virtual Inputs available in the IED. If a Virtual Input is fully configured, it is shown in bold. A partially configured Virtual Input is shown in normal typeface. If a Virtual Input is unconfigured, it is shown greyed. Any unmapped inputs are listed in an additional summary. Report Control Block Summary. This shows all of the Report Control Blocks (RCB) available in the IED. If an RCB is fully configured, it is shown in bold. A partially configured RCB is shown using in normal typeface. If an RCB is unconfigured, it is shown greyed. Control Objects Summary. This shows all of the Control Objects available in the IED's data model, and what their configured control model is (Direct Operate, Select Before Operate). Uniqueness of Control Summary. This shows all of the Virtual Inputs available in the IED. If a Virtual Input is fully configured, it is shown in bold. A partially configured Virtual Input is shown in normal typeface. If a Virtual Input is unconfigured, it is shown greyed. Any unmapped inputs are listed in an additional summary. Measurements Summary. The Measurements summary shows all of the Measurement Objects available in the IED's data model, plus their configured range and deadband. Configurable Data Attributes Summary. The Configurable Data Attribute summary shows all of the Configurable Data Attributes available in the IED's data model, plus their data type and configured value.
524
P14D-B/G/L/Z-TM-EN-1
P14D
6.21
Chapter 12 - Settings Application Software
MANAGING SCL SCHEMA VERSIONS
The IEC 61850 IED Configurator s several versions of the SCL schema. This improves its reliability and correctly validates any version of SCL file. The schema files are not available and are encoded into a proprietary binary format that allows basic version control management by the IEC 61850 IED Configurator tool. Existing schema versions can be removed or new versions added. 1. 2. 3. 4.
Select Tools > Options. Click the General tab. Click the Manage Schemas button. New schema versions are provided in a binary distribution file. Click a schema and its details are shown in the left-hand pane.
To add a new SCL Schema: 1. 2.
In the left-hand pane, click Add New SCL Schema then search for the binary schema distribution file. Click Open to import the file. The IEC 61850 IED Configurator merges all schema versions in the distribution file into the application repository. If a schema version is already available in the application repository it is skipped.
To remove an SCL Schema: 1.
6.22
In the right-hand pane, right-click a schema and select Remove Schema File. This removes the selected SCL schema from the application repository. The operation cannot be undone.
CONFIGURATION BANKS
In the MiCOM IED there are two configuration banks for IEC 61850 configuration. The configuration bank concept is similar to that of setting groups for protection settings, promoting version management and helping to minimise IED down-time during system upgrades and maintenance. To view an IED's configuration bank details: 1. 2. 3.
Establish a connection to the MiCOM IED. Select Device > Manage IED. If the connection to the MiCOM IED is successful , the Manage IED window appears showing the details of the Active and Inactive configuration banks.
The following configuration banks can be edited. Switch banks button. This toggles the IED's configuration banks so the Active Bank becomes inactive and the Inactive Bank becomes active. The switching technique used ensures the system down-time is minimised to the start-up time of the new configuration. Refresh banks button. This forces the IEC 61850 IED Configurator tool to refresh the details displayed for the Active and Inactive configuration banks. It is especially useful if, for example, configuration banks have been toggled directly on the IED. Extract ICD file button. This button is only enabled for IEDs that hold their own local copy of their ICD template file. Press this button to define where the ICD template file that is contained in the IED should be saved. After the ICD template is extracted, it can be made available as an Installed template. Extract configuration buttons. These buttons extract the appropriate configuration bank and open it for viewing or editing in a new window.
P14D-B/G/L/Z-TM-EN-1
525
Chapter 12 - Settings Application Software
6.23
P14D
TRANSFER OF CONFIGURATIONS
The IED Configurator tool can be used to transfer configurations to and from any ing MiCOM IED. If you send a configuration to a ing MiCOM IED, it is automatically stored in the Inactive configuration bank. It therefore does not immediately affect the current Active configuration. To send a configuration to a MiCOM IED: 1. 2. 3.
6.24
Establish a connection to the MiCOM IED. Select Device > Send Configuration. The IED Configurator tool checks the compatibility of the IED model number. It then transfers the configuration to the IED.
EXPORTING INSTALLED ICD TEMPLATE FILES
Any installed ICD template file can be exported by the IEC 61850 IED Configurator tool to a -defined location. 1. 2. 3.
6.25
Select Tools > Export Installed ICD File. The Template dialog appears. Select the MiCOM IED type for which the template file is to be exported. Click the Select button. Specify the location and filename of the ICD template file being exported.
EXPORTING CONFIGURED SCL FILES
Any IED configuration in an Editor window can be exported to a configured SCL file, if it has not been opened for restricted editing. To export a configured SCL file, the IED Configurator tool needs the IED's ICD template file. 1. In an Editor window, select Tools > Export Configuration to SCL. 2. Select the MCL configuration file which is to be exported. 3. Specify the destination filename for the configured SCL file. Configuration items that are specific to MCL are not exported. This is because the information is not ed by the SCL schema. It is therefore important to save the configuration in an MCL file. The main reason for exporting configured SCL files is to allow configuration information to be shared between multiple SCL/IED configurator tools. This is for the configuration of, for example, GOOSE message exchange.
526
P14D-B/G/L/Z-TM-EN-1
P14D
7
Chapter 12 - Settings Application Software
DNP3 CONFIGURATOR
DNP3 (Distributed Network Protocol) is a master/slave protocol developed for reliable communications between various types of data acquisition and control equipment. It allows interoperability between various SCADA components in substations. It was designed to function with adverse electrical conditions such as electromagnetic distortion, aging components and poor transmission media. The DNP3 Configurator allows you to retrieve and edit its settings and send the modified file back to a MiCOM IED.
7.1
PREPARING FILES OFFLINE TO SEND TO AN IED
To prepare files, it is not necessary to connect to an IED. 1. 2. 3. 4. 5. Or
Select the IED type. Click the DNP3 Settings File tile. Click Open Default File. Select the IED from the list and click Next. Type or select a model number and click Finish. The Default DNP3 Settings screen appears.
1. From the main screen, select File > Open File > Px40 > DNP3 Settings File. 2. Select the IED file from the list and click Open. Then 1. 2. 3. 4.
7.2
Expand the Explorer view and double click an item. The left-hand column shows a list of available Master Points. Using the buttons, add or remove items from the left-hand column to list of Configured Points in the right-hand column. Right-click any Configured Point in the right-hand column for further settings. Click OK.
SEND SETTINGS TO AN IED
To send settings to a device, connect the PC to the IED and select the communication port. See Getting Started (on page 499). There must be at least one setting file in a settings folder for a device. 1. 2. 3. 4. 5.
7.3 1. 2. 3. 4.
From the main screen, select View > System Explorer. Expand the view to see the required device. Right-click the device name and select Send. In the Send to... dialog, select the setting files and click Send. Click Close.
EXTRACT SETTINGS FROM AN IED From the main screen, select View > System Explorer. Expand the view to see the required device. Right-click the device name and select Extract Settings. To exrtract all settings select Extract Full Settings then Yes. Click Close.
P14D-B/G/L/Z-TM-EN-1
527
Chapter 12 - Settings Application Software
7.4 1. 2.
528
P14D
VIEW IED SETTINGS Under System, Substation, Voltage Level, Bay, Device, DNP3, double-click the New System. In the left-hand pane, expand the DNP3 Over Ethernet properties.
P14D-B/G/L/Z-TM-EN-1
P14D
8
Chapter 12 - Settings Application Software
CURVE TOOL
The Programmable Curve Tool (UPCT) allows you to create -defined curves and to and these curves to and from the Px4x range of IEDs. You can use this tool to create programmable overcurrent and overfluxing operating and reset curves. Its -friendly interface lets you easily create and visualize curves either by entering formulae or data points.
8.1
FEATURES
The Curve Tool allows you to: ● ● ● ● ● ● ● ● ● ● ● ●
8.2
Create new configuration curve files or edit existing curve files Enter a defined number of curve points or a -defined formula Create and save multiple formulae Associate the -defined curve with a predefined curve template Interpolate between curve points Save curve formulae in XML format and configure curve points in CSV format, enabling easy data exchange Save configured curve data in CRV format, suitable for into the IED Easily of the curve data from an IED Input constants with -defined values Graphically display curves with zoom, pan, and point-on-curve facilities Colour code multiple curves to allow effective comparison Print curves or save curves in a range of standard image formats
SCREEN LAYOUT
The curve selection table and Curve Plot are in the right-hand panes. The Curve Details, Curve Points, Input Table View and Product View are in the left-hand-panes. To change the width of the left- and right-hand panes, drag the vertical border between them.
8.3
CURVE SELECTION PANE
To open an existing curve: 1. 2. 3.
8.4
Select File > Open Curve. You can open several curves and the Curve Selection pane has a list of those available. As you import or create more curves, they appear as rows in the table. Check the checkbox to select a curve and the corresponding row is then highlighted. Selecting the curve displays it in the Curve Plot pane and makes it available for or . Select View > Show Curve Details to view the Curve Details.
CURVE PLOT PANE
The Curve Plot pane displays the curves showing time on the y-axis and Q (multiples of nominal current) on the x-axis. This is the standard method of defining protection IED configuration curves. Right-click anywhere in the Curve Plot pane to carry out a range of flexible operations on the curves from the context sensitive menu. Operations include copying the image, zooming, panning and printing. Images can be saved as PNG, GIF, JPEG, TIFF or BMP. Right-click any point on the plot and select Show Point Values to show the Q and T values at that point.
P14D-B/G/L/Z-TM-EN-1
529
Chapter 12 - Settings Application Software
8.4.1
P14D
ZOOMING AND PANNING
To zoom in, drag a box around the area using the mouse. To pan, click and hold the left mouse button while holding the shift key and move the mouse in the relevant direction. To un-zoom or un-pan, right-click the Curve Plot and select Un-zoom or Un-pan. To revert to the original view, right-click the Curve Plot and select Undo All Zoom/Pan.
8.4.2
SCALES AND GRID LINES
To change the scales: 1. Select Graph Options. 2. Select X-Axis Scale or Y-Axis Scale. 3. Select logarithmic or linear. To change the grid lines: 1. 2.
8.5
Select Graph Options > Grid Lines. Select Major Grid Lines or Minor Grid Lines to show the grid lines in a coarse or fine scale.
CURVE DETAILS PANE
To show further details about the curves, select View > Show Curve Detail. In the Curve Details pane you can define the name and description of the curve. You can enter a string up to 16 standard ASCII characters. If you do not enter a name, the default name New Curve is used. The formula name and template version are also displayed if applicable. To close the Curve Detail dialog, click the X in the right-hand corner. To auto-hide the Curve Detail, click the icon next to the cross. This shows the plot full size and only shows the curve detail when you position the cursor in the marked area in the left-hand margin.
8.6
CURVE POINTS PANE
The Curve Points pane has three columns Index. Each curve point has a unique index number associated with it, starting at 0, incrementing by 1 and ending with the last curve point. Q (multiples of setting). Q, in this context stands for Quantity. It is the secondary current Is, expressed in multiples of the nominal current In. T (Time in secs). T is the imposed delay time, expressed in seconds.
8.6.1
ENTERING VALUES OF Q AND T INTO THE TABLE
To input values for Q and T to define a table: 1. 2.
Select File > New > Input Table. Insert the values for Q and T up to a maximum of 256 curve points (index 0 to 255). The tool instantaneously updates the graph view as points are entered. If fewer points are inserted, the tool automatically interpolates points using linear interpolation. To copy and paste an entire table from Excel or other compatible table formats: 1. 2.
530
Copy the table to the clipboard. Position the cursor in the top left-hand Q cell and paste.
P14D-B/G/L/Z-TM-EN-1
P14D
8.7
Chapter 12 - Settings Application Software
INPUT TABLE VIEW
This allows you to show show or hide the curve and its associated points. It also allows you to choose the colour of the plotted curve.
8.8
PRODUCT VIEW
This allows you to select a curve template from the Px40 product range. You can choose whether or not to plot the product curve and its points. This pane also allows you to choose the colour of the plotted product curve.
8.9 1. 2. 3.
4. 5. 6. 7. 8.
9. 10.
FORMULA EDITOR To open the Formula Editor select View > Show Formula Editor. Enter the formula in the T= field. The formula is case sensitive, use only uppercase letters. Select the required template from the Curve Template dropdown box. The curve you are creating with the formula must be associated with a predefined template. This must match the template of one of the curves stored in the IED. The template defines a curve with a specific spread of points which can be ed to the IED. Enter the formula name into the Formula Name field. This can be any combination of standard ASCII characters up to 32 characters. If you need a Definite Time characteristic, check the DMT (Definite Minimum Time) checkbox. Then enter fixed values for the tripping current multiplier (Q) and the delay time (T). You can enter any constants into the formula and the first eight letters of the Greek alphabet are included in the formula editor as buttons. Click a button to enter the character in the Formula field. Input the formula constants into the Value column. To validate the formula, click the Formula button at the bottom left corner of the screen. The names of the constants used in the formula are shown in the Input Constants table. The formula verifier checks the operators are valid but does not check if the formula is valid or if the results are out of range. Select the Options tab, click Save As and enter a file name. The file is saved in XML format. Enter up to 16 standard ASCII characters. Once the constants are entered and the file is saved, click the Generate Curve button (next to the Formula button) to generate a curve. The curve appears in the Curve Plot pane.
Allowed Formula Editor operators Operators
Description
+
Plus
-
Minus
*
Multiply
/
Divide
^
Raise to the power of
sqrt()
Square Root
ln()
Natural logarithm
Sin
Sin function
Cos
Cos function
Tan
Tan function
P14D-B/G/L/Z-TM-EN-1
531
Chapter 12 - Settings Application Software
8.10
P14D
CURVE TEMPLATE DEFINITIONS
Many protection functions use a graphical curve to define their Operate and Reset characteristics. These are inverse curves with current on the x-axis and time on the y-axis and each curve has 256 points. In the Phasor tool, the curves created with the formula or points table must match the templates of their respective curves stored in the IED. Each curve is defined by 256 points with a specific spread of the points in different areas of the curve. The following are examples of Curve Tool templates. Curve tool templates Template
Description
Overcurrent Operate
Overcurrent protection IDMT operate curve
Overcurrent Reset
Overcurrent protection IDMT reset curve
Thermal Overload Operate
Thermal overload protection operate (heating) curve
Thermal Overload Reset
Thermal overload protection reset (cooling) curve
Undervoltage Operate
Undervoltage protection operate curve
The curve templates have a clearly defined number of graphical points to define certain portions of the curve. The following tables are examples of template definitions. Overcurrent operate Range
Number of points
Range 1: 1x to 3x setting
128
Range 2: 3x to 32x setting
116
Range 3: 32x to 76x setting
12
Overall range
256
Overcurrent reset Range
Number of points
Range 1: 1x to 0.96x setting
116
Range 2: 0.96x to 0.7x setting
128
Range 3: 0.7x to 0x setting
12
Overall range
256
Thermal overload operate Range
Number of points
Range 1: 1x to 4x setting
150
Range 2: 4x to 5x setting
68
Range 3: 5x to 10x setting
32
Range 4: 10x to 32x setting
6
Thermal overload reset Number of points
Range Range 1: 1x to 0.96x setting
116
Range 2: 0.96x to 0.7x setting
128
532
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 12 - Settings Application Software
Range
Number of points
Range 3: 0.7x to 0x setting
12
Overall range
256
8.11
CONNECTING TO AN IED
Depending on the model, the MiCOM IEDs will have one or more of the following ports to which you can connect to in order to transfer curve files: ● Front USB ● Front serial ● Rear RS485 ● Rear Ethernet The front port is a temporary local connection used to set up the IED. The rear serial port is typically used for multi-drop SCADA. The Ethernet port runs at 10/100 Mbps and is typically used for network SCADA. To configure the communication settings for ing and ing the curves to and from the IED 1. 2. 3.
Select Device > Connection Configuration. The Edit Connection dialog appears. In the Scheme dropdown box, select which port to configure. Click the Transaction Values tab. These are the default values. If you make changes and need to revert to the default settings, click the Restore Defaults button.
The following is a list of transaction values and their definitions Busy Hold-off Time (ms). The time interval used by Courier between receiving a BUSY response and sending a subsequent POLL BUFFER command. Busy Count. The maximum number of BUSY responses that will be accepted for a single Courier transaction before aborting the transaction. To cope with abnormal situations where a device is not replying correctly to requests, a limit is placed on the number of BUSY responses that should be accepted. Without this limit the link to the device would be stuck in a loop. Reset Response Time (ms). The maximum time from a sending the last byte of a Courier Reset Remote Link message to receiving the first byte of a response. When that time has elapsed the request is aborted. Response Time (ms). The maximum time from a sending the last byte of a Courier message to receiving the first byte of a response. When that time has elapsed the request is aborted. The Response Time parameter is used for all messages except Courier Reset Remote Link messages. Try Count. The number of tries before aborting the request. Transmit Delay Time (ms). The minimum delay that is put between receiving a response and transmitting the next request. Transmit delay is normally set to zero but can be set to a few milliseconds when using half duplex communication. This gives the other end of the link time to change from transmitting to receiving. Global Transmit Time (ms). The minimum delay that is put between transmitting a global message and the next transmission.
8.11.1
CONNECTING TO A SERIAL PORT
If you connect to a serial port, the Serial tab appears. 1. 2.
Click the Serial tab. The fields are already populated with the default settings. Enter the Relay Address. This is an integer which represents the Courier address of the IED.
P14D-B/G/L/Z-TM-EN-1
533
Chapter 12 - Settings Application Software
8.11.2
P14D
CONNECTING TO THE ETHERNET PORT
If you connect to the Ethernet port, the Ethernet tab appears. 1. 2. 3. 4.
8.12 1.
2. 3. 4. 5. 6.
8.13 1. 2.
534
There is no DH so you must know the IP address and enter it manually. The T port can be dynamic or static. If you need a static T port, check the Use fixed incoming T port checkbox and enter the Fixed incoming port number. If the device is attached to a bay unit, click the Device is attached to a bay unit checkbox. Then select from the Bus Address dropdown box. Enter the Relay Address. This is an integer which represents the Courier address of the IED.
SEND A CURVE TO AN IED To open an existing curve, select File > Open Curve. You can open several curves and the Curve Selection pane has a list of those available. As you import or create more curves, they appear as rows in the table. Check the checkbox to select a curve and the corresponding row is then highlighted. Selecting the curve displays it in the Curve Plot pane and makes it available for or . Click the Device tab and select Send Curve. The Send Curve Form appears. The IED stores several curve characteristics. In the Curve Characteristic dropdown box, select which curve you want to overwrite. Click Send to send the curve to the IED then click Get Curve Ref. Check the PC Curve Value is the same as the Relay Curve Value. This shows that the send has been successful because it overwrites the existing Relay Curve Value.
EXTRACT A CURVE FROM AN IED Select Device > Extract Curve. Select File > Save > Input Table View to save the curve file in CSV format or select File > Save > Product View to save the curve file in CRV format.
P14D-B/G/L/Z-TM-EN-1
P14D
9
Chapter 12 - Settings Application Software
S&R COURIER
Settings and Records - Courier enables you to connect to any Courier device, retrieve and edit its settings and send the modified settings back to a Courier device, including DNP 3.0 configuration if ed by the device. Although each device has different settings, each cell is presented in a uniform style, showing the permissible range and step size allowed. Settings and Records - Courier also enables you to: ● ● ● ● ● ● ●
9.1 1. 2. 3.
9.2 1. 2.
extract events from a device extract disturbance records from a device control breakers and isolators set date and time on device set active group on device change the address of a device save settings, DNP 3.0 configuration, events and disturbance files to disk
SET UP IED COMMUNICATION Select Device > Communications Setup. The Communications Setup dialog appears. If the configuration you want to use already exists, select it from the Scheme drop-down list and click OK. If the configuration you want to use does not exist, create a new communications setup.
CREATE A NEW COMMUNICATION SETUP Select Device > Communications Setup. The Communications Setup dialog box appears. Select the connection: Serial, Modem or Internet.
If using a serial connection, 1. 2. 3.
Select the Serial tab. In the COM Port drop-down list, select the serial port to which the device will be connected. Select the Baud rate and Framing.
If using a modem, 1. 2.
Select the Modem tab. Click Configure… to enter the phone number.
Then for all connection types, 1. 2. 3. 4.
Select the Transaction Values tab and complete the fields. Click Save As. Enter a name in the Save Communications Parameters As field and click OK. Click OK to configure the communications port.
P14D-B/G/L/Z-TM-EN-1
535
Chapter 12 - Settings Application Software
9.3 1. 2. 3. 4. 5.
P14D
OPEN A CONNECTION Select Device > Open Connection. If known, enter the device address in the Address field, otherwise click Browse to scan available devices. Click OK to open the connection. Enter the using four alphabetic characters. Click OK. If the is valid, the connection is made and the On-line window appears.
Note: If the device is set to the default , the Enter dialog is not needed for enhanced DNP 3.0 devices.
9.4 1. 2. 3. 4.
5. 6.
9.5 1. 2. 3. 4. 5. 6.
9.6 1. 2. 3.
9.7 1. 2. 3. 4.
536
CREATE A NEW OR DEFAULT IED DNP 3.0 FILE Select File > New. Select DNP File. The New DNP 3.0 File dialog appears. Select the required device type from the Device Type drop-down list. The model numbers for the device type are displayed. Select the model number from the Model Number list or use the Advanced button to construct the required model number. If duplicate model numbers exist, the Header details give version numbers and other identifying information. The appropriate language is displayed in the Language drop-down list, showing the language of the file. If more than one language type is ed, the Language drop-down list shows the languages for the device type. Click OK. A new DNP 3.0 file is generated, based on the selected model.
EXTRACT A SETTINGS FILE FROM A DEVICE Select Device > Open Connection to open a connection to the required device. In the Online Device window, right-click the device name. Select Send To > New Settings File. The New Settings File dialog appears. Select the device model number. Click OK. Once the extraction is complete, a window appears showing the settings.
SAVE A SETTINGS FILE Select File > Save As. Edit the File Name or Header fields as required. Click Save.
SEND A SETTINGS FILE TO A DEVICE Open a connection to the required device. Make sure the destination file is in the active window. Select File > Send To Click the appropriate device.
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 12 - Settings Application Software
10
AEDR2
AutoExtract Disturbance Records 2 (AEDR2) automatically reads COMTRADE disturbance records from the rear communication ports of both K-Series and MiCOM Px40 devices with the Courier protocol, and from Px40 or Px30 devices with the IEC 60870‑5‑103 protocol. AEDR2 is configured with an initialisation file. This file contains all settings, file names and file directories needed for configuration. This file can be created and edited using a standard text editor. Log files are also defined in the initialisation file which are used by AEDR2 to record a history of events and errors. Once configured, disturbance records are automatically extracted according to a schedule from devices connected in a defined range of addresses. This is done using the Windows® Scheduled Task facility which can be used to execute one or several schedules. All new disturbance records are saved to a -defined drive and filename. AEDR2 also has a test function to ensure the initialisation file has been properly configured. The command line is used to execute the test function and validate the initialisation file. The command line can also be used to manually execute the AEDR2 application on demand. WinAEDR2 is a management facility for AEDR2. It shows the history of all previous extractions and has shortcut buttons to launch WaveWin, Windows Explorer and the Scheduled Task facility. It can also be used to view log files, and edit and test the initialisation file.
10.1
INITIALISATION FILE
First of all you need to create or edit the initialisation file (AEDR2.INI) with a text editor such as Microsoft® Notepad. It needs to be configured for each application and for the communication requirements of the connected devices. The AEDR2.INI file contains 3 sections: the common section headed [AEDR2], the Courier section headed [Courier] and the IEC 60870-5-103 section headed [IEC-103]. Section entries are only included when nondefault values are needed.
10.1.1
COMMON SECTION Function
Description
Values
Default
ErrorLogFileName
Filename of Error Log
Valid filename
1
Error.log
ExtractionLogFileName
Filename of Extraction Log
Valid filename
1
Extraction.log
StatusLogFileName
Filename of Status Log
Valid filename
1
Status.log
ComtradeName
Used to create Comtrade short filenames
Part of valid filename
2
DR
ComtradeDir
Where to store the resulting Comtrade files
Valid directory
1
empty
ComtradeFormat
Defines Comtrade format
1991 or 1999
ReportMissingDevices
1 indicates that any device not found between MinAddress and MaxAddress is reported as "not found" in the Error Log
0 or 1
3
0
LongFileNames
1 indicates Comtrade long filenames
0 or 1
4
0
LFN_TCode
For long filenames, defines the Time Zone with respect to UTC
Valid time zone
LFN_Substation
For long filenames, the substation name or code where the Part of valid filename originating device is located
P14D-B/G/L/Z-TM-EN-1
1999
0z empty
537
Chapter 12 - Settings Application Software
Function
P14D
Description
Values
The company of the specified substation
LFN_Company
Default
Part of valid filename
empty
Use full pathnames for files or directories (e.g. "C:\Directory\SubDir"). If relative paths are used, they are assumed to be relative to the directory in which the applications are installed. Short filenames use the following format: DEV_XX_TIMESTAMP
DEV identifies the device – C for Courier or I for IEC 60870-5-103 followed by the 3-digit device address. For example 061001,231941657,0z,South Park,C001,Stafford Power,,,,.DAT XX denotes the value of the ComtradeName key TIMESTAMP expresses the date and time when the disturbance was recorded, in the format YYYY-MMDD--HH-MM-SS. For example, C001_DR_2006-10-01--23-19-41.DAT Function
Value
ReportMissingDevices LongFileNames
10.1.2
Description
0
Missing devices are not reported as errors.
1
Arrange all device addresses consecutively without gaps.
0
Records are saved using the short file name format.
1
Records are saved using the long file name format as defined by the IEEE.
COURIER SECTION Key
Purpose
Values
Default
MinAddress
Minimum device address
1 to 254
1
empty
MaxAddress
Maximum device address
1 to 254
1
empty
CommPort
Which COM port to use
Valid COM port
2
COM1
BaudRate
Baud rate to use
Valid baud rate
ElevenBits
Ten or Eleven bits
0 or 1
BusyHoldoff
Standard Courier parameter
Integer
50
BusyCount
ditto
Integer
100
ResetResponse
ditto
Integer
100
Response
ditto
Integer
100
TryCount
ditto
Integer
3
TransmitDelay
ditto
Integer
5
GlobalTransmit
ditto
Integer
10
UseModem
Whether to use a Modem
0 or 1
0
TAPI_ModemName
Modem Name
String
empty
TAPI_LineAddress
Line Address
Integer
0
TAPI_NumberToDial
Number to Dial
String
empty
TAPI_UseCountryAndAreaCodes
Whether to use Country/Area codes
Integer
0
API_AreaCode
Area Code to dial
String
empty
TAPI_CountryCode
Country Code to dial
String
empty
538
9600 3
1
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 12 - Settings Application Software
Key
Purpose
Values
Defines which devices (if any) uses Secondary Port extraction
SecondaryPort
Default
ALL or NONE or a sequence of numbers e.g. 1,4,77,12
4
NONE
The MinAddress and MaxAddress entries must either be both included or both omitted. If included, MaxAddress must be greater than MinAddress. All Courier addresses between MinAddress and MaxAddress (inclusive) are tried. If omitted, no Courier address is tried. Both Courier and IEC 60870-5-103 disturbance extraction can use the same COM port. This is because all Courier devices are polled first, each time the AEDR2 application runs, followed by all IEC 60870-5-103 devices. If ElevenBits = 0, serial data is set to 1 start bit, 8 data bits, no parity and 1 stop bit. If ElevenBits = 1, serial data is set to 1 start bit, 8 data bits, even parity and 1 stop bit. Secondary Port Extraction means the disturbance records can be read from the device but not deleted. Primary Port Extraction means that disturbance records are deleted from the device once read. The value SecondaryPort can be set in one of three ways: ● NONE All devices are connected using their primary port. ● ALL All devices use the secondary port mechanism. ●
10.1.3
IEC 60870-5-103 SECTION Key
Purpose
Possible Values
Default
MinAddress
Minimum device address
0 .. 254
1
empty
MaxAddress
Maximum device address
0 .. 254
1
empty
CommPort
Which COM port to use
Valid COM port
COM1
BaudRate
Baud rate to use
Valid baud rate
9600
ElevenBits
Ten or Eleven bits
0 or 1
2
1
DModDirectory
Defines where the DMod directory is found
Valid directory
3
see note
LeaveInDevice
Defines which devices (if any) have disturbance records left in
ALL or NONE or a sequence of numbers e.g. 1,4,77,12
4
NONE
ComtradeDataFormat
Defines the Comtrade data format
BINARY or ASCII
ASCII
The MinAddress and MaxAddress entries must either be both included or both omitted. If included, MaxAddress must be greater than MinAddress. All IEC 60870-5-103 addresses between MinAddress and MaxAddress (inclusive) are tried. If omitted, no IEC 60870-5-103 address is tried. If ElevenBits = 0, serial data is set to 1 start bit, 8 data bits, no parity and 1 stop bit. If ElevenBits = 1, serial data is set to 1 start bit, 8 data bits, even parity and 1 stop bit.
P14D-B/G/L/Z-TM-EN-1
539
Chapter 12 - Settings Application Software
P14D
The DModDirectory value defines where the DMod files are. This is used for the descriptions of the signals in the disturbance records. The default directory is: C:\Program Files\Alstom Grid\MiCOM S1 Agile\S&R-103\DMod "Leave in Device" means that the disturbance records can be read from the device but not deleted. Otherwise, disturbance records are deleted from the device once read. The value LeaveInDevice can be set in one of three ways: ● NONE (all records are extracted and deleted) ● ALL (no records will be deleted from devices) ●
10.1.4
IEC 60870-5-103 SECTION
[AEDR2] ErrorLogFileName = TestError.log ExtractionLogFileName = TestExtraction.log StatusLogFileName = TestStatus.log ComtradeDir = C:\Project\AEDR2\WinAEDR2 ReportMissingDevices = 1 LongFileNames = 1 LFN_Substation = "South Park" LFN_Company = "Stafford Power" ComtradeFormat = 1999 [Courier] CommPort = COM1 BaudRate = 19200 ElevenBits = 1 MinAddress = 1 MaxAddress = 2 SecondaryPort = 1,3,5 [IEC-103] CommPort = COM1 BaudRate = 115200 ElevenBits = 1 MinAddress = 1 MaxAddress = 2 LeaveInDevice = ALL DModDirectory = C:\Program Files\Alstom Grid\MiCOM S1 Agile\S&R-103\DMod ComtradeDataFormat = ASCII UseModem = 0 TAPI_ModemName = Standard 56000 bps Modem TAPI_NumberToDial = 01223503445
10.2
IEC 60870-5-103 SECTION
The PC running AEDR2 can be connected to either to the Rear Port 1 or the Rear Port 2 (if fitted) of a Courier device. AEDR2 can not be used with the front port of Px40 IEDs. Rear Port 1 allows the disturbance records to be extracted or saved. Rear Port 2 can only save disturbance records. Extracted records are saved to the local PC then deleted from the device. Saved records are copied to the local PC but not deleted from the device. AEDR2 can extract or save disturbance records from IEC 60870-5-103 devices. It maintains a list of previously extracted records so it can only extract such records once. Devices using IEC 60870-5-103 and Courier use a single direct connection to the same or different COM ports. Devices using
540
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 12 - Settings Application Software
Courier can also connect using a modem link. AEDR2 can run on more than one COM port but it needs to be run separately for each, with each port or modem using its own initialisation file.
10.3
OPERATION
AEDR2 scans all the Courier and IEC 60870-5-103 device addresses in a specified range. If it does not find a device at an address it goes to the next address. You only need to specify the lowest and highest addresses, even if there are devices missing in the sequence. AEDR2 does not keep a list of known devices. Each time it runs, it scans all addresses in the specified range. You can add new devices or remove existing devices and AEDR2 extracts disturbance records from all addresses it finds in the range each time it operates. If a device is found at an address in the specified range and an error is found while extracting a record, the error is reported to a log file. When executed directly or by the Scheduled Task facility, the AEDR2 application runs invisibly in the background, without the WinAEDR2 interface running. The only communication between AEDR2 and WinAEDR2 is through three log files written by AEDR2 which are as follows: Error Log This contains errors reported by the Courier or IEC 60870‑5‑103 transfer mechanisms, or errors caused by missing devices. Each entry contains date, time and an error description. Extraction Log This has an entry for every record that is ed. Each entry contains date, time, communication type, device address, trigger date and time information. Status Log This file has one line showing the time and date that AEDR2 was last run. The Status Log is overwritten each time AEDR2 is run.
10.4
DISTURBANCE RECORD FILES
For each disturbance record, a set of two or three files are created in standard COMTRADE format (*.CFG, *.HDR, *.DAT). Filenames in a set use the following format,
10.5
OPERATION
All errors are output to a log file. Some errors may create more than one error in the log file. The log file name is settable. See the LogFileName entry in the INI file.
P14D-B/G/L/Z-TM-EN-1
541
Chapter 12 - Settings Application Software
10.6 1. 2. 3.
4. 5.
P14D
USING THE SCHEDULED TASKS PROGRAM Select Start > Settings > Control . Double-click Scheduled Tasks. The Scheduled Tasks program starts. Double click Add Scheduled Task. The Scheduled Tasks Wizard starts. This lets you schedule the program to run at regular intervals from once a day to once a year (inclusive). Once the task has been created, it can be scheduled more frequently than once a day. Double-click AEDR2, the Properties dialog appears. Select Schedule > Advanced to configure it to run at intervals which can be as small as one minute.
Note: The Scheduled Tasks facility can also be run directly from the WinAEDR2 application.
The Scheduled Tasks program is a component that is included with Windows®. It allows programs to be run automatically at predetermined times. Other programs are available from independent companies that provide more comprehensive facilities and these can be used as alternatives to run AEDR2.
10.7
SCHEDULED TASKS PROGRAM TUTORIAL
When creating a scheduled task, test the INI file first. To set the Scheduled Tasks Program to run AEDR2, 1. 2. 3. 4.
5. 6. 7. 8. 9. 10.
Select Start > Settings > Control . Double-click the Scheduled Tasks icon. The Scheduled Tasks program starts. Double click Add Scheduled Task. The Scheduled Tasks Wizard starts. Click Next. Ignore the list of programs and click the Browse button. Find AEDR2.exe. If you loaded MiCOM P14D at the default location it is at C:\Program Files\Alstom Grid\MiCOM S1 Agile \WinAEDR2\AEDR2.exe. Select AEDR2.exe and click the Open button. Select Daily and click Next. If you want it to operate more often than daily you can do this later. Select the Start Time and Start Date and click Next. Enter your name and (twice) and click Next. Click Open advanced properties for this task when I click Finish then click Finish. The Properties dialog opens. In this basic tutorial it’s only necessary to set how often AEDR2 runs and set which INI file it uses.
To set how often AEDR2 operates, 1. 2. 3. 4. 5.
542
Click the Schedule tab, then the Advanced button. The Advanced Schedule Options dialog appears. Enable Repeat Task and select Every 30 minutes. This sets Schedule Tasks to operate AEDR2 every 30 minutes. Enable Duration and select 24 hour(s). Enable If the task is still running, stop it at this time. Click OK.
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 12 - Settings Application Software
To tell the Scheduled Tasks which INI file AEDR2 should use, 1. 2. 3.
Click the Task tab. In the Run edit box, enter AEDR2.exe as the program to run. Enter a space after AEDR2.exe then the name of the INI file it uses. If the INI file contains spaces, enclose it in in double quotes. Do NOT add the /t option when running automatically. For example, "C:\Program Files\Alstom Grid\MiCOM S1 Agile\WinAEDR2\AEDR2.exe" " C:\Program Files\Alstom Grid\MiCOM S1 Agile\WinAEDR2\example.ini"
4. Click OK to complete setting up. If you need to modify the settings later, in the Schedule Tasks window, double-click the scheduled task and the Properties dialog opens. Note: If you need to use several INI files for Courier devices at various locations, take care over when each one operates. For example, if AEDR2 uses two INI files which use the same COM port at the same time, it will fail. However, if the two INI files use different COM ports at the same time, it will not fail.
P14D-B/G/L/Z-TM-EN-1
543
Chapter 12 - Settings Application Software
11
P14D
WINAEDR2
WinAEDR2 is a management facility for AEDR2. It shows the history of all previous extractions and has shortcut buttons to launch WaveWin, Windows Explorer and the Scheduled Task facility. It can also be used to view log files, and edit and test the initialisation file.
11.1
FUNCTIONS
The main window lists the most recently extracted records in the order of extraction. There are also buttons to launch the following functions. WaveWin launches the WaveWin COMTRADE viewer application ExtractionLog launches notepad to view the extraction log ErrorLog launches notepad to view the error log Explorer launches Windows Explorer Scheduler launches the "Scheduled Tasks" application Edit .INI File launches notepad to edit INI file Test .INI File tests the INI file for errors and logs any errors Run AEDR2 launches the AEDR2.exe application AEDR2 Status shows the run status of AEDR2
544
P14D-B/G/L/Z-TM-EN-1
P14D
12
Chapter 12 - Settings Application Software
WAVEWIN
Wavewin is used for viewing and analysing waveforms from disturbance records. It can be used to determine the sequence of events that led to a fault. Wavewin provides the following functions. For further details please refer to the Wavewin manual. ● ● ● ● ● ● ●
12.1
File management Query management Log management Report generation Sequence of Events(SOE) Conversion of COMTRADE files Waveform summary
FILE MANAGER FEATURES
The File Manager is used to manage files, search the contents of a drive or directory, and edit, plot or draw the contents of a file. This feature is similar to Windows Explorer with application-specific functions tailored for the Power Utility industry. The functions include automatic event file association, specialized copy or move, intelligent queries, report files, COMTRADE conversion and compression routines, merge and append waveform and load files, event summaries and calibration reports. The File Manager s the IEEE long file naming format.
12.2
SAVE AS COMTRADE
Oscillography formats ed by the software can be converted to the COMTRADE ASCII or Binary format. Two Comtrade versions are ed: the older 1991 format and the newer 1999 format. The Comtrade format can be selected from the Data Plotting Window’s Properties dialog. The default format is the newer 1999 format. To create a COMTRADE file, 1. 2. 3. 4.
Place the cursor on the event file or mark the desired files Select Options > Save As COMTRADE (ASCII or Binary). Enter the destination path and filename (do not enter a filename extension). Click OK. The .DAT and .CFG files are created automatically. If a path is not defined, the COMTRADE files are saved in the active directory. If the sample values in the selected file(s) are RMS calibrated and the desired COMTRADE file must have instantaneous values, set the Comtrade Settings fields to automatically convert the RMS data to instantaneous values. To set the Comtrade Settings fields,
1. In the Analysis display, open the Window Properties dialog. 2. Select the Comtrade tab. 3. In the Convert RMS Calibrated Data to Peak Data dropdown box, select Yes. To automatically convert the selected file(s) to COMTRADE using the IEEE long filename format, 1. 2. 3.
In the Save As Comtrade dialog, check the Use the ComNames Naming Convention to Name the Comtrade File(s) field Leave the File Name field empty. Click OK.
P14D-B/G/L/Z-TM-EN-1
545
Chapter 12 - Settings Application Software
P14D
All files marked in the table are converted to the selected COMTRADE format and are named using the IEEE long file naming convention.
546
P14D-B/G/L/Z-TM-EN-1
P14D
13
Chapter 12 - Settings Application Software
DEVICE (MENU) TEXT EDITOR
The Menu Text Editor enables you to modify and replace the menu texts held in MiCOM Px4x IEDs. For example, you may want to customise an IED so that menus appear in a language other than one of the standard languages. By loading a copy of the current menu text file in one of the standard languages into the reference column, you can type the appropriate translation of each menu entry into the target column. This can then be sent to the IED through your PC's parallel port, replacing one of the current standard languages. New menu text files created this way can also be saved to disk for later use or further editing.
13.1 1. 2. 3. 4. 5. 6.
13.2 1. 2. 3. 4. 5.
13.3 1. 2. 3. 4.
13.4 1. 2. 3. 4. 5.
13.5 1. 2.
OPEN A CONNECTION Select Device > Open Connection. The Open Connection dialog appears. Select the Parallel Port to which the device is connected. Select the Device Timeout in minutes. Click OK. The dialog is displayed. Type the . This is displayed as asterisks. Click OK. A message appears confirming the connection has been opened.
CHANGE CONNECTION Open a connection with the device. Select Device > Change . The Change dialog appears. In the New box, enter the new . This is displayed as asterisks. In the New box, enter the again. Click OK to accept.
OPEN A MENU TEXT FILE AS A REFERENCE Select the Reference column. Select File > Open. The Open File dialog appears. Select the required menu text file then click the Open button. The menu text file appears in the Reference column.
EDIT TEXT FILE OF DEVICE Select File > New to create a default menu text file for the required device or select File > Open to open an existing file. The menu text file appears in the Target column. Select the required text cell in the Target tab corresponding to the text in the Reference tab. Edit the file as required. Select File > Save As. Edit the File Name or Header fields as required. Click Save.
SEND EDITED TEXT FILE TO DEVICE Connect a PC with a parallel cable to the required device. Select Device > Open Connection to open a connection to the required device.
P14D-B/G/L/Z-TM-EN-1
547
Chapter 12 - Settings Application Software
3. 4. 5.
548
P14D
Select Send To Device. Click OK. Once the sending of the text file is complete, the new text appears in the menu on the IED screen.
P14D-B/G/L/Z-TM-EN-1
SCHEME LOGIC CHAPTER 13
Chapter 13 - Scheme Logic
550
P14D
P14D-B/G/L/Z-TM-EN-1
P14D
1
Chapter 13 - Scheme Logic
CHAPTER OVERVIEW
Alstom Grid products are supplied with pre-loaded Fixed Scheme Logic (FSL) and Programmable Scheme Logic (PSL). The FSL schemes cannot be modified. They have been individually designed to suit the model in question. Each model also provides default PSL schemes, which have also been designed to suit each model. If these schemes suit your requirements, you do not need to take any action. However, if you want to change the input-output mappings, or to implement custom scheme logic, you can change these, or create new PSL schemes using the PSL editor. This chapter provides details of the in-built FSL schemes and the default PSL schemes. This chapter contains the following sections: Chapter Overview Introduction to the Scheme Logic Fixed Scheme Logic Programmable Scheme Logic
551 552 554 559
P14D-B/G/L/Z-TM-EN-1
551
Chapter 13 - Scheme Logic
2
P14D
INTRODUCTION TO THE SCHEME LOGIC
The Scheme Logic is a functional module within the IED, through which all mapping of inputs to outputs is handled. The scheme logic can be split into two parts; the Fixed Scheme Logic (FSL) and the Programmable Scheme Logic (PSL). The FSL Scheme Logic is logic that has been designed and implemented at the factory. It is logic that is necessary for the fundamental workings of the IED. It is fixed and cannot be changed. The PSL is logic that is -programmable. The PSL consists of logic gates and timers, which combine and condition the DDB signals. The logic gates can be programmed to perform a range of different logic functions and can accept any number of inputs. The timers are used either to create a programmable delay or to condition the logic outputs. The PSL logic is event driven. Only the part of the PSL logic that is affected by the particular input change that has occurred is processed. This reduces the amount of processing time used by the PSL, when compared to some competition devices. The device is shipped with a selection of default schemes, which should cover basic applications, but you can modify these default schemes to create custom schemes, if desired. You can also create new schemes from scratch, should you wish to do so. The Scheme Logic module is built around a concept called the digital data bus (DDB). The DDB is a parallel data bus containing all of the digital signals (inputs, outputs, and internal signals), which are available for use in the FSL and PSL The following diagram shows how the scheme logic interacts with the rest of the IED.
Energising quantities
Fixed LEDs
SL inputs
SL outputs
Protection functions
Opto-inputs
Programmable LEDs PSL and FSL
Control input module
Goose outputs
Goose inputs
Output relays Control inputs
Function keys
Ethernet processing module
V02011
Figure 143: Scheme Logic Interfaces The inputs to the scheme logic are: ● Opto-inputs: Optically-coupled logic inputs ● Function keys: Keys on the device (not on 20TE models)
552
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 13 - Scheme Logic
● Control inputs: Software inputs for controlling functionality ● Goose inputs: Messages from other devices via the IEC61850 interface (not on all models) ● Scheme Logic inputs: Inputs from the protection functions (SL inputs are protection function outputs) The outputs from the scheme logic are: ● ● ● ●
Programmable LEDs Output relays Goose outputs: Messages to other devices via the IEC61850 interface (not on all models) Scheme Logic outputs: Outputs to the protection functions (SL outputs are protection function inputs)
Examples of internal inputs and outputs include: ● IN>1 Trip: This is an output from the Stage 1 Earth Fault protection function, which can be input into the PSL to create further functionality. This is therefore an SL input. ● Thermal Trip: This is an output from the the thermal protection function, which can be input into the PSL to create further functionality. This is therefore an SL input. ● Reset Relays/LED: This is an SL output, which can be asserted to reset the output relays and LEDs. The FSL is fixed, but the PSL allows you to create your own scheme logic design. For this, you need a suitable PC package to facilitate the design of the PSL scheme. This PC package is provided in the form of the the PSL Editor, which is included as part of the MiCOM S1 Agile engineering tool. The PSL Editor is one of a suite of applications available in the settings application software, but is also available as a standalone package. This tool is described in the Settings Application Software chapter.
P14D-B/G/L/Z-TM-EN-1
553
Chapter 13 - Scheme Logic
3
P14D
FIXED SCHEME LOGIC
This section contains logic diagrams of the fixed scheme logic, which covers all of the device models. You must be aware that some models do not contain all the functionality described in this section.
554
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 13 - Scheme Logic
3.1
ANY START LOGIC I>1 Start
I>2 Start
I>3 Start
I>4 Start
I>5 Start
I>6 Start
I2>1 Start
I2>2 Start
I2>3 Start
I2>4 Start
IN1>1 Start
IN1>2 Start
IN1>3 Start
IN1>4 Start
IN2>1 Start
IN2>2 Start
IN2>3 Start
IN2>4 Start
ISEF>1 Start
ISEF>2 Start
ISEF>3 Start
ISEF>4 Start
V<1 Start
V<2 Start
V<3 Start
V>1 Start
V>2 Start
V>3 Start
VN>1 Start
VN>2 Start
VN>3 Start
V2> Start
BrokenLine Start
Power>1 3PhStart
Power>1 A Start
Power>1 B Start
Power>1 C Start
Power>2 3PhStart
Power>2 A Start
Power>2 B Start
Power>2 C Start
Power<1 3PhStart
Power<1 A Start
Power<1 B Start
Power<1 C Start
Power<2 3PhStart
Power<2 A Start
Power<2 B Start
Power<2 C Start
SensP1 Start A
SensP2 Start A
Stg1 f+t Sta
Stg1 df/dt+t Sta
Stg1 f+Df/Dt Sta
Stg2 f+t Sta
Stg2 df/dt+t Sta
Stg2 f+Df/Dt Sta
Stg3 f+t Sta
Stg3 df/dt+t Sta
Stg3 f+Df/Dt Sta
Stg4 f+t Sta
Stg4 df/dt+t Sta
Stg4 f+Df/Dt Sta
Stg5 f+t Sta
Stg5 df/dt+t Sta
Stg5 f+Df/Dt Sta
Stg6 f+t Sta
Stg6 df/dt+t Sta
Stg6 f+Df/Dt Sta
Stg7 f+t Sta
Stg7 df/dt+t Sta
Stg7 f+Df/Dt Sta
Stg8 f+t Sta
Stg8 df/dt+t Sta
Stg8 f+Df/Dt Sta
Stg9 f+t Sta
Stg9 df/dt+t Sta
Stg9 f+Df/Dt Sta
dv/dt1 StartA/AB
dv/dt1 StartB/BC
dv/dt1 StartC/CA
dv/dt1 Start
dv/dt2 StartA/AB
dv/dt2 StartB/BC
dv/dt2 StartC/CA
dv/dt2 Start
dv/dt3 StartA/AB
dv/dt3 StartB/BC
dv/dt3 StartC/CA
dv/dt3 Start
dv/dt4 StartA/AB
dv/dt4 StartB/BC
dv/dt4 StartC/CA
dv/dt4 Start
1
Any Start
Key: External DDB Signal AND gate
&
OR gate
1
V02000
Figure 144: Any Start Logic
P14D-B/G/L/Z-TM-EN-1
555
Chapter 13 - Scheme Logic
3.2
P14D
VTS ACCELERATION INDICATION LOGIC Trip Command In
VTS Acc Ind Key: External DDB Signal AND gate
V02001
&
OR gate
1
&
OR gate
1
Figure 145: VTS Acceleration Indication Logic
3.3
CB FAIL SEF PROTECTION LOGIC ISEF>1 Trip ISEF>2 Trip ISEF>3 Trip
1
CBF SEF Trip-1
ISEF>4 Trip CBF SEF Trip-1
&
CBF SEF Trip
Trip Command In Key: External DDB Signal
V02002
AND gate
Figure 146: CB Fail SEF Protection Logic
556
P14D-B/G/L/Z-TM-EN-1
P14D
3.4
Chapter 13 - Scheme Logic
CB FAIL NON CURRENT PROTECTION LOGIC V<1 Trip V<3 Trip V>2 Trip VN>1 Trip VN>3 Trip Power>1 3Ph Trip Power>1 B Trip Power>2 3Ph Trip Power>2 B Trip Power<1 3Ph Trip Power<1 B Trip Power<2 3Ph Trip Power<2 B Trip SensP1 Trip A Stg1 f+t Trp Stg1 df/dt+t Trp Stg2 f+t Trp Stg2 df/dt+t Trp Stg3 f+t Trp Stg3 df/dt+t Trp Stg4 f+t Trp Stg4 df/dt+t Trp Stg5 f+t Trp Stg5 df/dt+t Trp Stg6 f+t Trp Stg6 df/dt+t Trp Stg7 f+t Trp Stg7 df/dt+t Trp Stg8 f+t Trp Stg8 df/dt+t Trp Stg9 f+t Trp Stg9 df/dt+t Trp dv/dt1 Trip A/AB dv/dt1 Trip C/CA dv/dt2 Trip A/AB dv/dt2 Trip C/CA dv/dt3 Trip A/AB dv/dt3 Trip C/CA dv/dt4 Trip A/AB dv/dt4 Trip C/CA V02003
V<2 Trip V>1 Trip V>3 Trip VN>2 Trip V2> Trip Power>1 A Trip Power>1 C Trip Power>2 A Trip Power>2 C Trip Power<1 A Trip Power<1 C Trip Power<2 A Trip Power<2 C Trip SensP2 Trip A Stg1 f+df/dt Trp Stg1 f+Df/Dt Trp Stg2 f+df/dt Trp Stg2 f+Df/Dt Trp Stg3 f+df/dt Trp Stg3 f+Df/Dt Trp
1
CBF Non I Trip-1
Stg4 f+df/dt Trp Stg4 f+Df/Dt Trp Stg5 f+df/dt Trp
CBF Non I Trip-1
&
CBF Non I Trip
Trip Command In
Stg5 f+Df/Dt Trp Stg6 f+df/dt Trp Stg6 f+Df/Dt Trp Stg7 f+df/dt Trp Stg7 f+Df/Dt Trp Stg8 f+df/dt Trp Stg8 f+Df/Dt Trp Stg9 f+df/dt Trp Stg9 f+Df/Dt Trp dv/dt1 Trip B/BC dv/dt1 Trip dv/dt2 Trip B/BC dv/dt2 Trip dv/dt3 Trip B/BC dv/dt3 Trip dv/dt4 Trip B/BC dv/dt4 Trip
Key: External DDB Signal AND gate
&
OR gate
1
Figure 147: CB Fail Non Current Protection Logic
P14D-B/G/L/Z-TM-EN-1
557
Chapter 13 - Scheme Logic
3.5
P14D
COMPOSITE EARTH FAULT START LOGIC IN1>1 Start IN1>3 Start IN2>1 Start IN2>3 Start ISEF>1 Start ISEF>3 Start VN>1 Start VN>3 Start
IN1>2 Start IN1>4 Start IN2>2 Start IN2>4 Start
1
Start N
ISEF>2 Start ISEF>4 Start Key: External DDB Signal
VN>2 Start
AND gate
V02004
&
OR gate
1
Figure 148: Composite Earth Fault Start Logic
3.6
ANY TRIP LOGIC Trip Command In
Trip Command Out Key: External DDB Signal AND gate
V02005
&
OR gate
1
Figure 149: Any Trip Logic
3.7
SEF ANY START LOGIC ISEF1>1 Start ISEF1>2 Start ISEF1>3 Start
1
ISEF> Start
ISEF1>4 Start Key: External DDB Signal
V02006
AND gate
&
OR gate
1
Figure 150: SEF Any Start Logic
558
P14D-B/G/L/Z-TM-EN-1
P14D
4
Chapter 13 - Scheme Logic
PROGRAMMABLE SCHEME LOGIC
This section contains logic diagrams of the default programmable scheme logic, which covers all of the device models. You must be aware that some models do not contain all the functionality described in this section. All these diagrams can be viewed, edited and printed from the PSL Editor.
P14D-B/G/L/Z-TM-EN-1
559
Chapter 13 - Scheme Logic
4.1
P14D
TRIP OUTPUT MAPPINGS I>1 Trip
I>2 Trip
I>3 Trip
I>4 Trip
I>5 Trip
I>6 Trip
I2>1 Trip
I2>2 Trip
I2>3 Trip
I2>4 Trip
IN1>1 Trip
IN1>2 Trip
IN1>3 Trip
IN1>4 Trip
IN2>1 Trip
IN2>2 Trip
IN2>3 Trip
IN2>4 Trip
ISEF>1 Trip
ISEF>2 Trip
ISEF>3 Trip
ISEF>4 Trip
V<1 Trip
V<2 Trip
V<3 Trip
V>1 Trip
V>2 Trip
V>3 Trip
VN>1 Trip
VN>2 Trip
VN>3 Trip
V2> Trip
BrokenLine Trip
Power>1 3PhTrip
Power>1 A Trip
Power>1 B Trip
Power>1 C Trip
Power>2 3PhTrip
Power>2 A Trip
Power>2 B Trip
Power>2 C Trip
Power<1 3PhTrip
Power<1 A Trip
Power<1 B Trip
Power<1 C Trip
Power<2 3PhTrip
Power<2 A Trip
Power<2 B Trip
Power<2 C Trip
SensP1 Trip A
SensP2 Trip A
Stg1 f+t Trp
Stg1 df/dt+t Trp
Stg1 f+Df/Dt Trp
Stg2 f+t Trp
Stg2 df/dt+t Trp
Stg2 f+Df/Dt Trp
Stg3 f+t Trp
Stg3 df/dt+t Trp
Stg3 f+Df/Dt Trp
Stg4 f+t Trp
Stg4 df/dt+t Trp
Stg4 f+Df/Dt Trp
Stg5 f+t Trp
Stg5 df/dt+t Trp
Stg5 f+Df/Dt Trp
Stg6 f+t Trp
Stg6 df/dt+t Trp
Stg6 f+Df/Dt Trp
Stg7 f+t Trp
Stg7 df/dt+t Trp
Stg7 f+Df/Dt Trp
Stg8 f+t Trp
Stg8 df/dt+t Trp
Stg8 f+Df/Dt Trp
Stg9 f+t Trp
Stg9 df/dt+t Trp
Stg9 f+Df/Dt Trp
dv/dt1 TripA/AB
dv/dt1 TripB/BC
dv/dt1 TripC/CA
dv/dt1 Trip
dv/dt2 TripA/AB
dv/dt2 TripB/BC
dv/dt2 TripC/CA
dv/dt2 Trip
dv/dt3 TripA/AB
dv/dt3 TripB/BC
dv/dt3 TripC/CA
dv/dt3 Trip
dv/dt4 TripA/AB
dv/dt4 TripB/BC
dv/dt4 TripC/CA
dv/dt4 Trip
1
Trip Command In Note: Trip Command In and Trip Command Out are ed together in the FSL
Key: External DDB Signal AND gate
&
OR gate
1
V02012
Figure 151: Trip Output Mappings
560
P14D-B/G/L/Z-TM-EN-1
P14D
4.2
Chapter 13 - Scheme Logic
OPTO-INPUT MAPPINGS Input L1
Block AR
Input L2
SG Select 1x
Input L3
IN1>3 Timer Block IN1>4 Timer Block
Input L4
I>3 Timer Block I>4 Timer Block
Input L5
CB Healthy
Input L6
Ext. Trip 3ph
Input L7
CB Aux 3ph(52-A)
Input L8
CB Aux 3ph(52-B)
V02015
Key: External DDB Signal
Figure 152: Opto-Input Mappings
P14D-B/G/L/Z-TM-EN-1
561
Chapter 13 - Scheme Logic
4.3
P14D
OUTPUT RELAY MAPPINGS IN/SEF> Blk Start
Output R1
I> Block Start
Output R2
Trip Comand Out
Output R3
SG-opto Invalid F out of Range VT Fail Alarm CT Fail Alarm CB Fail Alarm I^ Maint Alarm CB Ops Maint Alarm CB Op Time Maint
1
Output R4
Fault Freq Lock CB Status Alarm Man CB Trip Fail CB Cls Fail Man CB Unhealthy AR Lockout UV Block BFail1 Trip 3ph
Output R5
Control Close
Output R6
Control trip
Output R7
Any Start
Output R8 Key:
V02018
External DDB Signal
OR gate
1
Figure 153: Output Relay Mappings
LED MAPPINGS
4.4
V02021
Trip Command Out
LED1 Red
Any Start
LED1 Grn
CB Open 3 ph
LED2 Red
CB Closed 3 ph
LED2 Grn
AR In Progress
LED3 Red
Successful Close
LED3 Grn
AR Lockout
LED4 Red
AR In Service
LED4 Grn Key: External DDB Signal
Figure 154: LED Mappings
562
P14D-B/G/L/Z-TM-EN-1
P14D
4.5
Chapter 13 - Scheme Logic
CONTROL INPUT MAPPINGS Control Input 1
Reset Lockout
Control Input 2
AR Auto Mode
Control Input 3
Telecontrol Mode
Control Input 4
AR LiveLine Mode Key: External DDB Signal
V02023
Figure 155: Control Input Mappings
4.6
FUNCTION KEY MAPPINGS Function Key 1
Blk Rmt. CB Ops FnKey LED1 Red
Function Key 2
Init Trip CB FnKey LED2 Red FnKey LED2 Green
Function Key 3
Close in Prog
Init Close CB 1
FnKey LED3 Red FnKey LED3 Green Key: External DDB Signal OR gate
1
NOT gate
V02025
Figure 156: Function Key Mappings
CIRCUIT BREAKER MAPPING
4.7
CB Closed 3 ph
CB in Service Key: External DDB Signal
V02026
Figure 157: Circuit Breaker mapping
FAULT RECORD TRIGGER MAPPING
4.8
Output R3 V02027
Fault Rec Trig Key: External DDB Signal
Figure 158: Fault Record Trigger mapping
P14D-B/G/L/Z-TM-EN-1
563
Chapter 13 - Scheme Logic
4.9
P14D
HIGH IMPEDEANCE FAULT PROTECTION MAPPINGS CB Open 3 ph
HIF Forced Reset Key: External DDB Signal
V02029
Figure 159: High Impedance Fault Protection Mappings
4.10
CHECK SYNCHRONISATION AND VOLTAGE MONITOR MAPPINGS SysChks Inactive Check Sync 1 OK Check Sync 2 OK Live Line Dead Bus
Dead Line
Live Bus
Man Check Synch & 1
AR Sys Checks
&
&
Key: External DDB Signal OR gate
1
AND gate
&
V02028
Figure 160: Check Synchronisation and Voltage Monitor mappings
4.11
SETTINGS
The device contains a PSL DATA column, which can be used to track PSL modifications. A total of 12 cells are contained in the PSL DATA column; 3 for each setting group. Grp(n) PSL Ref: When ing a PSL scheme to an IED, you will be prompted to enter the relevant group number and a reference identifier. The first 32 characters of the reference identifier are displayed in this cell. The horizontal cursor keys can scroll through the 32 characters as the LCD display only displays 16 characters. Example: Grp. PSL Ref.
Date/time: This cell displays the date and time when the PSL scheme was ed to the IED. Example: 18 Nov 2002 08:59:32.047 Grp(n) PSL ID: This cell displays a unique ID number for the ed PSL scheme. Example:
564
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 13 - Scheme Logic
Grp. 1 PSL ID - 2062813232 The complete Settings table is shown below: Menu Text
Col
Row
Default Setting
Available Options
Description PSL DATA
B7
00
This column contains information about the Programmable Scheme Logic Grp1 PSL Ref
B7
01
Not settable
This setting displays the Group 1 PSL reference Date/Time
B7
02
Not settable
This setting displays the date and time the PSL was created Grp1 PSL ID
B7
03
Not settable
This setting displays the Group 1 PSL ID Grp2 PSL Ref
B7
11
Not settable
This setting displays the Group 2 PSL reference Date/Time
B7
12
Not settable
This setting displays the date and time the PSL was created Grp2 PSL ID
B7
13
Not settable
This setting displays the Group 2 PSL ID Grp3 PSL Ref
B7
21
Not settable
This setting displays the Group 3 PSL reference Date/Time
B7
22
Not settable
This setting displays the date and time the PSL was created Grp3 PSL ID
B7
23
Not settable
This setting displays the Group 3 PSL ID Grp4 PSL Ref
B7
31
Not settable
This setting displays the Group 4 PSL reference Date/Time
B7
32
Not settable
This setting displays the date and time the PSL was created Grp4 PSL ID
B7
33
Not settable
This setting displays the Group 4 PSL ID
P14D-B/G/L/Z-TM-EN-1
565
Chapter 13 - Scheme Logic
566
P14D
P14D-B/G/L/Z-TM-EN-1
INSTALLATION CHAPTER 14
Chapter 14 - Installation
568
P14D
P14D-B/G/L/Z-TM-EN-1
P14D
1
Chapter 14 - Installation
CHAPTER OVERVIEW
This chapter provides information about installing the product. This chapter contains the following sections: Chapter Overview Handling the Goods Mounting the Device Cables and Connectors Case Dimensions
569 570 571 577 582
P14D-B/G/L/Z-TM-EN-1
569
Chapter 14 - Installation
2
P14D
HANDLING THE GOODS
Our products are of robust construction but require careful treatment before installation on site. This section discusses the requirements for receiving and unpacking the goods, as well as associated considerations regarding product care and personal safety. Caution: Before lifting or moving the equipment you should be familiar with the Safety Information chapter of this manual.
2.1
RECEIPT OF THE GOODS
On receipt, ensure the correct product has been delivered. Unpack the product immediately to ensure there has been no external damage in transit. If the product has been damaged, make a claim to the transport contractor and notify us promptly. For products not intended for immediate installation, repack them in their original delivery packaging.
2.2
UNPACKING THE GOODS
When unpacking and installing the product, take care not to damage any of the parts and make sure that additional components are not accidentally left in the packing or lost. Do not discard any CDROMs or technical documentation. These should accompany the unit to its destination substation and put in a dedicated place. The site should be well lit to aid inspection, clean, dry and reasonably free from dust and excessive vibration. This particularly applies where installation is being carried out at the same time as construction work.
2.3
STORING THE GOODS
If the unit is not installed immediately, store it in a place free from dust and moisture in its original packaging. Keep any de-humidifier bags included in the packing. The de-humidifier crystals lose their efficiency if the bag is exposed to ambient conditions. Restore the crystals before replacing it in the carton. Ideally regeneration should be carried out in a ventilating, circulating oven at about 115°C. Bags should be placed on flat racks and spaced to allow circulation around them. The time taken for regeneration will depend on the size of the bag. If a ventilating, circulating oven is not available, when using an ordinary oven, open the door on a regular basis to let out the steam given off by the regenerating silica gel. On subsequent unpacking, make sure that any dust on the carton does not fall inside. Avoid storing in locations of high humidity. In locations of high humidity the packaging may become impregnated with moisture and the de-humidifier crystals will lose their efficiency. The device can be stored between –25º to +70ºC (-13ºF to +158ºF).
2.4
DISMANTLING THE GOODS
If you need to dismantle the device, always observe standard ESD (Electrostatic Discharge) precautions. The minimum precautions to be followed are as follows: ● Use an antistatic wrist band earthed to a suitable earthing point. ● Avoid touching the electronic components and PCBs.
570
P14D-B/G/L/Z-TM-EN-1
P14D
3
Chapter 14 - Installation
MOUNTING THE DEVICE
The products are available in the following forms ● For flush and rack mounting ● For retrofitting K-series models ● Software only (for upgrades)
3.1
FLUSH MOUNTING
-mounted devices are flush mounted into s using M4 SEMS Taptite self-tapping screws with captive 3 mm thick washers (also known as a SEMS unit). These fastenings are available in packs of five (our part number ZA0005 104). Caution: Do not use conventional self-tapping screws, because they have larger heads and could damage the faceplate.
Alternatively, you can use tapped holes if the has a minimum thickness of 2.5 mm. For applications where the product needs to be semi-projection or projection mounted, a range of collars are available. If several products are mounted in a single cut-out in the , mechanically group them horizontally or vertically into rigid assemblies before mounting in the . Caution: Do not fasten products with pop rivets because this makes them difficult to remove if repair becomes necessary.
If the product is mounted on a BS EN60529 IP52 compliant , fit a metallic sealing strip between ading products (part no GN2044 001) and fit a sealing ring around the complete assembly, according to the following table. Width
Sealing ring for single tier
Sealing ring for double tier
10TE
GJ9018 002
GJ9018 018
15TE
GJ9018 003
GJ9018 019
20TE
GJ9018 004
GJ9018 020
25TE
GJ9018 005
GJ9018 021
30TE
GJ9018 006
GJ9018 022
35TE
GJ9018 007
GJ9018 023
40TE
GJ9018 008
GJ9018 024
45TE
GJ9018 009
GJ9018 025
50TE
GJ9018 010
GJ9018 026
55TE
GJ9018 011
GJ9018 027
60TE
GJ9018 012
GJ9018 028
65TE
GJ9018 013
GJ9018 029
70TE
GJ9018 014
GJ9018 030
75TE
GJ9018 015
GJ9018 031
80TE
GJ9018 016
GJ9018 032
P14D-B/G/L/Z-TM-EN-1
571
Chapter 14 - Installation
3.1.1
P14D
RACK MOUNTING
-mounted variants can also be rack mounted using single-tier rack frames (our part number FX0021 101), as shown in the figure below. These frames are designed with dimensions in accordance with IEC 60297 and are supplied pre-assembled ready to use. On a standard 483 mm (19 inch) rack this enables combinations of case widths up to a total equivalent of size 80TE to be mounted side by side. The two horizontal rails of the rack frame have holes drilled at approximately 26 mm intervals. Attach the products by their mounting flanges using M4 Taptite self-tapping screws with captive 3 mm thick washers (also known as a SEMS unit). These fastenings are available in packs of five (our part number ZA0005 104). Caution: Risk of damage to the front cover molding. Do not use conventional self-tapping screws, including those supplied for mounting MiDOS products because they have slightly larger heads.
Once the tier is complete, the frames are fastened into the racks using mounting angles at each end of the tier.
Figure 161: Rack mounting of products Products can be mechanically grouped into single tier (4U) or multi-tier arrangements using the rack frame. This enables schemes using products from different product ranges to be pre-wired together before mounting. Use blanking plates to fill any empty spaces. The spaces may be used for installing future products or because the total size is less than 80TE on any tier. Blanking plates can also be used to mount ancillary components. The part numbers are as follows: Blanking plate part number
Case size summation 5TE
GJ2028 101
10TE
GJ2028 102
15TE
GJ2028 103
20TE
GJ2028 104
25TE
GJ2028 105
572
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 14 - Installation
Case size summation
Blanking plate part number
30TE
GJ2028 106
35TE
GJ2028 107
40TE
GJ2028 108
3.2
K-SERIES RETROFIT
A major advantage of the P40 Agile platform is its backward compatibility with the K-series products. The P40 Agile products have been designed such that the case, back terminal layout and pin-outs are identical to their K-series predecessors and can be retrofitted without the usual overhead associated with replacing and rewiring devices. This allows easy upgrade of the protection system with minimum impact and minimum shutdown time of the feeder. The equivalencies of the models are as follows: Case width (TE)
Case width (mm)
Equivalent K series
Products
20TE
102.4 mm (4 inches)
KCGG140/142
P14N
30TE
154.2 mm (6 inches)
KCEG140/142
P14D
The old K-series products can be removed by sliding the cradle out of the case. The new P40 Agile cradle can then be inserted into the old case as shown below:
Figure 162: Inserting cradle into case Both K-series products and P40 Agile products are equipped with CT shorting links. Depending on the model, your device may or may not be equipped with CTs. If there are CTs present, spring-loaded shorting s (see below) ensure that the terminals into which the CTs connect are shorted before the CT s are broken, when withdrawing the cradle from the case. This ensures that no voltage is developed between the two terminals on breaking the CT connections. If no CTs are present, the CT terminals are permanently shorted internally.
P14D-B/G/L/Z-TM-EN-1
573
Chapter 14 - Installation
P14D
E01407
Figure 163: Spring-loaded CT shorting s Before withdrawing the cradle it is important to: ● Check the existing case for any damage ● Check the wiring is in good condition, especially the earth wiring ● Check the continuity of the earth connection to the cublicle earthing bar. If there is any doubt as to the integrity of any of these aspects, your local representative. Caution: After removing the K-series product from its case, refit it into the case that came with your device, for storage or reuse in another location.
The difference between a standard device and a K-series retrofit device is that the retrofit device has internal links between terminals 7 and 13, and terminals 8 and 14 respectively. This is so that equipment driven by the K-series field voltage conected to terminals 7 and 8, will continue to be driven indirectly via terminals 13 and 14 when replaced by P40 Agile products. A K-series device provides a 48V DC field voltage between terminals 7 and 8. This field voltage is intended for driving auxiliary equipment such as opto-inputs. P40 Agile devices DO NOT provide this field voltage. For this reason, P40 Agile retrofit devices have internal shorting links between terminals 7 and 13, and terminals 8 and 14 respectively. The intention of this is to provide the auxiliary supply voltage to terminals 7 and 8 in lieue of the field voltage. Caution: The voltage on terminals 7 and 8 mirros that of the auxiliary supply voltage. If the auxiliary supply voltage on terminals 13 and 14 is not 48V DC, then the voltage on terminals 7 and 8 is also not 48V DC. This means that the P40 Agile K-series retrofit models should only be used on sites where the auxiliary supply voltage is 48V DC.
574
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 14 - Installation
Caution: When retrofitting a K-series device, ensure the load on terminals 7 and 8 is limited to a maximum of 5A. A jumplead with a 5A ceramic timelag fuse is fitted internally.
3.2.1
CONVENTIONS
The P40 Agile products have different conventions from the K-series products when it comes to numbering some hardware components. It is very important that you are aware of this. This is just a matter of convention and does not affect the terminal compatibility. The equivalencies are as follows: Component
P40 Agile products
K-series products
Output relay
RL1
RL0
Output relay
RL2
RL1
Output relay
RL3
RL2
Output relay
RL4
RL3
Output relay
RL5
RL4
Output relay
RL6
RL5
Output relay
RL7
RL6
Output relay
RL8
RL7
Opto-input
L1
L0
Opto-input
L2
L1
Opto-input
L3
L2
Opto-input
L4
L3
Opto-input
L5
L4
Opto-input
L6
L5
Opto-input
L7
L6
Opto-input
L8
L7
3.3
SOFTWARE ONLY
It is possible to upgrade an existing device by purchasing software only (providing the device is already fitted with the requisite hardware). There are two options for software-only products: ● Your device is sent back to the Alstom factory for upgrade. ● The software is sent to you for upgrade. Please your local representative if you wish to procure the services of a commissioning engineer to help you with your device upgrade. Note: Software-only products are licensed for use with devices with specific serial numbers.
P14D-B/G/L/Z-TM-EN-1
575
Chapter 14 - Installation
P14D
Caution: Do not attempt to upgrade an existing device if the software has not been licensed for that speciific device.
576
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 14 - Installation
4
CABLES AND CONNECTORS
This section describes the type of wiring and connections that should be used when installing the device. For pin-out details please refer to the Hardware Design chapter or the wiring diagrams. Caution: Before carrying out any work on the equipment you should be familiar with the Safety Section and the ratings on the equipment’s rating label.
4.1
TERMINAL BLOCKS
The P40 Agile devices use MiDOS terminal blocks as shown below.
Figure 164: MiDOS terminal block The MiDOS terminal block consists of up to 28 x M4 screw terminals. The wires should be terminated with rings using 90° ring terminals, with no more than two rings per terminal. The products are supplied with sufficient M4 screws. M4 90° crimp ring terminals are available in three different sizes depending on the wire size. Each type is available in bags of 100. Wire size
Part number mm2
Insulation color
ZB9124 901
0.25 - 1.65
(22 – 16 AWG)
Red
ZB9124 900
1.04 - 2.63 mm2 (16 – 14 AWG)
Blue
ZB9124 904
2.53 - 6.64 mm2 (12 – 10 AWG)
Un-insulated
P14D-B/G/L/Z-TM-EN-1
577
Chapter 14 - Installation
P14D
Caution: Always fit an insulating sleeve over the ring terminal.
4.2
POWER SUPPLY CONNECTIONS
These should be wired with 1.5 mm PVC insulated multi-stranded copper wire terminated with M4 ring terminals. The wire should have a minimum voltage rating of 300 V RMS. Caution: Protect the auxiliary power supply wiring with a maximum 16 A high rupture capacity (HRC) type NIT or TIA fuse.
4.3
EARTH CONNNECTION
Every device must be connected to the cubicle earthing bar using the M4 earth terminal. Use a wire size of at least 2.5 mm2 terminated with a ring terminal. Due to the physical limitations of the ring terminal, the maximum wire size you can use is 6.0 mm2 using ring terminals that are not pre-insulated. If using pre insulated ring terminals, the maximum wire size is reduced to 2.63 mm2 per ring terminal. If you need a greater cross-sectional area, use two wires in parallel, each terminated in a separate ring terminal. The wire should have a minimum voltage rating of 300 V RMS. Note: To prevent any possibility of electrolytic action between brass or copper ground conductors and the rear of the product, precautions should be taken to isolate them from one another. This could be achieved in several ways, including placing a nickel-plated or insulating washer between the conductor and the product case, or using tinned ring terminals.
4.4
CURRENT TRANSFORMERS
Current transformers would generally be wired with 2.5 mm2 PVC insulated multi-stranded copper wire terminated with M4 ring terminals. Due to the physical limitations of the ring terminal, the maximum wire size you can use is 6.0 mm2 using ring terminals that are not pre-insulated. If using pre insulated ring terminals, the maximum wire size is reduced to 2.63 mm2 per ring terminal. If you need a greater cross-sectional area, use two wires in parallel, each terminated in a separate ring terminal. The wire should have a minimum voltage rating of 300 V RMS. Caution: Current transformer circuits must never be fused.
Note: If there are CTs present, spring-loaded shorting s ensure that the terminals into which the CTs connect are shorted before the CT s are broken.
578
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 14 - Installation
Note: For 5A CT secondaries, we recommend using 2 x 2.5 mm2 PVC insulated multi-stranded copper wire.
4.5
VOLTAGE TRANSFORMER CONNECTIONS
Voltage transformers should be wired with 2.5 mm2 PVC insulated multi-stranded copper wire terminated with M4 ring terminals. The wire should have a minimum voltage rating of 300 V RMS.
4.6
WATCHDOG CONNECTIONS
These should be wired with 1 mm PVC insulated multi-stranded copper wire terminated with M4 ring terminals. The wire should have a minimum voltage rating of 300 V RMS.
4.7
EIA(RS)485 AND K-BUS CONNECTIONS
For connecting the EIA(RS485) / K-Bus ports, use 2-core screened cable with a maximum total length of 1000 m or 200 nF total cable capacitance. A typical cable specification would be: ● Each core: 16/0.2 mm2 copper conductors, PVC insulated ● Nominal conductor area: 0.5 mm2 per core ● Screen: Overall braid, PVC sheathed To guarantee the performance specifications, you must ensure continuity of the screen, when daisy chaining the connections. The device is supplied with an earth link pack (part number ZA0005092) consisting of an earth link and a self-tapping screw to facilitate this requirement. The earth link is fastened to the Midos block just below terminal number 56 as shown:
E01402
Figure 165: Earth link for cable screen There is no electrical connection of the cable screen to the device. The link is provided purely to link together the two cable screens.
P14D-B/G/L/Z-TM-EN-1
579
Chapter 14 - Installation
4.8
P14D
IRIG-B CONNECTION
The optional IRIG-B input uses the same terminals as the EIA(RS)485 port RP1. It is therefore apparent that RS485 communications and IRIG-B input are mutually exclusive. A typical cable specification would be: ● Each core: 16/0.2 mm2 copper conductors, PVC insulated ● Nominal conductor area: 0.5 mm2 per core ● Screen: Overall braid, PVC sheathed
4.9
OPTO-INPUT CONNECTIONS
These should be wired with 1 mm2 PVC insulated multi-stranded copper wire terminated with M4 ring terminals. Each opto-input has a selectable preset ½ cycle filter. This makes the input immune to noise induced on the wiring. This can, however slow down the response. If you need to switch off the ½ cycle filter, either use double pole switching on the input, or screened twisted cable on the input circuit. Caution: Protect the opto-inputs and their wiring with a maximum 16 A high rupture capacity (HRC) type NIT or TIA fuse.
4.10
OUTPUT RELAY CONNECTIONS
These should be wired with 1 mm PVC insulated multi-stranded copper wire terminated with M4 ring terminals.
4.11
ETHERNET METALLIC CONNECTIONS
If the device has a metallic Ethernet connection, it can be connected to either a 10Base-T or a 100Base-TX Ethernet hub. Due to noise sensitivity, we recommend this type of connection only for short distance connections, ideally where the products and hubs are in the same cubicle. For increased noise immunity, CAT 6 (category 6) STP (shielded twisted pair) cable and connectors can be used. The connector for the Ethernet port is a shielded RJ-45. The pin-out is as follows: Pin
Signal name
Signal definition
1
TXP
Transmit (positive)
2
TXN
Transmit (negative)
3
RXP
Receive (positive)
4
-
Not used
5
-
Not used
6
RXN
Receive (negative)
7
-
Not used
8
-
Not used
4.12
ETHERNET FIBRE CONNECTIONS
We recommend the use of fibre-optic connections for permanent connections in a substation environment. The 100 Mbps fibre optic port is based on the 100BaseFX standard and uses type LC connectors. They are compatible with 50/125 µm or 62.5/125 µm multimode fibres at 1300 nm wavelength.
580
P14D-B/G/L/Z-TM-EN-1
P14D
4.13
Chapter 14 - Installation
USB CONNECTION
The IED has a type B USB socket on the front . A standard USB printer cable (type A one end, type B the other end) can be used to connect a local PC to the IED. This cable is the same as that used for connecting a printer to a PC.
P14D-B/G/L/Z-TM-EN-1
581
Chapter 14 - Installation
5
P14D
CASE DIMENSIONS 99.0mm 10.5mm
A = Clearance holes B = Mounting holes
78.0mm
A
B
B
A
159.0mm 168.0mm
243.1mm A 23.5mm
B
B 52.0mm
A
8 holes
3.4mm 213.1mm
177.0mm
102.4mm
E01403
Figure 166: 20TE case dimensions
582
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 14 - Installation
151.0mm 129.5mm
10.75
A B
A = Clearance hole B = Mounting hole B
A
159.0mm 168.0mm
A B
B
A 242.7mm
23.7mm
8 holes
103.6mm
3.4mm
213.1mm
177.0mm
154.2mm
E01404
Figure 167: 30TE case dimensions
P14D-B/G/L/Z-TM-EN-1
583
Chapter 14 - Installation
584
P14D
P14D-B/G/L/Z-TM-EN-1
COMMISSIONING INSTRUCTIONS CHAPTER 15
Chapter 15 - Commissioning Instructions
586
P14D
P14D-B/G/L/Z-TM-EN-1
P14D
1
Chapter 15 - Commissioning Instructions
CHAPTER OVERVIEW
This chapter contains the following sections: Chapter Overview General Guidelines Commissioning Test Menu Commissioning Equipment Product Checks Setting Checks Protection Timing Checks Onload Checks Final Checks
587 588 589 592 593 601 603 605 607
P14D-B/G/L/Z-TM-EN-1
587
Chapter 15 - Commissioning Instructions
2
P14D
GENERAL GUIDELINES
Alstom Grid IEDs are self-checking devices and will raise an alarm in the unlikely event of a failure. This is why the commissioning tests are less extensive than those for non-numeric electronic devices or electromechanical relays. To commission the IEDs, you do not need to test every IED function. You need only that the hardware is functioning correctly and that the application-specific software settings have been applied. You can check the settings by extracting them using appropriate setting software, or by means of the front interface (HMI ). The customer is usually responsible for determining the settings to be applied and for testing any scheme logic. The menu language is -selectable, so the Commissioning Engineer can change it for commissioning purposes if required. Note: to restore the language setting to the customer’s preferred language on completion.
Caution: Before carrying out any work on the equipment you should be familiar with the contents of the Safety Section or Safety Guide SFTY/4LM as well as the ratings on the equipment’s rating label. Warning: Do not disassemble the IED in any way during commissioning.
588
P14D-B/G/L/Z-TM-EN-1
P14D
3
Chapter 15 - Commissioning Instructions
COMMISSIONING TEST MENU
The IED provides several test facilities under the COMMISSION TESTS menu heading. There are menu cells that allow you to monitor the status of the opto-inputs, output relay s, internal Digital Data Bus (DDB) signals and -programmable LEDs. This section describes the commissioning tests available in the IED's Commissioning test menu.
3.1
OPTO I/P STATUS CELL (OPTO-INPUT STATUS)
This cell can be used to monitor the status of the opto-inputs while they are sequentially energised with a suitable DC voltage. The cell displays the status of the opto-inputs as a binary string, '1' meaning energised, '0' meaning deenergised. If you move the cursor along the binary numbers, the corresponding label text is displayed for each logic input.
3.2
RELAY O/P STATUS CELL (RELAY OUTPUT STATUS)
This cell displays the status of the DDB signals that result in energisation of the output relays as a binary string, a '1' indicating an operated state and '0' a non-operated state. If you move the cursor along the binary numbers the corresponding label text is displayed for each relay output. The displayed information can be used to indicate the status of the output relays when the IED is in service. You can also check for relay damage by comparing the status of the output s with their associated bits. Note: When the Test Mode cell is set to s Blocked, this cell continues to indicate which s would operate if the IED was in-service. It does not show the actual status of the output relays.
3.3
TEST PORT STATUS CELL
This cell displays the status of the DDB signals that have been allocated in the Monitor Bit cells. If you move the cursor along the binary numbers, the corresponding DDB signal text string is displayed for each monitor bit. By using this cell with suitable monitor bit settings, the state of the DDB signals can be displayed as various operating conditions or sequences are applied to the IED. This allows you to test the Programmable Scheme Logic (PSL).
3.4
MONITOR BIT 1 TO 8 CELLS
The eight Monitor Bit cells allows you to select eight DDB signals that can be observed in the Test Port Status cell. Each Monitor Bit cell can be assigned to a particular DDB signal. You set it by entering the required DDB signal number from the list of available DDB signals.
3.5
TEST MODE CELL
This cell allows you to perform secondary injection testing. It also lets you test the output s directly by applying menu-controlled test signals. To go into test mode, select the 'Test Mode' option in the Test Mode cell. This takes the IED out of service causing an alarm condition to be recorded and the Out of Service LED to illuminate. This also freezes any
P14D-B/G/L/Z-TM-EN-1
589
Chapter 15 - Commissioning Instructions
P14D
information stored in the CB CONDITION column. In IEC 60870-5-103 versions, it changes the Cause of Transmission (COT) to Test Mode. In Test Mode, the output s are still active. To disable the output s you must select the 's Blocked' option Once testing is complete, return the device back into service by setting the Test Mode Cell back to 'Disabled'. Caution: When the cell is in Test Mode, the Scheme Logic still drives the output relays, which could result in tripping of circuit breakers. To avoid this, set the Test Mode cell to 's Blocked'.
Note: 'Test mode' and 's Blocked' mode can also be selected by energising an opto-input mapped to the Test Mode signal, and the Block signal respectively.
3.6
TEST PATTERN CELL
The Test Pattern cell is used to select the output relay s to be tested when the Test cell is set to 'Apply Test'. The cell has a binary string with one bit for each -configurable output , which can be set to '1' to operate the output and '0' to not operate it.
3.7
TEST CELL
When the 'Apply Test' command in this cell is issued, the s set for operation change state. Once the test has been applied, the command text on the LCD will change to No Operation and the s will remain in the Test state until reset by issuing the 'Remove Test' command. The command text on the LCD will show No Operation after the 'Remove Test' command has been issued. Note: When the Test Mode cell is set to 's Blocked' the Relay O/P Status cell does not show the current status of the output relays and therefore cannot be used to confirm operation of the output relays. Therefore it will be necessary to monitor the state of each in turn.
3.8
TEST LEDS CELL
When the 'Apply Test' command in this cell is issued, the -programmable LEDs illuminate for approximately 2 seconds before switching off, and the command text on the LCD reverts to No Operation.
3.9
TEST AUTORECLOSE CELL
Where the IED provides an auto-reclose function, this cell will be available for testing the sequence of circuit breaker trip and auto-reclose cycles. The ‘3 Pole Test’ command causes the device to perform the first three phase trip/reclose cycle so that associated output s can be checked for operation at the correct times during the cycle. Once the trip output has operated the command text will revert to 'No Operation' whilst the rest of the auto-reclose cycle is performed. To test subsequent three-phase autoreclose cycles, you repeat the ‘3 Pole Test’ command.
590
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 15 - Commissioning Instructions
Note: The default settings for the programmable scheme logic has the ‘AR Trip Test’ signals mapped to the ‘Trip Input’ signals. If the programmable scheme logic has been changed, it is essential that these signals retain this mapping for the ‘Test Auto-reclose’ facility to work.
3.10
RED AND GREEN LED STATUS CELLS
These cells contain binary strings that indicate which of the -programmable red and green LEDs are illuminated when accessing from a remote location. A '1' indicates that a particular LED is illuminated. Note: When the status in both Red LED Status and Green LED Status cells is ‘1’, this indicates the LEDs illumination is yellow.
P14D-B/G/L/Z-TM-EN-1
591
Chapter 15 - Commissioning Instructions
4
COMMISSIONING EQUIPMENT
4.1
MINIMUM EQUIPMENT REQUIRED
P14D
As a minimum, the following equipment is required: ● Multifunctional current and voltage injection test set (where applicable) ● Multimeter with suitable AC current range, and DC voltage ranges of 0 - 440 V and 0 - 250 V respectively ● Continuity tester (if not included in multimeter). ● A portable PC, installed with appropriate software (MiCOM S1 Agile)
4.2
OPTIONAL EQUIPMENT REQUIRED
● Multi-finger test plug: ▪ P992 for test block type P991 ▪ MMLB for test block type MMLG blocks ● Electronic or brushless insulation tester with a DC output not exceeding 500 V ● KITZ K-Bus - EIA(RS)232 protocol converter for testing EIA(RS)485 K-Bus port, if applicable ● EIA(RS)485 to EIA(RS)232 converter for testing EIA(RS)485 Courier/MODBUS/IEC60870-5-103/ DNP3 port, if applicable ● A portable printer (for printing a setting record from the portable PC). ● Phase angle meter (where applicable) ● Phase rotation meter ● Fibre optic power meter (where applicable) ● Fibre optic test leads (where applicable)
592
P14D-B/G/L/Z-TM-EN-1
P14D
5
Chapter 15 - Commissioning Instructions
PRODUCT CHECKS
These product checks are designed to ensure that the device has not been physically damaged prior to commissioning, is functioning correctly and that all input quantity measurements are within the stated tolerances. If the application-specific settings have been applied to the IED prior to commissioning, you should make a copy of the settings. This will allow you to restore them at a later date if necessary. This can be done by: ● Obtaining a setting file from the customer. ● Extracting the settings from the IED itself, using a portable PC with appropriate setting software. If the customer has changed the that prevents unauthorised changes to some of the settings, either the revised should be provided, or the original restored before testing. Note: If the has been lost, a recovery can be obtained from Alstom Grid.
5.1
PRODUCT CHECKS WITH THE IED DE-ENERGISED Warning: The following group of tests should be carried out without the auxiliary supply being applied to the IED and, if applicable, with the trip circuit isolated.
The current and voltage transformer connections must be isolated from the IED for these checks. If a P991 test block is provided, the required isolation can be achieved by inserting test plug type P992. This open circuits all wiring routed through the test block. Before inserting the test plug, you should check the scheme diagram to ensure that this will not cause damage or a safety hazard (the test block may, for example, be associated with protection current transformer circuits). The sockets in the test plug, which correspond to the current transformer secondary windings, must be linked before the test plug is inserted into the test block. Warning: Never open-circuit the secondary circuit of a current transformer since the high voltage produced may be lethal and could damage insulation.
If a test block is not provided, the voltage transformer supply to the IED should be isolated by means of the links or connecting blocks. The line current transformers should be short-circuited and disconnected from the IED terminals. Where means of isolating the auxiliary supply and trip circuit (for example isolation links, fuses and MCB) are provided, these should be used. If this is not possible, the wiring to these circuits must be disconnected and the exposed ends suitably terminated to prevent them from being a safety hazard.
5.1.1
VISUAL INSPECTION Caution: Check the rating information provided with the device. Check that the IED being tested is correct for the line or circuit.
Carefully examine the IED to see that no physical damage has occurred since installation.
P14D-B/G/L/Z-TM-EN-1
593
Chapter 15 - Commissioning Instructions
P14D
Ensure that the case earthing connections (bottom left-hand corner at the rear of the IED case) are used to connect the IED to a local earth bar using an adequate conductor. Check that the current transformer shorting switches in the case are wired into the correct circuit. Ensure that, during withdrawal, they are closed by checking with a continuity tester. The shorting switches are between terminals 21 and 22, 23 and 24, 25 and 26, and 27 and 28.
5.1.2
INSULATION
Insulation resistance tests are only necessary during commissioning if explicitly requested. Isolate all wiring from the earth and test the insulation with an electronic or brushless insulation tester at a DC voltage not exceeding 500 V. Terminals of the same circuits should be temporarily connected together. The main groups of IED terminals are: ● ● ● ● ● ● ● ●
Voltage transformer circuits (not all models) Current transformer circuits (not all models) Supply voltage Opto-inputs Output Relay s EIA(RS)485 communication ports Ethernet communication ports (not all models) Case earth
The insulation resistance should be greater than 100 MW at 500 V. On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected to the IED.
5.1.3
EXTERNAL WIRING Caution: Check that the external wiring is correct according to the relevant IED and scheme diagrams. Ensure that phasing/phase rotation appears to be as expected.
If a P991 test block is provided, check the connections against the scheme diagram. We recommend that you make the supply connections to the live side of the test block (coloured orange) and use the odd numbered terminals. The auxiliary DC voltage supply uses terminals 13 (supply positive) and 14 (supply negative). Unlike the Kseries products, the P40Agile series does not provide a field voltage supply. For K-series retrofit applications where pin-to-pin compatibility is required, the equivalent P40 Agile products emulate the field voltage supply by having internal links between pins 7 and 13, and pins 8 and 14, respectively.
5.1.4
WATCHDOG S
Using a continuity tester, check that the Watchdog s are in the following states: De-energised
Terminals 3-5
Closed
4-6
Open
594
P14D-B/G/L/Z-TM-EN-1
P14D
5.1.5
Chapter 15 - Commissioning Instructions
POWER SUPPLY
The IED can accept a nominal DC voltage from 24 V DC to 250 V DC, or a nominal AC voltage from 110 V AC to 240 V AC at 50 Hz or 60 Hz. Ensure that the power supply is within this operating range. The power supply must be rated at 12 Watts. Warning: Do not energise the IED or interface unit using the battery charger with the battery disconnected as this can irreparably damage the power supply circuitry.
Caution: Energise the IED only if the auxiliary supply is within the specified operating ranges. If a test block is provided, it may be necessary to link across the front of the test plug to connect the auxiliary supply to the IED.
5.2
PRODUCT CHECKS WITH THE IED ENERGISED Warning: The current and voltage transformer connections must remain isolated from the IED for these checks. The trip circuit should also remain isolated to prevent accidental operation of the associated circuit breaker.
The following group of tests verifies that the IED hardware and software is functioning correctly and should be carried out with the supply applied to the IED.
5.2.1
WATCHDOG S
Using a continuity tester, check that the Watchdog s are in the following states: Terminals
Energised
3-5
Open
4-6
Closed
5.2.2
TEST LCD
The Liquid Crystal Display (LCD) is designed to operate in a wide range of substation ambient temperatures. For this purpose, the IEDs have an LCD Contrast setting. The contrast is factory pre-set, but it may be necessary to adjust the contrast to give the best in-service display. To change the contrast, you can increment or decrement the LCD Contrast cell in the CONFIGURATION column. Caution: Before applying a contrast setting, make sure that it will not make the display so light or dark such that menu text becomes unreadable. It is possible to restore the visibility of a display by ing a setting file, with the LCD Contrast set within the typical range of 7 - 11.
P14D-B/G/L/Z-TM-EN-1
595
Chapter 15 - Commissioning Instructions
5.2.3
P14D
DATE AND TIME
The date and time is stored in non-volatile memory. If the values are not already correct, set them to the correct values. The method of setting will depend on whether accuracy is being maintained by the IRIG-B port or by the IED's internal clock. When using IRIG-B to maintain the clock, the IED must first be connected to the satellite clock equipment (usually a P594), which should be energised and functioning. 1. 2. 3. 4. 5.
Set the IRIG-B Sync cell in the DATE AND TIME column to ‘Enabled’. Ensure the IED is receiving the IRIG-B signal by checking that cell IRIG-B Status reads ‘Active’. Once the IRIG-B signal is active, adjust the time offset of the universal co coordinated time (satellite clock time) on the satellite clock equipment so that local time is displayed. Check that the time, date and month are correct in the Date/Time cell. The IRIG-B signal does not contain the current year so it will need to be set manually in this cell. Reconnect the IRIG-B signal.
If the time and date is not being maintained by an IRIG-B signal, ensure that the IRIG-B Sync cell in the DATE AND TIME column is set to ‘Disabled’. 1.
5.2.4
Set the date and time to the correct local time and date using Date/Time cell or using the serial protocol.
TEST LEDS
On power-up, all LEDs should first flash yellow. Following this, the green "Healthy" LED should illuminate indicating that the device is healthy. The IED's non-volatile memory stores the states of the alarm, the trip, and the -programmable LED indicators (if configured to latch). These indicators may also illuminate when the auxiliary supply is applied. If any of these LEDs are ON then they should be reset before proceeding with further testing. If the LEDs successfully reset (the LED goes off), no testing is needed for that LED because it is obviously operational. Note: In most cases, alarms related to the communications channels will not reset at this stage.
5.2.5
TEST ALARM AND OUT-OF-SERVICE LEDS
The alarm and out of service LEDs can be tested using the COMMISSION TESTS menu column. 1. 2.
Set the Test Mode cell to ‘s Blocked’. Check that the out of service LED illuminates continuously and the alarm LED flashes.
It is not necessary to return the Test Mode cell to ‘Disabled’ at this stage because the test mode will be required for later tests.
5.2.6
TEST TRIP LED
The trip LED can be tested by initiating a manual circuit breaker trip. However, the trip LED will operate during the setting checks performed later. Therefore no further testing of the trip LED is required at this stage.
5.2.7
TEST -PROGRAMMABLE LEDS
To test these LEDs, set the Test LEDs cell to 'Apply Test'. Check that all -programmable LEDs illuminate.
596
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 15 - Commissioning Instructions
5.2.8
TEST OPTO-INPUTS
This test checks that all the opto-inputs on the IED are functioning correctly. The opto-inputs should be energised one at a time. For terminal numbers, please see the external connection diagrams in the "Wiring Diagrams" chapter. Ensuring correct polarity, connect the supply voltage to the appropriate terminals for the input being tested. The status of each opto-input can be viewed using either the Opto I/P Status cell in the SYSTEM DATA column, or the Opto I/P Status cell in the COMMISSION TESTS column. A '1' indicates an energised input and a '0' indicates a de-energised input. When each opto-input is energised, one of the characters on the bottom line of the display changes to indicate the new state of the input.
5.2.9
TEST OUTPUT RELAYS
This test checks that all the output relays are functioning correctly. 1. 2. 3. 4. 5. 6. 7. 8. 9.
Ensure that the IED is still in test mode by viewing the Test Mode cell in the COMMISSION TESTS column. Ensure that it is set to 'Blocked'. The output relays should be energised one at a time. To select output relay 1 for testing, set the Test Pattern cell as appropriate. Connect a continuity tester across the terminals corresponding to output relay 1 as shown in the external connection diagram. To operate the output relay set the Test cell to 'Apply Test'. Check the operation with the continuity tester. Measure the resistance of the s in the closed state. Reset the output relay by setting the Test cell to 'Remove Test'. Repeat the test for the remaining output relays. Return the IED to service by setting the Test Mode cell in the COMMISSION TESTS menu to 'Disabled'.
5.2.10
TEST SERIAL COMMUNICATION PORT RP1
You need only perform this test if the IED is to be accessed from a remote location. The test will vary depending on the communications protocol used. It is not the intention of this test to the operation of the complete communication link between the IED and the remote location, just the IED's rear communication port and, if applicable, the protocol converter. 5.2.10.1
CHECK PHYSICAL CONNECTIVITY
The rear communication port RP1 is presented on terminals 54 and 56. Screened twisted pair cable is used to make a connection to the port. The cable screen should be connected to the earth link just below pin 56:
P14D-B/G/L/Z-TM-EN-1
597
Chapter 15 - Commissioning Instructions
P14D
E01402
Figure 168: RP1 physical connection For K-Bus applications, pins 54 and 56 are not polarity sensitive and it does not matter which way round the wires are connected. EIA(RS)485 is polarity sensitive, so you must ensure the wires are connected the correct way round (pin 54 is positive, pin 56 is negative). If K-Bus is being used, a Kitz protocol converter (KITZ101, KITZ102 OR KITZ201) will have been installed to convert the K-Bus signals into RS232. Likewise, if RS485 is being used, an RS485-RS232 converter will have been installed. In the case where a protocol converter is being used, a laptop PC running appropriate software (such as MiCOM S1 Agile) can be connected to the incoming side of the protocol converter. An example for K-bus to RS232 conversion is shown below. RS485 to RS232 would follow the same principle, only using a RS485-RS232 converter. Most modern laptops have USB ports, so it is likely you will also require a RS232 to USB converter too.
IED
IED
IED
RS232
Computer
RS232-USB converter
K-Bus
KITZ protocol converter
V01001
Figure 169: Remote communication using K-bus 5.2.10.2
CHECK LOGICAL CONNECTIVITY
The logical connectivity depends on the chosen data protocol, but the principles of testing remain the same for all protocol variants: 1. 2. 3.
598
Ensure that the communications baud rate and parity settings in the application software are set the same as those on the protocol converter. For Courier models, ensure that you have set the correct RP1 address Check that communications can be established with this IED using the portable PC/Master Station.
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 15 - Commissioning Instructions
5.2.11
TEST SERIAL COMMUNICATION PORT RP2
RP2 is only available on selected models. If applicable, this test is the same as for RP1 only the relevant terminals are 82 and 84.
5.2.12
TEST ETHERNET COMMUNICATION
To test the Ethernet communication: 1. 2.
3.
Connect a portable PC running the appropriate IEC 61850 Client Software or MMS browser to the IED's Ethernet port. Configure the IP parameters (IP Address, Subnet Mask, Gateway) and SNTP time synchronisation parameters (SNTP Server 1, SNTP Server 2). You can import the IP parameter configuration from an SCL file or apply them manually using the IED Configurator tool, which is installed as part of MiCOM S1 Agile. These cannot be configured via the IED’s HMI on the front . Check that communication with this IED can be established.
Note: If the assigned IP address is duplicated elsewhere on the same network, the remote communications will operate in an indeterminate way. However, the device will check for a conflict on every IP configuration change and at power up. An alarm will be raised if an IP conflict is detected. The device can be configured to accept data from networks other than the local network by using the ‘Gateway’ setting.
5.2.13
TEST CURRENT INPUTS
This test verifies that the current measurement inputs are configured correctly. All devices leave the factory set for operation at a system frequency of 50 Hz. If operation at 60 Hz is required then this must be set in the Frequency cell in the SYSTEM DATA column. 1. 2. 3.
Apply current equal to the line current transformer secondary winding rating to each current transformer input in turn. Check its magnitude using a multi-meter or test set readout. The corresponding reading can then be checked in the MEASUREMENTS 1 column. Record the displayed value. The measured current values will either be in primary or secondary Amperes. If the Local Values cell in the MEASURE’T SETUP column is set to 'Primary', the values displayed should be equal to the applied current multiplied by the corresponding current transformer ratio (set in the TRANS. RATIOS column), as shown below. If the Local Values cell is set to Secondary, the value displayed should be equal to the applied current.
Note: If a PC connected to the IED using the rear communications port is being used to display the measured current, the process will be similar. However, the setting of the Remote Values cell in the MEASURE’T SETUP column will determine whether the displayed values are in primary or secondary Amperes.
The measurement accuracy of the IED is ±1%. However, an additional allowance must be made for the accuracy of the test equipment being used. Cell in MEASUREMENTS 1
Corresponding CT ratio (in TRANS. RATIOS column)
IA magnitude IB magnitude IC magnitude
Phase CT Primary / Phase CT Sec'y
IN measured mag
E/F CT Primary / E/F CT Secondary
P14D-B/G/L/Z-TM-EN-1
599
Chapter 15 - Commissioning Instructions
Cell in MEASUREMENTS 1 ISEF magnitude
5.2.14
P14D
Corresponding CT ratio (in TRANS. RATIOS column) SEF CT Primary / SEF CT Secondary
TEST VOLTAGE INPUTS
This test verifies that the voltage measurement inputs are configured correctly. 1. 2. 3.
Apply rated voltage to each voltage transformer input in turn Check its magnitude using a multimeter or test set readout. The corresponding reading can then be checked in the MEASUREMENTS 1 column. Record the value displayed. The measured voltage values will either be in primary or secondary Volts. If the Local Values cell in the MEASURE’T SETUP column is set to 'Primary', the values displayed should be equal to the applied voltage multiplied by the corresponding voltage transformer ratio (set in the TRANS. RATIOS column) as shown below. If the Local Values cell is set to Secondary, the value displayed should be equal to the applied voltage.
Note: If a PC connected to the IED using the rear communications port is being used to display the measured current, the process will be similar. However, the setting of the Remote Values cell in the MEASURE’T SETUP column will determine whether the displayed values are in primary or secondary Amperes.
Cell in MEASUREMENTS 1
Corresponding VT ratio (in TRANS. RATIOS column)
VAN magnitude VBN magnitude VCN magnitude
Main VT Primary / Main VT Sec'y
C/S Voltage Mag
C/S VT Primary / C/S VT Secondary
600
P14D-B/G/L/Z-TM-EN-1
P14D
6
Chapter 15 - Commissioning Instructions
SETTING CHECKS
The setting checks ensure that all of the application-specific settings (both the IED’s function and programmable scheme logic settings) have been correctly applied. Note: If applicable, the trip circuit should remain isolated during these checks to prevent accidental operation of the associated circuit breaker.
6.1
APPLY APPLICATION-SPECIFIC SETTINGS
There are two different methods of applying the settings to the IED ● Transferring settings to the IED from a pre-prepared setting file using MiCOM S1 Agile ● Enter the settings manually using the IED’s front HMI
6.1.1
TRANSFERRING SETTINGS FROM A SETTINGS FILE
This is the preferred method for transferring function settings as it is much faster, and there is a lower margin for error. 1.
2. 3. 4.
Connect a laptop/PC (that is running MiCOM S1 Agile) to the IED's front port (could be serial RS232 or USB depending on the product), or a rear Courier communications port (with a KITZ protocol converter if necessary). Power on the IED Right-click on the appropriate device name in the System Explorer pane and select Send In the Send to dialog select the setting files and click Send
Note: If the device name does not already exist in the System Explorer system, then first perform a Quick Connect to the IED. It will then be necessary to manually add the settings file to the device name in the Studio Explorer system. Refer to the MiCOM S1 Studio help for details of how to do this.
6.1.2
ENTERING SETTINGS USING THE HMI
It is not possible to change the PSL using the IED’s front HMI. 1. 2.
Starting at the default display, press the Down cursor key to show the first column heading. Use the horizontal cursor keys to select the required column heading.
3. 4.
Use the vertical cursor keys to view the setting data in the column. To return to the column header, either press the Up cursor key for a second or so, or press the Cancel key once. It is only possible to move across columns at the column heading level. To return to the default display, press the Up cursor key or the Cancel key from any of the column headings. If you use the auto-repeat function of the Up cursor key, you cannot go straight to the default display from one of the column cells because the auto-repeat stops at the column heading. To change the value of a setting, go to the relevant cell in the menu, then press the Enter key to change the cell value. A flashing cursor on the LCD shows that the value can be changed. You may be prompted for a first. To change the setting value, press the vertical cursor keys. If the setting to be changed is a binary value or a text string, select the required bit or character to be changed using the left and right cursor keys.
5.
6.
7.
P14D-B/G/L/Z-TM-EN-1
601
Chapter 15 - Commissioning Instructions
8. 9.
P14D
Press the Enter key to confirm the new setting value or the Clear key to discard it. The new setting is automatically discarded if it is not confirmed within 15 seconds. For protection group settings and disturbance recorder settings, the changes must be confirmed before they are used. When all required changes have been entered, return to the column heading level and press the down cursor key. Before returning to the default display, the following prompt appears. Update settings? ENTER or CLEAR
10.
Press the Enter key to accept the new settings or press the Clear key to discard the new settings.
Note: If the menu time-out occurs before the setting changes have been confirmed, the setting values are also discarded. Control and settings are updated immediately after they are entered, without the Update settings prompt. It is not possible to change the PSL using the IED’s front HMI.
Caution: Where the installation needs application-specific PSL, the relevant .psl files, must be transferred to the IED, for each and every setting group that will be used. If you do not do this, the factory default PSL will still be resident. This may have severe operational and safety consequences.
602
P14D-B/G/L/Z-TM-EN-1
P14D
7
Chapter 15 - Commissioning Instructions
PROTECTION TIMING CHECKS
There is no need to check every protection function. Only one protection function needs to be checked as the purpose is to the timing on the processor is functioning correctly.
7.1
OVERCURRENT CHECK
If the overcurrent protection function is being used, test the overcurrent protection for stage 1. 1.
Check for any possible dependency conditions and simulate as appropriate.
2. 3. 4. 5. 6.
In the CONFIGURATION column, disable all protection elements other than the one being tested. Make a note of which elements need to be re-enabled after testing. Connect the test circuit Perform the test Check the operating time
7.2 1. 2. 3.
CONNECTING THE TEST CIRCUIT Use the PSL to determine which output relay will operate when an overcurrent trip occurs. Use the output relay assigned to Trip Output A. Use the PSL to map the protection stage under test directly to an output relay.
Note: If using the default PSL, use output relay 3 as this is already mapped to the DDB signal Trip Command Out.
4. 5.
6.
Connect the output relay so that its operation will trip the test set and stop the timer. Connect the current output of the test set to the A-phase current transformer input. If the I>1 Directional cell in the OVERCURRENT column is set to ‘Directional Fwd’, the current should flow out of terminal 21. If set to ‘Directional Rev’, it should flow into terminal 21. If the I>1 Directional cell in the OVERCURRENT column has been set to ‘Directional Fwd’ or ‘Directional Rev’, the rated voltage should be applied to terminals 18 and 19. Ensure that the timer starts when the current is applied.
Note: If the timer does not stop when the current is applied and stage 1 has been set for directional operation, the connections may be incorrect for the direction of operation set. Try again with the current connections reversed.
7.3 1. 2. 3. 4.
7.4
PERFORMING THE TEST Ensure that the timer is reset. Apply a current of twice the setting shown in the I>1 Current Set cell in the OVERCURRENT column. Note the time displayed when the timer stops. Check that the red trip LED has illuminated.
CHECK THE OPERATING TIME
Check that the operating time recorded by the timer is within the range shown below. For all characteristics, allowance must be made for the accuracy of the test equipment being used.
P14D-B/G/L/Z-TM-EN-1
603
Chapter 15 - Commissioning Instructions
P14D
Operating time at twice current setting and time multiplier/ time dial setting of 1.0
Characteristic
Nominal (seconds)
Range (seconds)
DT
I>1 Time Delay] setting
Setting ±2%
IEC S Inverse
10.03
9.53 - 10.53
IEC V Inverse
13.50
12.83 - 14.18
IEC E Inverse
26.67
24.67 - 28.67
UK LT Inverse
120.00
114.00 - 126.00
IEEE M Inverse
3.8
3.61 - 4.0
IEEE V Inverse
7.03
6.68 - 7.38
IEEE E Inverse
9.50
9.02 - 9.97
US Inverse
2.16
2.05 - 2.27
US ST Inverse
12.12
11.51 - 12.73
Note: With the exception of the definite time characteristic, the operating times given are for a Time Multiplier Setting (TMS) or Time Dial Setting (TDS) of 1. For other values of TMS or TDS, the values need to be modified accordingly.
Note: For definite time and inverse characteristics there is an additional delay of up to 0.02 second and 0.08 second respectively. You may need to add this the IED's acceptable range of operating times.
Caution: On completion of the tests, you must restore all settings that were disabled for testing purposes.
604
P14D-B/G/L/Z-TM-EN-1
P14D
8
Chapter 15 - Commissioning Instructions
ONLOAD CHECKS
Onload checks can only be carried out if there are no restrictions preventing the energisation of the plant, and the other devices in the group have already been commissioned. Remove all test leads and temporary shorting links, then replace any external wiring that has been removed to allow testing. Warning: If any external wiring has been disconnected for the commissioning process, replace it in accordance with the relevant external connection or scheme diagram.
8.1 1. 2.
3. 4.
CONFIRM CURRENT CONNECTIONS Measure the current transformer secondary values for each input using a multimeter connected in series with the corresponding current input. Check that the current transformer polarities are correct by measuring the phase angle between the current and voltage, either against a phase meter already installed on site and known to be correct or by determining the direction of power flow by ing the system control centre. Ensure the current flowing in the neutral circuit of the current transformers is negligible. Compare the values of the secondary phase currents and phase angle with the measured values, which can be found in the MEASUREMENTS 1 column.
If the Local Values cell is set to ‘Secondary’, the values displayed should be equal to the applied secondary voltage. The values should be within 1% of the applied secondary voltages. However, an additional allowance must be made for the accuracy of the test equipment being used. If the Local Values cell is set to ‘Primary’, the values displayed should be equal to the applied secondary voltage multiplied the corresponding voltage transformer ratio set in the TRANS. RATIOS column. The values should be within 1% of the expected values, plus an additional allowance for the accuracy of the test equipment being used.
8.2 1. 2. 3.
CONFIRM VOLTAGE CONNECTIONS Using a multimeter, measure the voltage transformer secondary voltages to ensure they are correctly rated. Check that the system phase rotation is correct using a phase rotation meter. Compare the values of the secondary phase voltages with the measured values, which can be found in the MEASUREMENTS 1 menu column. Cell in MEASUREMENTS 1 Column
VAB Magnitude VBC Magnitude VCA Magnitude VAN Magnitude VBN Magnitude VCN Magnitude C/S Voltage Mag.
P14D-B/G/L/Z-TM-EN-1
Corresponding VT ratio in ‘TRANS. RATIO column
Main VT Primary / Main VT Sec'y
CS VT Primary / CS VT Secondary
605
Chapter 15 - Commissioning Instructions
P14D
If the Local Values cell is set to ‘Secondary’, the values displayed should be equal to the applied secondary voltage. The values should be within 1% of the applied secondary voltages. However, an additional allowance must be made for the accuracy of the test equipment being used. If the Local Values cell is set to ‘Primary’, the values displayed should be equal to the applied secondary voltage multiplied the corresponding voltage transformer ratio set in the TRANS. RATIOS column. The values should be within 1% of the expected values, plus an additional allowance for the accuracy of the test equipment being used.
8.3
ON-LOAD DIRECTIONAL TEST
This test ensures that directional overcurrent and fault locator functions have the correct forward/reverse response to fault and load conditions. For this test you must first know the actual direction of power flow on the system. If you do not already know this you must determine it using adjacent instrumentation or protection already in-service. ● For load current flowing in the Forward direction (power export to the remote line end), the A Phase Watts cell in the MEASUREMENTS 2 column should show positive power g. ● For load current flowing in the Reverse direction (power import from the remote line end), the A Phase Watts cell in the MEASUREMENTS 2 column should show negative power g. Note: This check applies only for Measurement Modes 0 (default), and 2. This should be checked in the MEASURE’T. SETUP column (Measurement Mode = 0 or 2). If measurement modes 1 or 3 are used, the expected power flow g would be opposite to that shown above.
In the event of any uncertainty, check the phase angle of the phase currents with respect to their phase voltage.
606
P14D-B/G/L/Z-TM-EN-1
P14D
9 1. 2.
3. 4. 5. 6.
7. 8. 9.
Chapter 15 - Commissioning Instructions
FINAL CHECKS Remove all test leads and temporary shorting leads. If you have had to disconnect any of the external wiring in order to perform the wiring verification tests, replace all wiring, fuses and links in accordance with the relevant external connection or scheme diagram. Ensure that the IED has been restored to service by checking that the Test Mode cell in the COMMISSION TESTS column is set to ‘Disabled’. The settings applied should be carefully checked against the required application-specific settings to ensure that they are correct, and have not been mistakenly altered during testing. Ensure that all protection elements required have been set to Enabled in the CONFIGURATION column If the IED is in a new installation or the circuit breaker has just been maintained, the circuit breaker maintenance and current counters should be zero. These counters can be reset using the Reset All Values cell. If the required access level is not active, the device will prompt for a to be entered so that the setting change can be made. If the menu language has been changed to allow accurate testing it should be restored to the customer’s preferred language. If a P991/MMLG test block is installed, remove the P992/MMLB test plug and replace the cover so that the protection is put into service. Ensure that all event records, fault records, disturbance records, alarms and LEDs and communications statistics have been reset.
P14D-B/G/L/Z-TM-EN-1
607
Chapter 15 - Commissioning Instructions
608
P14D
P14D-B/G/L/Z-TM-EN-1
MAINTENANCE AND TROUBLESHOOTING CHAPTER 16
Chapter 16 - Maintenance and Troubleshooting
610
P14D
P14D-B/G/L/Z-TM-EN-1
P14D
1
Chapter 16 - Maintenance and Troubleshooting
CHAPTER OVERVIEW
The Maintenance and Troubleshooting chapter provides details of how to maintain and troubleshoot products based on the Px4x and P40Agile platforms. Always follow the warning signs in this chapter Failure to do so may result injury or defective equipment. Caution: Before carrying out any work on the equipment you should be familiar with the contents of the Safety Section or the Safety Guide SFTY/4LM and the ratings on the equipment’s rating label.
The troubleshooting part of the chapter allows an error condition on the IED to be identified so that appropriate corrective action can be taken. If the IED develops a fault, it is usually possible to identify which module needs replacing. It is not possible to perform an on-site repair to a faulty module. If you return a faulty unit or module to the manufacturer or one of their approved service centres, you should include a completed copy of the Repair or Modification Return Authorization (RMA) form. This chapter contains the following sections: Chapter Overview Maintenance Troubleshooting
611 612 614
P14D-B/G/L/Z-TM-EN-1
611
Chapter 16 - Maintenance and Troubleshooting
2
MAINTENANCE
2.1
MAINTENANCE CHECKS
P14D
In view of the critical nature of the application, Alstom Grid products should be checked at regular intervals to confirm they are operating correctly. Alstom Grid products are designed for a life in excess of 20 years. The devices are self-supervising and so require less maintenance than earlier designs of protection devices. Most problems will result in an alarm, indicating that remedial action should be taken. However, some periodic tests should be carried out to ensure that they are functioning correctly and that the external wiring is intact. It is the responsibility of the customer to define the interval between maintenance periods. If your organisation has a Preventative Maintenance Policy, the recommended product checks should be included in the regular program. Maintenance periods depend on many factors, such as: ● ● ● ● ●
The operating environment The accessibility of the site The amount of available manpower The importance of the installation in the power system The consequences of failure
Although some functionality checks can be performed from a remote location, these are predominantly restricted to checking that the unit is measuring the applied currents and voltages accurately, and checking the circuit breaker maintenance counters. For this reason, maintenance checks should also be performed locally at the substation. Caution: Before carrying out any work on the equipment you should be familiar with the contents of the Safety Section or the Safety Guide SFTY/4LM and the ratings on the equipment’s rating label.
2.1.1
ALARMS
First check the alarm status LED to see if any alarm conditions exist. If so, press the Read key repeatedly to step through the alarms. After dealing with any problems, clear the alarms. This will clear the relevant LEDs.
2.1.2
OPTO-ISOLATORS
Check the opto-inputs by repeating the commissioning test detailed in the Commissioning chapter.
2.1.3
OUTPUT RELAYS
Check the output relays by repeating the commissioning test detailed in the Commissioning chapter.
2.1.4
MEASUREMENT ACCURACY
If the power system is energised, the measured values can be compared with known system values to check that they are in the expected range. If they are within a set range, this indicates that the A/D conversion and the calculations are being performed correctly. Suitable test methods can be found in Commissioning chapter. Alternatively, the measured values can be checked against known values injected into the device using the test block, (if fitted) or injected directly into the IED's terminals. Suitable test methods can be found in the Commissioning chapter. These tests will prove the calibration accuracy is being maintained.
612
P14D-B/G/L/Z-TM-EN-1
P14D
2.2
Chapter 16 - Maintenance and Troubleshooting
REPLACING THE UNIT
If your product should develop a fault while in service, depending on the nature of the fault, the watchdog s will change state and an alarm condition will be flagged. In the case of a fault, you should normally replace the cradle which slides easily out of the case. This can be done without disturbing the scheme wiring. In the unlikely event that the problem lies with the wiring and/or terminals, then you must replace the complete device, rewire and re-commission the device. Caution: If the repair is not performed by an approved service centre, the warranty will be invalidated. Caution: Before carrying out any work on the equipment, you should be familiar with the contents of the Safety Information section of this guide or the Safety Guide SFTY/4LM, as well as the ratings on the equipment’s rating label. This should ensure that no damage is caused by incorrect handling of the electronic components. Warning: Before working at the rear of the unit, isolate all voltage and current supplying it.
Note: The Alstom Grid products have integral current transformer shorting switches which will close, for safety reasons, when the terminal block is removed.
To replace the cradle without disturbing the case and wiring: 1. 2. 3.
Remove the faceplate. Carefully withdraw the cradle from the front. To reinstall the unit, follow the above instructions in reverse, ensuring that each terminal block is relocated in the correct position and the chassis ground, IRIG-B and fibre optic connections are replaced. The terminal blocks are labelled alphabetically with ‘A’ on the left hand side when viewed from the rear. Once the unit has been reinstalled, it should be re-commissioned as set out in the Commissioning chapter.
2.3
CLEANING Warning: Before cleaning the IED, ensure that all AC and DC supplies and transformer connections are isolated, to prevent any chance of an electric shock while cleaning.
Only clean the equipment with a lint-free cloth dampened with clean water. Do not use detergents, solvents or abrasive cleaners as they may damage the product's surfaces and leave a conductive residue.
P14D-B/G/L/Z-TM-EN-1
613
Chapter 16 - Maintenance and Troubleshooting
P14D
3
TROUBLESHOOTING
3.1
SELF-DIAGNOSTIC SOFTWARE
The IED includes several self-monitoring functions to check the operation of its hardware and software while in service. If there is a problem with the hardware or software, it should be able to detect and report the problem, and attempt to resolve the problem by performing a reboot. In this case, the device would be out of service for a short time, during which the ‘Healthy’ LED on the front of the device is switched OFF and the watchdog at the rear is ON. If the restart fails to resolve the problem, the unit takes itself permanently out of service; the ‘Healthy’ LED stays OFF and watchdog stays ON. If a problem is detected by the self-monitoring functions, the device attempts to store a maintenance record to allow the nature of the problem to be communicated to the . The self-monitoring is implemented in two stages: firstly a thorough diagnostic check which is performed on boot-up, and secondly a continuous self-checking operation, which checks the operation of the critical functions whilst it is in service.
3.2
POWER-UP ERRORS
If the IED does not appear to power up, use the following checks to determine whether the fault is in the external wiring, auxiliary fuse, IED power supply module or IED front . Test
Check
Action
1
Measure the voltage on terminals 13 and 14. the If the auxiliary voltage is correct, go to test 2. Otherwise check the wiring and voltage level and polarity against the rating label fuses in the auxiliary supply.
2
Check the LEDs and LCD backlight switch on at power-up. Also check the N/O (normally open) watchdog on terminals 4 and 6 to see if they close.
3.3
If the LEDs and LCD backlight switch on, or the Watchdog s close and no error code is displayed, the error is probably on the main processor board. If the LEDs and LCD backlight do not switch on and the N/O Watchdog does not close, the fault is probably in the IED power supply module.
ERROR MESSAGE OR CODE ON POWER-UP
The IED performs a self-test during power-up. If it detects an error, a message appears on the LCD and the power-up sequence stops. If the error occurs when the IED application software is running, a maintenance record is created and the device reboots. Test
Check
Action
1
If the IED locks up and displays an error code permanently, go to test 2. Is an error message or code permanently displayed during If the IED prompts for input, go to test 3. power up? If the IED reboots automatically, go to test 4.
2
Record displayed error and re-apply IED supply.
Record whether the same error code is displayed when the IED is rebooted, then the local service centre stating the error code and product details.
3
The IED displays a message for corrupt settings and prompts for the default values to be restored for the affected settings.
The power-up tests have detected corrupted IED settings. Restore the default settings to allow the power-up to complete, and then reapply the application-specific settings.
The IED resets when the power-up is complete. A record error code is displayed.
Programmable scheme logic error due to excessive execution time. Restore the default settings by powering up with both horizontal cursor keys pressed, then confirm restoration of defaults at the prompt using the Enter key. If the IED powers up successfully, check the programmable logic for paths. Other error codes relate to software errors on the main processor board, the local service centre.
4
614
P14D-B/G/L/Z-TM-EN-1
P14D
3.4
Chapter 16 - Maintenance and Troubleshooting
OUT OF SERVICE LED ON AT POWER-UP
Test
Check
Action
1
Using the IED menu, confirm the Commission Test or Test If the setting is Enabled, disable the test mode and make sure the Out of Mode setting is Enabled. If it is not Enabled, go to test 2. Service LED is OFF.
2
Check for the H/W Fail maintenance record. This indicates a discrepancy between the IED model number and the hardware. Examine the Maint Data; cell. This indicates the causes of the failure using bit fields: Bit Meaning
Select the VIEW RECORDS column then view the last maintenance record from the menu.
3.5
0
The application 'type' field in the Cortec does not match the software ID
1
The 'subset' field in the model number does not match the software ID
2
The 'platform' field in the model number does not match the software ID
3
The 'product type' field in the model number does not match the software ID
4
The 'protocol' field in the Cortec does not match the software ID
5
The 'model' field in the Cortec does not match the software ID
6
The first 'software version' field in the does not match the software ID
7
The second 'software version' field in the Cortec does not match the software ID
8
No VTs are fitted
9
No CTs are fitted
10
No Earth CT is fitted
11
No SEF CT is fitted
ERROR CODE DURING OPERATION
The IED performs continuous self-checking. If the IED detects an error it displays an error message, logs a maintenance record and after a short delay resets itself. A permanent problem (for example due to a hardware fault) is usually detected in the power-up sequence. In this case the IED displays an error code and halts. If the problem was transient, the IED reboots correctly and continues operation. By examining the maintenance record logged, the nature of the detected fault can be determined.
3.6
MAL-OPERATION DURING TESTING
3.6.1
FAILURE OF OUTPUT S
An apparent failure of the relay output s can be caused by the configuration. Perform the following tests to identify the real cause of the failure. The self-tests that the coils of the output relay s have been energized. An error is displayed if there is a fault in the output relay board. Check
Test
Action If this LED is ON, the relay may be in test mode or the protection has been disabled due to a hardware error.
1
Is the Out of Service LED ON?
2
Examine the status in the Commissioning section If the relevant bits of the status are operated, go to test 4; if not, of the menu. go to test 3.
P14D-B/G/L/Z-TM-EN-1
615
Chapter 16 - Maintenance and Troubleshooting
Test
P14D
Check
Action
3
Examine the fault record or use the test port to check the protection element is operating correctly.
If the protection element does not operate, check the test is correctly applied. If the protection element operates, check the programmable logic to make sure the protection element is correctly mapped to the s.
4
Using the Commissioning or Test mode function, apply a test pattern to the relevant relay output s. Consult the correct external connection diagram and use a continuity tester at the rear of the relay to check the relay output s operate.
If the output relay operates, the problem must be in the external wiring to the relay. If the output relay does not operate the output relay s may have failed (the self-tests that the relay coil is being energized). Ensure the closed resistance is not too high for the continuity tester to detect.
3.6.2
FAILURE OF OPTO-INPUTS
The opto-isolated inputs are mapped onto the IED's internal DDB signals using the programmable scheme logic. If an input is not recognized by the scheme logic, use the Opto I/P Status cell in the COMMISSION TESTS column to check whether the problem is in the opto-input itself, or the mapping of its signal to the scheme logic functions. If the device does not correctly read the opto-input state, test the applied signal. the connections to the opto-input using the wiring diagram and the nominal voltage settings in the OPTO CONFIG column. To do this: 1.
Select the nominal battery voltage for all opto-inputs by selecting one of the five standard ratings in the Global Nominal V cell. 2. Select 'Custom' to set each opto-input individually to a nominal voltage. 3. Using a voltmeter, check that the voltage on its input terminals is greater than the minimum pick-up level (See the Technical Specifications chapter for opto pick-up levels). If the signal is correctly applied, this indicates failure of an opto-input, which case, the complete cradle should be replaced.
3.6.3
INCORRECT ANALOGUE SIGNALS
If the measured analogue quantities do not seem correct, use the measurement function to determine the type of problem. The measurements can be configured in primary or secondary . 1. 2. 3. 4.
Compare the displayed measured values with the actual magnitudes at the terminals. Check the correct terminals are used Check the CT and VT ratios set are correct. Check the phase displacement to confirm the inputs are correctly connected
3.7
PSL EDITOR TROUBLESHOOTING
A failure to open a connection could be due to one or more of the following: ● ● ● ● ● ●
3.7.1
The IED address is not valid (this address is always 1 for the front port) in not valid Communication set-up (COM port, Baud rate, or Framing) is not correct Transaction values are not suitable for the IED or the type of connection The connection cable is not wired correctly or broken The option switches on any protocol converter used may be incorrectly set
DIAGRAM RECONSTRUCTION
Although a scheme can be extracted from an IED, a facility is provided to recover a scheme if the original file is unobtainable.
616
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 16 - Maintenance and Troubleshooting
A recovered scheme is logically correct but much of the original graphical information is lost. Many signals are drawn in a vertical line down the left side of the canvas. Links are drawn orthogonally using the shortest path from A to B. Any annotation added to the original diagram such as titles and notes are lost. Sometimes a gate type does not appear as expected. For example, a single-input AND gate in the original scheme appears as an OR gate when ed. Programmable gates with an inputs-to-trigger value of 1 also appear as OR gates
3.7.2
PSL VERSION CHECK
The PSL is saved with a version reference, time stamp and CRC check. This gives a visual check whether the default PSL is in place or whether a new application has been ed.
3.8
REPAIR AND MODIFICATION PROCEDURE
Please follow these steps to return an Automation product to us: 1.
2.
3.
4.
5.
Get the Repair and Modification Return Authorization (RMA) form For an electronic version of the RMA form, go to the following url: http://www.alstom.com/grid/productrepair/ Fill in the RMA form Fill in only the white part of the form. Please ensure that all fields marked (M) are completed such as: ▪ Equipment model ▪ Model No. and Serial No. ▪ Description of failure or modification required (please be specific) ▪ Value for customs (in case the product requires export) ▪ Delivery and invoice addresses ▪ details Send the RMA form to your local For a list of local service s worldwide, go to following url: http://www.alstom.com/grid/productrepair/ The local service provides the shipping information Your local service provides you with all the information needed to ship the product: ▪ Pricing details ▪ RMA number ▪ Repair centre address If required, an acceptance of the quote must be delivered before going to the next stage. Send the product to the repair centre ▪ Address the shipment to the repair centre specified by your local ▪ Make sure all items are packaged in an anti-static bag and foam protection ▪ Make sure a copy of the import invoice is attached with the returned unit ▪ Make sure a copy of the RMA form is attached with the returned unit ▪ E-mail or fax a copy of the import invoice and airway bill document to your local .
P14D-B/G/L/Z-TM-EN-1
617
Chapter 16 - Maintenance and Troubleshooting
618
P14D
P14D-B/G/L/Z-TM-EN-1
TECHNICAL SPECIFICATIONS CHAPTER 17
Chapter 17 - Technical Specifications
620
P14D
P14D-B/G/L/Z-TM-EN-1
P14D
1
Chapter 17 - Technical Specifications
CHAPTER OVERVIEW
This chapter describes the technical specifications of the product. This chapter contains the following sections: Chapter Overview Interfaces Current Protection Functions Voltage and Frequency Protection Functions Power Protection Functions Monitoring and Control Measurements and Recording Standards Compliance Mechanical Specifications Ratings Environmental Conditions Type Tests Electromagnetic Compatibility
621 622 625 630 634 635 637 638 639 640 643 644 645
P14D-B/G/L/Z-TM-EN-1
621
Chapter 17 - Technical Specifications
2
INTERFACES
2.1
FRONT USB PORT
P14D
Front USB port Use
For local connection to laptop for configuration purposes and firmware s
Standard
USB
Connector
USB type B
Isolation
Isolation to ELV level
Protocol
Courier
Constraints
Maximum cable length 5 m
2.2
REAR SERIAL PORT 1 Rear serial port 1
Use
For SCADA communications (multi-drop)
Standard
EIA(RS)485, K-bus
Terminal type
MiDOS
Connector
General purpose block, M4 screws (2 wire)
Cable
Screened twisted pair (STP)
ed Protocols
Courier, IEC-60870-5-103, DNP3.0, MODBUS
Isolation
Isolation to SELV level
Constraints
Maximum cable length 1000 m
2.3
REAR SERIAL PORT 2 Rear serial port 2
Use
For SCADA communications (multi-drop)
Standard
EIA(RS)485, K-bus, EIA(RS)232
Terminal type
MiDOS
Connector
General purpose block, M4 screws (2 wire)
Cable
Screened twisted pair (STP)
ed Protocols
Courier
Isolation
Isolation to SELV level
Constraints
Maximum cable length 1000 m
2.4
IRIG-B PORT IRIG-B Interface (De-modulated)
Use
External clock synchronization signal
Standard
IRIG 200-98 format B00X
Terminal type
MiDOS
Connector
General purpose block, M4 screws (2 wire)
Cable type
Screened twisted pair (STP)
622
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 17 - Technical Specifications
IRIG-B Interface (De-modulated) Isolation
Isolation to SELV level
Constraints
Maximum cable length 1000 m
Accuracy
< +/- 1 s per day
2.5
REAR ETHERNET PORT - FIBRE Rear Ethernet port (fiber)
Main Use
IEC 61850 or DNP3 SCADA communications
Connector
UNI SONET OC-3 LC (1 each for Tx and Rx)
Standard
IEEE 802.3.u 100 BaseFX
Fibre type
Multimode 50/125 µm or 62.5/125 µm
ed Protocols
IEC 61850, DNP3.0 / Ethernet
Wavelength
1300 nm
2.5.1
100 BASE FX RECEIVER CHARACTERISTICS Parameter
Sym
Min.
Typ.
Max.
Unit
Input Optical Power Minimum at PIN Min. (W) Window Edge
-33.5
–31
dBm avg.
Input Optical Power Minimum at PIN Min. (C) Eye Center
-34.5
-31.8
Bm avg.
Input Optical Power Maximum
PIN Max.
-14
-11.8
dBm avg.
Conditions: TA = 0°C to 70°C, VCC = 4.75 V to 5.25 V
2.5.2
100 BASE FX TRANSMITTER CHARACTERISTICS Parameter
Output Optical Power BOL 62.5/125 µm NA = 0.275 Fibre EOL
Sym PO
Output Optical Power BOL 50/125 µm PO NA = 0.20 Fibre EOL
Min.
Typ.
Unit
-19 -20
-16.8
-14
dBm avg.
-22.5 -23.5
-20.3
-14
dBm avg.
10 -10
% dB
-45
dBm avg.
Optical Extinction Ratio Output Optical Power at Logic "0" State
Max.
PO
Conditions: TA = 0°C to 70°C, VCC = 4.75 V to 5.25 V
2.6
REAR ETHERNET PORT COPPER Rear Ethernet port (copper)
Main Use
IEC 61850 or DNP3.0 OE SCADA communications
Standard
IEEE 802.3 10BaseT/100BaseTX
Connector
RJ45
P14D-B/G/L/Z-TM-EN-1
623
Chapter 17 - Technical Specifications
P14D
Rear Ethernet port (copper) Cable type
Screened twisted pair (STP)
Isolation
1 kV
ed Protocols
IEC 61850, DNP3.0 / Over Ethernet
Constraints
Maximum cable length 10 m
624
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 17 - Technical Specifications
3
CURRENT PROTECTION FUNCTIONS
3.1
THREE-PHASE CURRENTPROTECTION Accuracy
DT Pick-up
Setting +/- 5%
Drop-off
0.95 x setting +/- 5%
Minimum trip level for IDMT elements
1.05 x Setting +/-5%
IDMT shape
According to IEC 60255-151:2009
IEEE reset
+/- 5% or 50 ms, whichever is greater
DT Operation
+/- 2% or 70 ms, whichever is greater (1.05 – <2) Is +/- 2% or 50 ms, whichever is greater (2 – 20) Is
DT Reset
+/- 5%
Repeatability
+/- 2.5%
Overshoot of overcurrent elements
<30 ms
3.1.1
DIRECTIONAL PARAMETERS Accuracy
Directional boundary accuracy (RCA +/-90%)
+/-2° with hysteresis <3°
DT Operation
+/- 2% or 80 ms, whichever is greater (1.05 – <2) Is +/- 2% or 60 ms, whichever is greater (2 – 20) Is
3.2
EARTH FAULT PROTECTION (MEASURED) Earth Fault
DT Pick-up
Setting +/- 5%
Drop-off
0.95 x Setting +/-5%
Minimum IDMT Trip level
1.05 x Setting +/-5%
IDMT shape
According to IEC 60255-151:2009 (Reference conditions TMS = 1, TD = 1 and IN1 > setting of 1 A, operating range 2-20 In)
IEEE reset
+/- 5% or 50 ms, whichever is greater
DT operation
+/- 2% or 70 ms, whichever is greater (1.05 – <2) Is +/- 2% or 50 ms, whichever is greater (2 – 20) Is
DT reset
+/- 5%
Repeatability
+/- 2.5%
3.3
EARTH FAULT PROTECTION (DERIVED) Earth Fault
DT Pick-up
Setting +/- 5%
Drop-off
0.95 x Setting +/-5%
Minimum IDMT Trip level
1.05 x Setting +/-5%
P14D-B/G/L/Z-TM-EN-1
625
Chapter 17 - Technical Specifications
P14D
Earth Fault IDMT shape
According to IEC 60255-151:2009 (Reference conditions TMS = 1, TD = 1 and IN2 > setting of 1 A, operating range 2-20 In)
IEEE reset
+/- 10% or 40 ms, whichever is greater
DT operation
+/- 2% or 70 ms, whichever is greater (1.05 – <2) Is +/- 2% or 50 ms, whichever is greater (1.05 – <2) Is
DT reset
+/- 2% or 50 ms, whichever is greater
Repeatability
+/- 5%
3.4
EARTH FAULT DIRECTIONALISATION Zero Sequence Polarising
Operating pick-up
+/-2% of RCA+/-90%
Hysteresis
<3°
VN> pick-up
Setting+/-10%
VN> drop-off
0.9 x Setting +/-10% Negative Sequence Polarising
Operating pick-up
+/-2% of RCA+/-90%
Hysteresis
<3°
VN2> pick-up
Setting+/-10%
VN2> drop-off
0.9 x Setting +/-10%
IN2> pick-up
Setting+/-10%
IN2> drop-off
0.9 x Setting +/-10%
3.5
SENSITIVE EARTH FAULT PROTECTION Sensitive Earth Fault (SEF)
Pick-up
Setting +/- 5%
Drop-off
0.95 x Setting +/-5%
Minimum IDMT Trip level
1.05 x Setting +/-5%
IDMT shape
According to IEC 60255-151:2009 (Reference conditions TMS = 1, TD = 1 and IN > setting of 100 mA, operating range 2-20 In)
IEEE reset
+/- 7.5% or 60 ms, whichever is greater
IDMT operation
+/- 2% or 70 ms, whichever is greater (1.05 - <2) Is +/- 2% or 50 ms, whichever is greater (2 - 20) Is
DT reset
+/- 5%
Repeatability
+/- 5%
DT Operation
+/- 2% or 80 ms, whichever is greater (1.05 - <2) Is +/- 2% or 60 ms, whichever is greater (2 - 20) Is
Note: SEF claims apply to SEF input currents of no more than 2 x In. For input ranges above 2 x In, the claim is not ed.
626
P14D-B/G/L/Z-TM-EN-1
P14D
3.5.1
Chapter 17 - Technical Specifications
SEF DIRECTIONALISATION Wattmetric SEF
Pick-up for P = 0 W
ISEF > +/-5% or 5 mA
Pick-up for P > 0 W
P > +/-5%
Drop-off for P = 0 W
0.95 x ISEF> +/- 5% or 5 mA
Drop-off for P > 0 W
0.9 x P> +/- 5% or 5 mA
Boundary accuracy
+/-5% with hysteresis < 1°
Repeatability
+/- 5%
SEF CosΦ Pick-up
Setting +/-5% for angles RCA+/-60°
Drop-off
0.9 x setting
IDMT shape
+/- 5% or 50 ms, whichever is greater (Reference conditions TMS = 1, TD = 1 and IN > setting of 100 mA, operating range 2-0 In)
IEEE reset
+/- 7.5% or 60 ms, whichever is greater
DT operation
+/- 2% or 50 ms, whichever is greater
DT reset
+/- 5%
Repeatability
+/- 2%
SEF SinΦ Pick-up
Setting +/-5% for angles RCA+/-60° to RCA+/-90°
Drop-off
0.9 x setting
IDMT shape
+/- 5% or 50 ms, whichever is greater (Reference conditions TMS = 1, TD = 1 and IN > setting of 100 mA, operating range 2-0In)
IEEE reset
+/- 7.5% or 60 ms, whichever is greater
DT operation
+/- 2% or 50 ms, whichever is greater
DT reset
+/- 5%
Repeatability
+/- 2%
3.6
RESTRICTED EARTH FAULT PROTECTION High Impedance Residual Earth Fault (REF)
Pick-up
Setting formula +/- 5%
Drop-off
0.8 x Setting formula +/-5%
Operating time
< 60 ms
High pick-up
Setting +/- 10%
High operating time
< 30 ms
Repeatability
< 15%
Low Impedance Residual Earth Fault (REF) Pick-up
Setting formula +/- 5%
Drop-off
0.8 x Setting formula +/-5%
P14D-B/G/L/Z-TM-EN-1
627
Chapter 17 - Technical Specifications
P14D
Low Impedance Residual Earth Fault (REF) Operating time
< 60 ms
High pick-up
Setting +/- 5%
High operating time
< 30 ms
Repeatability
< 15%
3.7
NEGATIVE SEQUNCE OVERCURRENT PROTECTION Accuracy
DT Pick-up
Setting +/- 5%
Drop-off
0.95 x Setting +/-5%
Minimum IDMT Trip level
1.05 x Setting +/-5%
IDMT shape
+/- 5% or 40 ms, whichever is greater
IEEE reset
+/- 5% or 50 ms, whichever is greater
DT operation
+/- 2% or 70 ms, whichever is greater (1.05 – <2) Is +/- 2% or 50 ms, whichever is greater (2 – 20) Is
DT Reset
+/- 5%
3.7.1
DIRECTIONAL PARAMETERS Accuracy
Directional boundary accuracy
+/- 2% with hysteresis < 1°
DT Operation
+/- 2% or 80 ms, whichever is greater (1.05 – <2) Is +/- 2% or 60 ms, whichever is greater (2 – 20) Is
3.8
CIRCUIT BREAKER FAIL AND UNDERCURRENT PROTECTION Accuracy
I< Pick-up
+/- 5% or 20 mA, whichever is greater
I< Drop-off
100% of setting +/- 5% or 20 mA, whichever is greater
Timers
+/- 2% or 50 ms, whichever is greater
Reset time
< 25 ms without DC offset < 35 ms with DC offset
3.9
BROKEN CONDUCTOR PROTECTION Accuracy
Pick-up
Setting +/- 2.5%
Drop-off
0.95 x Setting +/- 2.5%
DT operation
+/- 2% or 55 ms, whichever is greater
3.10
THERMAL OVERLOAD PROTECTION Accuracy
Thermal alarm pick-up
628
Calculated trip time +/- 10%
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 17 - Technical Specifications
Accuracy Thermal overload pick-up
Calculated trip time +/- 10%
Cooling time accuracy
+/- 15% of theoretical
Repeatability
<5%
Operating time measured with applied current of 20% above thermal setting.
3.11
COLD LOAD PICKUP PROTECTION Accuracy
I> Pick-up
Setting +/- 1.5%
IN> Pick-up
Setting +/- 1.5%
I> Drop-off
0.95 x Setting +/- 1.5%
IN> Drop-off
0.95 x Setting +/- 1.5%
DT operation
+/- 0.5% or 50 ms, whichever is greater
Repeatability
+/- 1%
3.12
SELECTIVE OVERCURRENT PROTECTION Accuracy
Fast Block operation
< 25 ms
Fast Block reset
< 30 ms
Time delay
Setting +/- 2% or 20 ms, whichever is greater
3.13
VOLTAGE DEPENDENT OVERCURRENT PROTECTION Accuracy
VCO/VRO threshold pick-up
Setting+/-5%
Overcurrent pick-up
K-factor x setting +/-5%
VCO/VRO threshold drop-off
1.05 x setting +/-5%
Overcurrent drop-off
0.95(K-factor x setting) +/-5%
Operating time
+/- 5% or 60 ms, whichever is greater
Repeatability
+/- 1%
P14D-B/G/L/Z-TM-EN-1
629
Chapter 17 - Technical Specifications
P14D
4
VOLTAGE AND FREQUENCY PROTECTION FUNCTIONS
4.1
UNDERVOLTAGE PROTECTION Accuracy
DT Pick-up
Setting +/- 5%
IDMT Pick-up
Setting +/- 5%
Drop-off
1.02 x Setting +/-5%
IDMT shape
+/- 3.5% or 40 ms, whichever is greater (<10 V) +/- 5% or 40 ms, whichever is greater (>10 V)
DT operation
+/- 2% or 50 ms, whichever is greater
Reset
< 75 ms
Repeatability
+/- 1%
4.2
OVERVOLTAGE PROTECTION Accuracy
DT Pick-up
Setting +/- 1%
IDMT Pick-up
Setting +/- 2%
Drop-off
0.98 x Setting +/-5%
IDMT shape
+/-3.5% or 40 ms, whichever is greater (<10 V) +/- 5% or 40 ms, whichever is greater (>10 V)
DT operation
+/- 2% or 50 ms, whichever is greater
Reset
< 75 ms
Repeatability
+/- 1%
4.3
RESIDUAL OVERVOLTAGE PROTECTION Derived NVD Accuracy
DT Pick-up
Setting +/- 5%
IDMT Pick-up
1.05 x Setting +/- 5%
Drop-off
0.95 x Setting +/-5%
IDMT shape
+/- 5% or 65 ms, whichever is greater
DT operation
+/- 2% or 20 ms or whichever is greater
Instantaneous operation
< 55 ms
Reset
< 35 ms
IDMT shape
+/- 60ms or 5%, whichever is greater
Repeatability
<10%
Measured NVD Accuracy DT Pick-up
630
Setting +/- 5%
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 17 - Technical Specifications
Measured NVD Accuracy IDMT Pick-up
1.05 x Setting +/- 5%
Drop-off
0.95 x Setting +/-5%
IDMT shape
+/- 5% or 65 ms, whichever is greater
DT operation
+/- 2% or 20 ms or whichever is greater
Instantaneous operation
< 55 ms
Reset
< 35 ms
IDMT shape
+/- 60 ms or 5%, whichever is greater
Repeatability
< 10%
4.4
NEGATIVE SEQUENCE VOLTAGE PROTECTION Accuracy
Pick-up
Setting +/- 5%
Drop-off
0.95 x Setting +/-5%
DT operation
+/- 2% or 65 ms, whichever is greater (70 Hz - 45 Hz) +/- 5% or 70 ms, whichever is greater (<45 Hz)
Repeatability
+/- 1%
4.5
RATE OF CHANGE OF VOLTAGE PROTECTION Accuracy for 110V VT
Tolerance
1% or 0.07, whichever is greater
Pick-up
Setting +/- tolerance
Drop-off for positive direction
(Setting – 0.07)+/- tolerance
Drop-off for negative direction
(Setting + 0.07)+/- tolerance
Operating time at 50Hz
(Average cycle x 20) +60 ms
Reset time at 50Hz
40 ms
4.6
OVERFREQUENCY PROTECTION Accuracy
Pick-up
Setting +/- 10 mHz
Drop-off
Setting -20 mHz +/- 10 mHz
Operating timer
+/- 2% or 50 ms, whichever is greater
Operating and Reset time Operating time (Fs/Ff ratio less than 2)
<125 ms
Operating time (Fs/Ff ratio between 2 and 30)
<150 ms
Operating time (Fs/Ff ratio greater than 30)
<200 ms
Reset time
<200 ms
Reference conditions: Tested using step changed in frequency with Freq. Av Cycles setting = 0 and no intentional time delay.
P14D-B/G/L/Z-TM-EN-1
631
Chapter 17 - Technical Specifications
P14D
Fs = start frequency – frequency setting Ff = frequency setting – end frequency
4.7
UNDERFREQUENCY PROTECTION Accuracy
Pick-up
Setting +/- 10 mHz
Drop-off
Setting + 20 mHz +/- 10 mHz
Operating timer
+/- 2% or 50 ms, whichever is greater
Operating and Reset time Operating time (Fs/Ff ratio less than 2)
<100 ms
Operating time (Fs/Ff ratio between 2 and 6)
<160 ms
Operating time (Fs/Ff ratio greater than 6)
<230 ms
Reset time
<200 ms
Reference conditions: Tested using step changed in frequency with Freq. Av Cycles setting = 0 and no intentional time delay. Fs = start frequency – frequency setting Ff = frequency setting – end frequency
4.8
SUPERVISED RATE OF CHANGE OF FREQUENCY PROTECTION Accuracy
Pick-up (f)
Setting +/- 10 mHz
Pick-up (df/dt)
Setting +/- 3% or +/- 10 mHz/s, whichever is greater
Drop-off (f, underfrequency)
Setting + 20 mHz +/- 10 mHz
Drop-off (f, overfrequency)
Setting - 20 mHz +/- 10 mHz
Drop-off (df/dt, falling, for settings between 10 mHz/s and Setting + 5 mHz/s +/- 10 mHz/s 100 mHz/s) Drop-off (df/dt, falling, for settings greater than 100 mHz/s)
Setting + 50 mHz/s +/- 5% or +/- 55 mHz/s, whichever is greater
Drop-off (df/dt, rising, for settings between 10 mHz/s and Setting - 5 mHz/s +/- 10 mHz/s 100 mHz/s ) Drop-off (df/dt, rising, for settings greater than 100 mHz/s)
Setting - 50 mHz/s +/- 5% or +/- 55 mHz/s, whichever is greater
Operating and Reset time Instantaneous operating time (Freq AvCycles setting = 0)
<125 ms
Reset time time (df/dt AvCycles setting = 0)
<400 ms
4.9
INDEPENDENT RATE OF CHANGE OF FREQUENCY PROTECTION Accuracy
Pick-up (df/dt)
632
Setting +/- 3% or +/- 10 mHz/s, whichever is greater
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 17 - Technical Specifications
Accuracy Drop-off (df/dt, falling, for settings between 10 mHz/s and 100 mHz/s)
Setting + 5 mHz/s +/- 10 mHz/s
Drop-off (df/dt, falling, for settings greater than 100 mHz/s)
Setting + 50 mHz/s +/- 5% or +/- 55 mHz/s, whichever is greater
Drop-off (df/dt, rising, for settings between 10 mHz/s and 100 mHz/s)
Setting - 5 mHz/s +/- 10 mHz/s
Drop-off (df/dt, rising, for settings greater than 100 mHz/s)
Setting - 50 mHz/s +/- 5% or +/- 55 mHz/s, whichever is greater
Operating timer
+/- 2% or 50 ms, whichever is greater
Operating and Reset time Operating time (for ramps 2 x seting or greater)
<200 ms
Operating time (for ramps 1.3 x seting or greater)
<300 ms
Reset time time (df/dt AvCycles setting = 0 for df/dt settings greater than <250 ms 0.1 Hz/s and no intentional time delay)
4.10
AVERAGE RATE OF CHANGE OF FREQUENCY PROTECTION Accuracy
Pick-up (f)
Setting +/- 10 mHz
Pick-up (Df/Dt)
Setting +/- 100 mHz/s
Drop-off (falling)
Setting + 20 mHz +/- 10 mHz
Drop-off (rising)
Setting - 20 mHz +/- 10 mHz
Operating timer
+/- 2% or 30 ms, whichever is greater
Operating time Operating time (Freq. Av Cycles setting = 0)
<125 ms
Reference conditions: To maintain accuracy, the minimum time delay setting should be: Dt> 0.375 x Df + 0.23 (f0r Df setting <1Hz) Dt> 0.156 x Df + 0.47 (for Df setting >= 1Hz)
4.11
LOAD RESTORATION Accuracy
Pick-up
Setting +/- 2.5%
Drop-off
0.95% x Setting +/- 2.5%
Restoration timer
+/- 2% or 50 ms, whichever is greater
Holding timer
+/- 2% or 50 ms, whichever is greater
P14D-B/G/L/Z-TM-EN-1
633
Chapter 17 - Technical Specifications
P14D
5
POWER PROTECTION FUNCTIONS
5.1
OVERPOWER / UNDERPOWER Accuracy
Pick-up
Setting +/- 10%
Reverse/Overpower Drop-off
0.95 x Setting +/- 10%
Low forward power Drop-off
1.05 x Setting +/- 10%
Angle variation pick-up
+/- 2°
Angle variation drop-off
+/- 2.5°
Operating time
+/- 2% or 50 ms, whichever is greater
Repeatability
< 5%
Disengagement time
<50 ms
tRESET
+/- 5%
Instantaneous operating time
< 50 ms
5.2
SENSITIVE POWER Accuracy
Pick-up
Setting +/- 10%
Reverse/Overpower Drop-off
0.9 x Setting +/- 10%
Low forward power Drop-off
1.1 x Setting +/- 10%
Angle variation pick-up
+/- 2°
Angle variation drop-off
+/- 2.5°
Operating time
+/- 2% or 50 ms, whichever is greater
Repeatability
< 5%
Disengagement time
<50 ms
tRESET
+/- 5%
Instantaneous operating time
< 50 ms
634
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 17 - Technical Specifications
6
MONITORING AND CONTROL
6.1
VOLTAGE TRANSFORMER SUPERVISION Accuracy
Fast block operation
< 25 ms
Fast block reset
< 30 ms
Time delay
+/- 2% or 20 ms, whichever is greater
6.2
CURRENT TRANSFORMER SUPERVISION Standard CTS Accuracy
IN> Pick-up
Setting +/- 5%
VN< Pick-up
Setting +/- 5%
IN> Drop-off
0.9 x setting +/- 5%
VN< Drop-off
1.05 x setting +/-5% or 1 V, whichever is greater
Time delay operation
Setting +/-2% or 20 ms, whichever is greater
CTS block operation
< 1 cycle
CTS reset
< 35 ms
6.3
CB STATE AND CONDITION MONITORING Accuracy
Timers
+/- 40 ms or 2%, whichever is greater
Broken current accuracy
< +/- 5%
6.4
PSL TIMERS Accuracy
Output conditioner timer
Setting +/- 2% or 50 ms, whichever is greater
Dwell conditioner timer
Setting +/- 2% or 50 ms, whichever is greater
Pulse conditioner timer
Setting +/- 2% or 50 ms, whichever is greater
6.5
CHECK SYNCHRONISATION Accuracy
Timers
6.6
+/- 20 ms or 2%, whichever is greater
DC SUPPLY MONITOR Accuracy
Measuring Range
P14D-B/G/L/Z-TM-EN-1
19 V-310 V ±5%
635
Chapter 17 - Technical Specifications
P14D
Accuracy Tolerance
±1.5 V for 19-100 V ±2% for 100-200 V ±2.5% for 200-300 V
Pickup
100% of Setting ± Tolerance *
Dropoff
Hysteresis 2% 102% of Setting ± Tolerance for the upper limit * 98% of Setting ± Tolerance for the lower limit *
Operating Time
Setting ± (2% or 500 ms whichever is greater)
Disengage Time
< 250 ms
* Tested at 21°C
636
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 17 - Technical Specifications
7
MEASUREMENTS AND RECORDING
7.1
GENERAL General Measurement Accuracy
General measurement accuracy
Typically +/- 1%, but +/- 0.5% between 0.2 - 2 In/Vn
Phase
0° to 360° +/- 0.5%
Current
0.05 to 3 In +/- 1.0% of reading
Voltage
0.05 to 2 Vn +/- 1.0% of reading
Frequency
40 to 70 Hz +/- 0.025 Hz
Power (W)
0.2 to 2 Vn and 0.05 to 3 In +/- 5.0% of reading at unity power factor
Reactive power (Vars)
0.2 to 2 Vn and 0.05 to 3 In +/- 5.0% of reading at zero power factor
Apparent power (VA)
0.2 to 2 Vn and 0.05 to 3 In +/- 5.0% of reading
Energy (Wh)
0.2 to 2 Vn and 0.2 to 3 In +/- 5.0% of reading at zero power factor
Energy (Varh)
0.2 to 2 Vn and 0.2 to 3 In +/- 5.0% of reading at zero power factor
7.2
DISTURBANCE RECORDS Disturbance Records Measurement Accuracy
Maximum record duration
50 s
No of records
Minimum 5 at 10 seconds each Maximum 50 at 1 second each (8 records of 3 seconds, each via IEC 60870-5-103 protocol)
Magnitude and relative phases accuracy
±5% of applied quantities
Duration accuracy
±2%
Trigger position accuracy
±2% (minimum Trigger 100 ms)
7.3
EVENT, FAULT AND MAINTENANCE RECORDS Event, Fault & Maintenance Records
Record location
Flash memory
Viewing method
Front display or MiCOM S1 Agile
Extraction method
Extracted via the USB port
Number of Event records
Up to 2048 time tagged event records
Number of Fault Records
Up to 5
Number of Maintenance Records
Up to 10
7.4
FAULT LOCATOR Accuracy
Fault Location
P14D-B/G/L/Z-TM-EN-1
+/- 3.5% of line length Reference conditions: solid fault applied on line
637
Chapter 17 - Technical Specifications
8
STANDARDS COMPLIANCE
8.1
EMC COMPLIANCE: 2004/108/EC
P14D
Compliance with the European Commission Directive on EMC is demonstrated using a Technical File. Compliance with EN60255-26:2009 was used to establish conformity.
8.2
PRODUCT SAFETY: 2006/95/EC
Compliance with the European Commission Low Voltage Directive (LVD) is demonstrated using a Technical File. Compliance with EN 60255-27: 2005 was used to establish conformity:
8.3
R&TTE COMPLIANCE
Radio and Telecommunications Terminal Equipment (R&TTE) directive 99/5/EC. Conformity is demonstrated by compliance to both the EMC directive and the Low Voltage directive, to zero volts.
8.4
UL/CUL COMPLIANCE
Canadian and USA Underwriters Laboratory File Number E202519 (where marked)
638
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 17 - Technical Specifications
9
MECHANICAL SPECIFICATIONS
9.1
PHYSICAL PARAMTERS Physical Measurements
Case Types
20TE 30TE
Weight (20TE case)
2 kg – 3 kg (depending on chosen options)
Weight (30TE case)
3 kg – 4 kg (depending on chosen options)
Dimensions in mm (w x h x l) (20TE case)
W: 102.4mm H: 177.0mm D: 243.1mm
Dimensions in mm (w x h x l) (30TE case)
W: 154.2mm H: 177.0mm D: 243.1mm
Mounting
, rack, or retrofit
9.2
ENCLOSURE PROTECTION Enclosure Protection
Against dust and dripping water (front face)
IP52 as per IEC 60529:2002
Protection against dust (whole case)
IP50 as per IEC 60529:2002
Protection for sides of the case (safety)
IP30 as per IEC 60529:2002
Protection for rear of the case (safety)
IP10 as per IEC 60529:2002
9.3
MECHANICAL SPECIFICATIONS Mechanical Robustness
Vibration test per EN 60255-21-1:1996
Response: class 2, Endurance: class 2
Shock and bump immunity per EN 60255-21-2:1995
Shock response: class 4, Shock withstand: class 1, Bump withstand: class 4
Seismic test per EN 60255-21-3: 1995
Class 2
9.4
TRANSIT PACKAGING PERFORMANCE Packaging
Primary packaging carton protection
ISTA 1C
Vibration tests
3 orientations, 7 Hz, amplitude 5.3mm, acceleration 1.05g
Drop tests
10 drops from 610mm height on multiple carton faces, edges and corners
P14D-B/G/L/Z-TM-EN-1
639
Chapter 17 - Technical Specifications
P14D
10
RATINGS
10.1
AC MEASURING INPUTS AC Measuring Inputs
Nominal frequency
50 and 60 Hz (settable)
Operating range
40 to 70 Hz
Phase rotation
ABC or CBA
10.2
CURRENT TRANSFORMER INPUTS AC Current
Nominal current (In)
1A and 5A dual rated*
Nominal burden per phase
< 0.05 VA at In
AC current thermal withstand
Continuous: 4 x In 10 s: 30 x In 1 s: 100 x In Linear to 40 x In (non-offset ac current)
Note: A single input is used for both 1A and 5A applications. 1 A or 5 A operation is determined by means of software in the product’s database.
10.3
VOLTAGE TRANSFORMER INPUTS AC Voltage
Nominal voltage
100 V to 120 V, or 380V to 480 V phase-phase
Nominal burden per phase
< 0.1 VA at Vn
Thermal withstand
Continuous: 2 x Vn, 10 s: 2.6 x Vn
10.4
AUXILIARY SUPPLY VOLTAGE Power Supply Voltage
Nominal operating range
24-250 V DC +/-20% 110-240 V AC -20% + 10%
Maximum operating range
19 to 300 V DC
Frequency range for AC supply
45 – 65 Hz
Ripple
<15% for a DC supply (compliant with IEC 60255-11:2008)
10.5
NOMINAL BURDEN Nominal Burden
Quiescent burden
640
20TE
5 W max.
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 17 - Technical Specifications
Nominal Burden 30TE
6 W max.
30TE with 2nd rear communications
6.2 W max.
30TE with Ethernet or TCS
7 W max.
Additions for energised relay outputs
0.26 W per output relay
Opto-input burden
24 V
0.065 W max.
48 V
0.125 W max.
110 V
0.36 W max.
220 V
0.9 W max.
10.6
POWER SUPPLY INTERRUPTION Power Supply Interruption IEC 60255-11:2008 (dc) IEC 61000-4-11:2004 (ac)
Standard
Quiescent / half load
Full load
19.2 V – 110 V dc >110 Vdc
19.2 V – 110 V dc >110 Vdc
20TE
50 ms
100 ms
50 ms
100 ms
30TE
50 ms
100 ms
30 ms
50 ms
30TE with 2nd rear communications
30 ms
100 ms
20 ms
50 ms
30TE with Ethernet or TCS
50 ms
100 ms
20 ms
100 ms
Note: Maximum loading = all inputs/outputs energised.
Note: Quiescent or 1/2 loading = 1/2 of all inputs/outputs energised.
10.7
OUTPUT S Standard s
Compliance
In accordance with IEC 60255-1:2009
Use
General purpose relay outputs for signalling, tripping and alarming
Rated voltage
300 V
Maximum continuous current
10 A
Short duration withstand carry
30 A for 3 s 250 A for 30 ms
Make and break, dc resistive
50 W
Make and break, dc inductive
62.5 W (L/R = 50 ms)
Make and break, ac resistive
2500 VA resistive (cos f = unity)
Make and break, ac inductive
2500 VA inductive (cos f = 0.7)
Make and carry, dc resistive
30 A for 3 s, 10000 operations (subject to the above limits)
Make, carry and break, dc resistive
4 A for 1.5 s, 10000 operations (subject to the above limits)
P14D-B/G/L/Z-TM-EN-1
641
Chapter 17 - Technical Specifications
P14D
Standard s Make, carry and break, dc inductive
0.5 A for 1 s, 10000 operations (subject to the above limits)
Make, carry and break ac resistive
30 A for 200 ms, 2000 operations (subject to the above limits)
Make, carry and break ac inductive
10 A for 1.5 s, 10000 operations (subject to the above limits)
Loaded
1000 operations min.
Unloaded
10000 operations min.
Operate time
< 5 ms
Reset time
< 10 ms
10.8
WATCHDOG S Watchdog s
Use
Non-programmable s for relay healthy/relay fail indication
Breaking capacity, dc resistive
30 W
Breaking capacity, dc inductive
15 W (L/R = 40 ms)
Breaking capacity, ac inductive
375 VA inductive (cos f = 0.7)
10.9
ISOLATED DIGITAL INPUTS Opto-isolated digital inputs (opto-inputs)
Options
The opto-inputs with programmable voltage thresholds may be energized from the 48 V field voltage, or the external battery supply
Rated nominal voltage
24 to 250 V dc
Operating range
19 to 265 V dc
Withstand
300 V dc
Recognition time with half-cycle ac immunity filter removed
< 2 ms
Recognition time with filter on
< 12 ms
10.9.1
NOMINAL PICKUP AND RESET THRESHOLDS
Nominal Battery voltage
Logic levels: 60-80% DO/PU
Logic Levels: 50-70% DO/PU
24/27 V
Logic 0 < 16.2 V : Logic 1 > 19.2 V
Logic 0 <12.0 V : Logic 1 > 16.8
30/34
Logic 0 < 20.4 V : Logic 1 > 24.0 V
Logic 0 < 15.0 V : Logic 1 > 21.0 V
48/54
Logic 0 < 32.4 V : Logic 1 > 38.4 V
Logic 0 < 24.0 V : Logic 1 > 33.6 V
110/125
Logic 0 < 75.0 V : Logic 1 > 88.0 V
Logic 0 < 55.0 V : Logic 1 > 77.0 V
220/250
Logic 0 < 150 V : Logic 1 > 176.0 V
Logic 0 < 110.V : Logic 1 > 154.0 V
Note: Filter is required to make the opto-inputs immune to induced AC voltages.
642
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 17 - Technical Specifications
11
ENVIRONMENTAL CONDITIONS
11.1
AMBIENT TEMPERATURE RANGE Ambient Temperature Range
Compliance
IEC 60255-27: 2005
Test Method
IEC 60068-2-1: 1993 and 60068-2-2: 2007
Operating temperature range
-25°C to +55°C (-13°F to +131°F)
Storage and transit temperature range
-25°C to +70°C (-13°F to +158°F)
11.2
TEMPERATURE ENDURANCE TEST Temperature Endurance Test
Test Method
IEC 60068-2-1: 1993 and 60068-2-2: 2007
Operating temperature range
-40°C operation (96 hours) +85°C operation (96 hours)
Storage and transit temperature range
-40°C operation (96 hours) +85°C operation (96 hours)
11.3
AMBIENT HUMIDITY RANGE Ambient Humidity Range
Compliance
IEC 60068-2-78: 2001 and IEC 60068-2-30: 2005
Durability
56 days at 93% relative humidity and +40°C
Damp heat cyclic
six (12 + 12) hour cycles, 93% RH, +25 to +55°C
11.4
CORROSIVE ENVIRONMENTS Corrosive Environments
Compliance
IEC 60068-2-42: 2003, IEC 60068-2-43: 2003
Industrial corrosive environment/poor environmental control, Sulphur Dioxide
21 days exposure to elevated concentrations (25ppm) of SO2 at 75% relative humidity and +25°C
Industrial corrosive environment/poor environmental control, Hydrogen Sulphide
21 days exposure to elevated concentrations (10ppm) of SO2 at 75% relative humidity and +25°C
Salt mist
IEC 60068-2-52: 1996 KB severity 3
P14D-B/G/L/Z-TM-EN-1
643
Chapter 17 - Technical Specifications
12
TYPE TESTS
12.1
INSULATION
P14D
Insulation Compliance
IEC 60255-27: 2005
Insulation resistance
> 100 M ohm at 500 V DC (Using only electronic/brushless insulation tester)
12.2
CREEPAGE DISTANCES AND CLEARANCES Creepage Distances and Clearances
Compliance
IEC 60255-27: 2005
Pollution degree
3
Overvoltage category
lll
Impulse test voltage (not RJ45)
5 kV
Impulse test voltage (RJ45)
1 kV
12.3
HIGH VOLTAGE (DIELECTRIC) WITHSTAND High Voltage (Dielectric) Withstand
IEC Compliance
IEC 60255-27: 2005
Between all independent circuits
2 kV ac rms for 1 minute
Between independent circuits and protective earth conductor terminal
2 kV ac rms for 1 minute
Between all case terminals and the case earth
2 kV ac rms for 1 minute
Across open watchdog s
1 kV ac rms for 1 minute
Across open s of changeover output relays
1 kV ac rms for 1 minute
Between all RJ45 s and protective earth
1 kV ac rms for 1 minute
Between all screw-type EIA(RS)485 s and protective earth
1 kV ac rms for 1 minute
ANSI/IEEE Compliance
ANSI/IEEE C37.90-1989
Across open s of normally open output relays
1.5 kV ac rms for 1 minute
Across open s of normally open changeover output relays
1 kV ac rms for 1 minute
Across open watchdog s
1 kV ac rms for 1 minute
12.4
IMPULSE VOLTAGE WITHSTAND TEST Impulse Voltage Withstand Test
Compliance
IEC 60255-27: 2005
Between all independent circuits
Front time: 1.2 µs, Time to half-value: 50 µs, Peak value: 5 kV, 0.5 J
Between terminals of all independent circuits
Front time: 1.2 µs, Time to half-value: 50 µs, Peak value: 5 kV, 0.5 J
Between all independent circuits and protective earth conductor terminal
Front time: 1.2 µs, Time to half-value: 50 µs, Peak value: 5 kV, 0.5 J
Note: Exceptions are communications ports and normally-open output s
644
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 17 - Technical Specifications
13
ELECTROMAGNETIC COMPATIBILITY
13.1
1 MHZ BURST HIGH FREQUENCY DISTURBANCE TEST 1 MHz Burst High Frequency Disturbance Test
Compliance
IEC 60255-22-1: 2007 2008, Class III
Common-mode test voltage (level 3)
2.5 kV
Differential test voltage (level 3)
1.0 kV
13.2
DAMPED OSCILLATORY TEST Damped Oscillatory Test
Compliance
EN61000-4-18: 2011: Level 3, 100 kHz and 1 MHz. Level 4: 3 MHz, 10 MHz and 30 MHz
Common-mode test voltage (level 3)
2.5 kV
Common-mode test voltage (level 4)
4.0 kV
Differential mode test voltage
1.0 kV
13.3
IMMUNITY TO ELECTROSTATIC DISCHARGE Immunity to Electrostatic Discharge
Compliance
IEC 60255-22-2: 2008 Class 3 and Class 4,
Class 4 Condition
15 kV discharge in air to interface, display, and exposed metalwork
Class 3 Condition
8 kV discharge in air to all communication ports
13.4
ELECTRICAL FAST TRANSIENT OR BURST REQUIREMENTS Electrical Fast Transient or Burst Requirements
Compliance
IEC 60255-22-4: 2008 and EN61000-4-4:2004. Test severity level lll and lV
Applied to communication inputs
Amplitude: 2 kV, burst frequency 5 kHz and 100 KHz (level 4)
Applied to power supply and all other inputs except for communication inputs
Amplitude: 4 kV, burst frequency 5 kHz and 100 KHz (level 4)
13.5
SURGE WITHSTAND CAPABILITY Surge Withstand Capability
Compliance
IEEE/ANSI C37.90.1: 2002
Condition 1
4 kV fast transient and 2.5 kV oscillatory applied common mode and differential mode to opto inputs, output relays, CTs, VTs, power supply, field voltage
Condition 2
4 kV fast transient and 2.5 kV oscillatory applied common mode to communications, IRIG-B
P14D-B/G/L/Z-TM-EN-1
645
Chapter 17 - Technical Specifications
13.6
P14D
SURGE IMMUNITY TEST Surge Immunity Test
Compliance
IEC 61000-4-5: 2005 Level 4
Pulse duration
Time to half-value: 1.2/50 µs
Between all groups and protective earth conductor terminal
Amplitude 4 kV
Between terminals of each group (excluding communications ports)
Amplitude 2 kV
13.7
IMMUNITY TO RADIATED ELECTROMAGNETIC ENERGY Immunity to Radiated Electromagnetic Energy
Compliance
IEC 60255-22-3: 2007, Class III
Frequency band
80 MHz to 3.0 GHz
Spot tests at
80, 160, 380, 450, 900, 1850, 2150 MHz
Test field strength
10 V/m
Test using AM
1 kHz @ 80%
Compliance
IEEE/ANSI C37.90.2: 2004
Frequency band
80 MHz to 1 GHz
Spot tests at
80, 160, 380, 450 MHz
Waveform
1 kHz @ 80% am and pulse modulated
Field strength
35 V/m
13.8
RADIATED IMMUNITY FROM DIGITAL COMMUNICATIONS Radiated Immunity from Digital Communications
Compliance
IEC 61000-4-3: 2006, Level 4
Frequency bands
800 to 960 MHz, 1.4 to 2.0 GHz
Test field strength
30 V/m
Test using AM
1 kHz / 80%
13.9
RADIATED IMMUNITY FROM DIGITAL RADIO TELEPHONES Radiated Immunity from Digital Radio Telephones
Compliance
IEC 61000-4-3: 2002
Frequency bands
1.89 GHz
Test field strength
10 V/m
13.10
IMMUNITY TO CONDUCTED DISTURBANCES INDUCED BY RADIO FREQUENCY FIELDS Immunity to Conducted Disturbances Induced by Radio Frequency Fields
Compliance
IEC 61000-4-6: 2008, Level 3
Frequency bands
150 kHz to 80 MHz
646
P14D-B/G/L/Z-TM-EN-1
P14D
Chapter 17 - Technical Specifications
Immunity to Conducted Disturbances Induced by Radio Frequency Fields Test disturbance voltage
10 V rms
Test using AM
1 kHz @ 80%
Spot tests
27 MHz and 68 MHz
13.11
MAGNETIC FIELD IMMUNITY Magnetic Field Immunity
Compliance
IEC 61000-4-8: 2009 Level 5 IEC 61000-4-9/10: 2001 Level 5
IEC 61000-4-8 test
100 A/m applied continuously, 1000 A/m applied for 3 s
IEC 61000-4-9 test
1000 A/m applied in all planes
IEC 61000-4-10 test
100 A/m applied in all planes at 100 kHz/1 MHz with a burst duration of 2 seconds
13.12
CONDUCTED EMISSIONS Conducted Emissions
Compliance
EN 55022: 2010
Power supply test 1
0.15 - 0.5 MHz, 79 dBµV (quasi peak) 66 dBµV (average)
Power supply test 2
0.5 – 30 MHz, 73 dBµV (quasi peak) 60 dBµV (average)¤
RJ45 test 1
0.15 - 0.5 MHz, 97 dBµV (quasi peak) 84 dBµV (average)
RJ45 test 2
0.5 – 30 MHz, 87 dBµV (quasi peak) 74 dBµV (average)
13.13
RADIATED EMISSIONS Radiated Emissions
Compliance
EN 55022: 2010
Test 1
30 – 230 MHz, 40 dBµV/m at 10 m measurement distance
Test 2
230 – 1 GHz, 47 dBµV/m at 10 m measurement distance
Test 3
1 – 2 GHz, 76 dBµV/m at 10 m measurement distance
13.14
POWER FREQUENCY Radiated Emissions
Compliance
IEC 60255-22-7:2003
Opto-inputs (Compliance is achieved using the optoinput filter)
300 V common-mode (Class A) 150 V differential mode (Class A)
Note: Compliance is achieved using the opto-input filter
P14D-B/G/L/Z-TM-EN-1
647
Chapter 17 - Technical Specifications
648
P14D
P14D-B/G/L/Z-TM-EN-1
SYMBOLS AND GLOSSARY APPENDIX A
Appendix A - Symbols and Glossary
650
P14D
P14D-B/G/L/Z-TM-EN-1
P14D
1
Appendix A - Symbols and Glossary
CHAPTER OVERVIEW
This appendix contains and symbols you will find throughout the manual. This chapter contains the following sections: Chapter Overview Acronyms and Abbreviations Units for Digital Communications American Vs British English Terminology Logic Symbols and Logic Timers Logic Gates
651 652 658 659 660 664 666
P14D-B/G/L/Z-TM-EN-1
651
Appendix A - Symbols and Glossary
2
P14D
ACRONYMS AND ABBREVIATIONS Term
Description
A
Ampere
AA
Application Association
AC / ac
Alternating Current
ACSI
Abstract Communication Service Interface
ACSR
Aluminum Conductor Steel Reinforced
ALF
Accuracy Limit Factor
AM
Amplitude Modulation
ANSI
American National Standards Institute
AR
Auto-Reclose.
ARIP
Auto-Reclose In Progress
ASDU
Application Service Data Unit
ASCII
American Standard Code for Information Interchange
AUX / Aux
Auxiliary
AWG
American Wire Gauge
BAR
Block Auto-Reclose signal.
BCD
Binary Coded Decimal
BCR
Binary Counter Reading
BDEW
Bundesverband der Energie- und Wasserwirtschaft | Startseite (i.e. German Association of Energy and Water Industries)
BMP
BitMaP – a file format for a computer graphic
BOP
Blocking Overreach Protection - a blocking aided-channel scheme.
BRCB
Buffered Report Control Block
BRP
Beacon Redundancy Protocol
BU
Backup: Typically a back-up protection element
C/O
A ChangeOver having normally-closed and normally-open connections: Often called a "form C" .
CB
Circuit Breaker
CB Aux.
Circuit Breaker auxiliary s: Indication of the breaker open/closed status.
CBF
Circuit Breaker Failure protection
CDC
Common Data Class
CF
Control Function
Ch
Channel: usually a communications or signaling channel
CIP
Critical Infrastructure Protection standards
CLK / Clk
Clock
Cls
Close - generally used in the context of close functions in circuit breaker control.
CMV
Complex Measured Value
CNV
Current No Volts
COT
Cause of Transmission
NI
Centre for the Protection of National Infrastructure
CRC
Cyclic Redundancy Check
CRP
Cross-network Redundancy Protocol
652
P14D-B/G/L/Z-TM-EN-1
P14D
Appendix A - Symbols and Glossary
Term
Description
CRV
Curve (file format for curve information)
CRx
Channel Receive: Typically used to indicate a teleprotection signal received.
CS
Check Synchronism.
CSV
Comma Separated Values (a file format for database information)
CT
Current Transformer
CTRL.
Control
CTS
Current Transformer Supervision: To detect CT input failure.
CTx
Channel Transmit: Typically used to indicate a teleprotection signal send.
CU
Communication Unit
CVT
Capacitor-coupled Voltage Transformer - equivalent to terminology CCVT.
DAU
Data Acquisition Unit
DC
Data Concentrator
DC / dc
Direct Current
DCC
An Omicron compatible format
DDB
Digital Data Bus within the programmable scheme logic: A logic point that has a zero or 1 status. DDB signals are mapped in logic to customize the relay’s operation.
DDR
Dynamic Disturbance Recorder
DEF
Directional earth fault protection: A directionalized ground fault aided scheme.
DG
Distributed Generation
DH
Dynamic Host Configuration Protocol
DHP
Dual Homing Protocol
Diff
Differential protection.
DIN
Deutsches Institut für Normung (German standards body)
Dist
Distance protection.
DITA
Darwinian Information Typing Architecture
DLDB
Dead-Line Dead-Bus: In system synchronism check, indication that both the line and bus are deenergized.
DLLB
Dead-Line Live-Bus: In system synchronism check, indication that the line is de-energized whilst the bus is energized.
DLR
Dynamic Line Rating
DLY / Dly
Time Delay
DMT
Definite Minimum Time
DNP
Distributed Network Protocol
DPWS
Device Profile for Web Services
DST
Daylight Saving Time
DT
Definite Time: in the context of protection elements: An element which always responds with the same constant time delay on operation. Abbreviation of "Dead Time" in the context of auto-reclose:
DTD
Document Type Definition
DTOC
Definite Time Overcurrent
DTS
Date and Time Stamp
EF or E/F
Earth Fault (Directly equivalent to Ground Fault)
EIA
Electronic Industries Alliance
ELR
Environmental Lapse Rate
ER
Engineering Recommendation
P14D-B/G/L/Z-TM-EN-1
653
Appendix A - Symbols and Glossary
Term
P14D
Description
FCB
Frame Count Bit
FFT
Fast Fourier Transform
FIR
Finite Impulse Response
FLC
Full load current: The nominal rated current for the circuit.
FLT / Flt
Fault - typically used to indicate faulted phase selection.
Fn or FN
Function
FPGA
Field Programmable Gate Array
FPS
Frames Per Second
FTP
File Transfer Protocol
FWD, Fwd or Fwd.
Indicates an element responding to a flow in the "Forward" direction
GIF
Graphic Interchange Format – a file format for a computer graphic
GND / Gnd
Ground: used in distance settings to identify settings that relate to ground (earth) faults.
GOOSE
Generic Object Oriented Substation Event
GPS
Global Positioning System
GRP / Grp
Group. Typically an alternative setting group.
GSE
General Substation Event
GSSE
Generic Substation Status Event
GUI
Graphical Interface
HMI
Human Machine Interface
HIF
High Impedance Fault
HiZ
High Impedance (for Restricted Earth Fault)
HSR
High-availability Seamless Ring
HTML
Hypertext Markup Language
Current
I/O
Input/Output
I/P
Input
ICAO
International Civil Aviation Organization
ID
Identifier or Identification. Often a label used to track a software version installed.
IDMT
Inverse Definite Minimum Time. A characteristic whose trip time depends on the measured input (e.g. current) according to an inverse-time curve.
IEC
International Electro-technical Commission
IED
Intelligent Electronic Device
IEEE
Institute of Electrical and Electronics Engineers
IIR
Infinite Impulse Response
Inh
An Inhibit signal
Inst
An element with Instantaneous operation: i.e. having no deliberate time delay.
IP
Internet Protocol
IRIG
InterRange Instrumentation Group
ISA
International Standard Atmosphere
ISA
Instrumentation Systems and Automation Society
ISO
International Standards Organization
JPEF
t Photographic Experts Group – a file format for a computer graphic
L
Live
LAN
Local Area Network
654
P14D-B/G/L/Z-TM-EN-1
P14D
Appendix A - Symbols and Glossary
Term
Description
LCD
Liquid Crystal Display: The front- text display on the relay.
LD
Level Detector: An element responding to a current or voltage below its set threshold.
LDOV
Level Detector for Overvoltage
LDUV
Level Detector for Undervoltage
LED
Light Emitting Diode: Red or green indicator on the front-.
LLDB
Live-Line Dead-Bus : In system synchronism check, indication that the line is energized whilst the bus is de-energized.
Ln
Natural logarithm
LN
Logical Node
LoL
A Loss of Load scheme, providing a fast distance trip without needing a signaling channel.
LPDU
Link Protocol Data Unit
LPHD
Logical Physical Device
MC
MultiCast
MCB
Miniature Circuit Breaker
MCL
MiCOM Configuration Language
MICS
Model Implementation Conformance Statement
MMF
Magneto-Motive Force
MMS
Manufacturing Message Specification
MRP
Media Redundancy Protocol
MU
Merging Unit
MV
Measured Value
N
Neutral
N/A
Not Applicable
N/C
A Normally Closed or "break" : Often called a "form B" .
N/O
A Normally Open or "make" : Often called a "form A" .
NERC
North American Reliability Corporation
NIST
National Institute of Standards and Technology
NPS
Negative Phase Sequence
NVD
Neutral voltage displacement: Equivalent to residual overvoltage protection.
NXT
Abbreviation of "Next": In connection with hotkey menu navigation.
O/C
Overcurrent
O/P
Output
Opto
A generic term for a digital input.
OSI
Open Systems Interconnection
PCB
Printed Circuit Board
PCT
Protective Conductor Terminal (Ground)
PDC
Phasor Data Concentrator
Ph
Phase - used in distance settings to identify settings that relate to phase-phase faults.
PICS
Protocol Implementation Conformance Statement
PMU
Phasor Measurement Unit
PNG
Portable Network Graphics – a file format for a computer graphic
Pol
Polarize - typically the polarizing voltage used in making directional decisions.
POR
Permissive Over Reach
POST
Power On Self Test
P14D-B/G/L/Z-TM-EN-1
655
Appendix A - Symbols and Glossary
Term
P14D
Description
POTT
Permissive Over Reach Transfer Tripping
PRP
Parallel Redundancy Protocol
PSB
Power Swing Blocking, to detect power swing/out of step functions (ANSI 78).
PSL
Programmable Scheme Logic: The part of the relay’s logic configuration that can be modified by the , using the graphical editor within S1 Studio software.
PT
Power Transformer
PTP
Precision Time Protocol
PUR
A Permissive UnderReaching transfer trip scheme (alternative terminology: PUTT).
Q
Quantity defined as per unit value
R
Resistance
RBAC
Role Based Access Control
RCA
Relay Characteristic Angle - The center of the directional characteristic.
REB
Redundant Ethernet Board
REF
Restricted Earth Fault
Rev.
Indicates an element responding to a flow in the "reverse" direction
RMS / rms
Root mean square. The equivalent a.c. current: Taking into the fundamental, plus the equivalent heating effect of any harmonics.
RP
Rear Port: The communication ports on the rear of the IED
RS232
A common serial communications standard defined by the EIA
RS485
A common serial communications standard defined by the EIA (multi-drop)
RST or Rst
Reset generally used in the context of reset functions in circuit breaker control.
RSTP
Rapid Spanning Tree Protocol
RTU
Remote Terminal Unit
Rx
Receive: Typically used to indicate a communication transmit line/pin.
SBS
Straight Binary Second
SC
Synch-Check or system Synchronism Check.
SCADA
Supervisory Control and Data Acquisition
SCL
Substation Configuration Language
SCU
Substation Control Unit
SEF
Sensitive Earth Fault
SHP
Self Healing Protocol
SIR
Source Impedance Ratio
SMV
Sampled Measured Values
SNTP
Simple Network Time Protocol
SOA
Service Oriented Architecture
SOAP
Simple Object Access Protocol
SOC
Second of Century
SOTF
Switch on to Fault protection. Modified protection on manual closure of the circuit breaker.
SP
Single pole.
SPAR
Single pole auto-reclose.
SPC
Single Point Controllable
SPDT
Single Pole Dead Time. The dead time used in single pole auto-reclose cycles.
SPS
Single Point Status
SQRT
Square Root
656
P14D-B/G/L/Z-TM-EN-1
P14D
Appendix A - Symbols and Glossary
Term
Description
STP
Spanning Tree Protocol
SV
Sampled Values
SVM
Sampled Value Model
TAF
Turbine Abnormal Frequency
T
Transmission Control Protocol
TCS
Trip Circuit Supervision
TD
Time Dial. The time dial multiplier setting: Applied to inverse-time curves (ANSI/IEEE).
TE
Unit for case measurements: One inch = 5TE units
THD
Total Harmonic Distortion
TICS
Technical Issues Conformance Statement
TIFF
Tagged Image File Format – a file format for a computer graphic
TLS
Transport Layer Security protocol
TMS
Time Multiplier Setting: Applied to inverse-time curves (IEC)
TOC
Trip On Close ("line check") protection. Offers SOTF and TOR functionality.
TOR
Trip On Reclose protection. Modified protection on autoreclosure of the circuit breaker.
TP
Two-Part
TUC
Timed UnderCurrent
TVE
Total Vector Error
Tx
Transmit
UDP
Datagram Protocol
UPCT
Programmable Curve Tool
USB
Universal Serial bus
UTC
Universal Time Coordinated
V
Voltage
VA
Phase A voltage: Sometimes L1, or red phase
VB
Phase B voltage: Sometimes L2, or yellow phase
VC
Phase C voltage: Sometimes L3, or blue phase
VDR
Voltage Dependant Resistor
VT
Voltage Transformer
VTS
Voltage Transformer Supervision: To detect VT input failure.
WAN
Wide Area Network
XML
Extensible Markup Language
XSD
XML Schema Definition
ZS / ZL
Source to Line Impedance Ratio
P14D-B/G/L/Z-TM-EN-1
657
Appendix A - Symbols and Glossary
3
UNITS FOR DIGITAL COMMUNICATIONS Unit
Description
b
bit
B
Byte
kb
Kilobit(s)
kbps
Kilobits per second
kB
Kilobyte(s)
Mb
Megabit(s)
Mbps
Megabits per second
MB
Megabyte(s)
Gb
Gigabit(s)
Gbps
Gigabits per second
GB
Gigabyte(s)
Tb
Terabit(s)
Tbps
Terabits per second
TB
Terabyte(s)
658
P14D
P14D-B/G/L/Z-TM-EN-1
P14D
4
Appendix A - Symbols and Glossary
AMERICAN VS BRITISH ENGLISH TERMINOLOGY British English
American English
…ae…
…e…
…ence
…ense
…ise
…ize
…oe…
…e…
…ogue
…og
…our
…or
…ourite
…orite
…que
…ck
…re
…er
…yse
…yze
Aluminium
Aluminum
Centre
Center
Earth
Ground
Fibre
Fiber
Ground
Earth
Speciality
Specialty
P14D-B/G/L/Z-TM-EN-1
659
Appendix A - Symbols and Glossary
5
P14D
LOGIC SYMBOLS AND Symbol
Description
Units
&
Logical "AND": Used in logic diagrams to show an AND-gate function.
S
"Sigma": Used to indicate a summation, such as cumulative current interrupted.
t
"Tau": Used to indicate a time constant, often associated with thermal characteristics.
d
Angular displacement
rad
q
Angular displacement
rad
F
Flux
rad
f
Phase shift
rad
w
System angular frequency
rad
<
Less than: Used to indicate an "under" threshold, such as undercurrent (current dropout).
>
Greater than: Used to indicate an "over" threshold, such as overcurrent (current overload)
1
Logical "OR": Used in logic diagrams to show an OR-gate function.
ABC
Anti-clockwise phase rotation.
ACB
Clock-wise phase rotation.
C
Capacitance
A
df/dt
Rate of Change of Frequency protection
Hz/s
df/dt>1
First stage of df/dt protection
Hz/s
F<1
First stage of underfrequency protection: Could be labeled 81-U in ANSI terminology.
Hz
F>1
First stage of overfrequency protection: Could be labeled 81-O in ANSI terminology.
Hz
fmax
Minimum required operating frequency
Hz
fmin
Minimum required operating frequency
Hz
fn
Nominal operating frequency
Hz
Current
A
Ù
Current raised to a power: Such as when breaker statistics monitor the square of ruptured current squared (Ù power = An 2).
’f
Maximum internal secondary fault current (may also be expressed as a multiple of In)
A
<
An undercurrent element: Responds to current dropout.
A
>>
Current setting of short circuit element
In
>1
First stage of phase overcurrent protection: Could be labeled 51-1 in ANSI terminology.
A
>2
Second stage of phase overcurrent protection: Could be labeled 51-2 in ANSI terminology.
A
>3
Third stage of phase overcurrent protection: Could be labeled 51-3 in ANSI terminology.
A
>4
Fourth stage of phase overcurrent protection: Could be labeled 51-4 in ANSI terminology.
A
0
Earth fault current setting Zero sequence current: Equals one third of the measured neutral/residual current.
A
1
Positive sequence current.
A
2
Negative sequence current.
A
2>
Negative sequence overcurrent protection (NPS element).
A
2pol
Negative sequence polarizing current.
A
A
Phase A current: Might be phase L1, red phase.. or other, in customer terminology.
A
B
Phase B current: Might be phase L2, yellow phase.. or other, in customer terminology.
A
C
Phase C current: Might be phase L3, blue phase.. or other, in customer terminology.
A
diff
Current setting of biased differential element
A
660
P14D-B/G/L/Z-TM-EN-1
P14D
Appendix A - Symbols and Glossary
Symbol
Description
Units
f
Maximum secondary through-fault current
A
f max
Maximum secondary fault current (same for all feeders)
A
f max int
Maximum secondary contribution from a feeder to an internal fault
A
f Z1
Maximum secondary phase fault current at Zone 1 reach point
A
fe
Maximum secondary through fault earth current
A
feZ1
Maximum secondary earth fault current at Zone 1 reach point
A
fn
Maximum prospective secondary earth fault current or 31 x I> setting (whichever is lowest)
A
fp
Maximum prospective secondary phase fault current or 31 x I> setting (whichever is lowest)
A
m
Mutual current
A
M64
InterMiCOM64.
Mx
InterMiCOM64 bit (x=1 to 16)
n
Current transformer nominal secondary current. The rated nominal current of the relay: Software selectable as 1 amp or 5 amp to match the line CT input.
A
N
Neutral current, or residual current: This results from an internal summation of the three measured phase currents.
A
N>
A neutral (residual) overcurrent element: Detects earth/ground faults.
A
N>1
First stage of ground overcurrent protection: Could be labeled 51N-1 in ANSI terminology.
A
N>2
Second stage of ground overcurrent protection: Could be labeled 51N-2 in ANSI terminology.
A
s
Value of stabilizing current
A
S1
Differential current pick-up setting of biased differential element
A
S2
Bias current threshold setting of biased differential element
A
SEF>
Sensitive earth fault overcurrent element.
A
sn
Rated secondary current (I secondary nominal)
A
sp
Stage 2 and 3 setting
A
st
Motor start up current referred to CT secondary side
A
K
Dimensioning factor
K1
Lower bias slope setting of biased differential element
%
K2
Higher bias slope setting of biased differential element
%
Ke
Dimensioning factor for earth fault
km
Distance in kilometers
Kmax
Maximum dimensioning factor
Krpa
Dimensioning factor for reach point accuracy
Ks
Dimensioning factor dependent upon through fault current
Kssc
Short circuit current coefficient or ALF
Kt
Dimensioning factor dependent upon operating time
kZm
The mutual compensation factor (mutual compensation of distance elements and fault locator for parallel line coupling effects).
kZN
The residual compensation factor: Ensuring correct reach for ground distance elements.
L
Inductance
mi
Distance in miles.
N
Indication of "Neutral" involvement in a fault: i.e. a ground (earth) fault.
P1
Used in IEC terminology to identify the primary CT terminal polarity: Replace by a dot when using ANSI standards.
P2
Used in IEC terminology to identify the primary CT terminal polarity: The non-dot terminal.
Pn
Rotating plant rated single phase power
PN>
Wattmetric earth fault protection: Calculated using residual voltage and current quantities.
P14D-B/G/L/Z-TM-EN-1
A
W
661
Appendix A - Symbols and Glossary
Symbol
P14D
Description
Units
R
Resistance
W
R Gnd.
A distance zone resistive reach setting: Used for ground (earth) faults.
R Ph
A distance zone resistive reach setting used for Phase-Phase faults.
Rct
Secondary winding resistance
W
Rl
Resistance of single lead from relay to current transformer
W
Rr
Resistance of any other protective relays sharing the current transformer
W
Rrn
Resistance of relay neutral current input
W
Rrp
Resistance of relay phase current input
W
Rs
Value of stabilizing resistor
W
Rx
Receive: typically used to indicate a communication receive line/pin.
S1
Used in IEC terminology to identify the secondary CT terminal polarity: Replace by a dot when using ANSI standards.
S2
Used in IEC terminology to identify the secondary CT terminal polarity: The non-dot terminal.
t
A time delay.
t’
Duration of first current flow during auto-reclose cycle
s
T1
Primary system time constant
s
tfr
Auto-reclose dead time
s
tIdiff
Current differential operating time
s
Ts
Secondary system time constant
s
Tx
Transmit: typically used to indicate a communication transmit line/pin.
V
Voltage.
V
V<
An undervoltage element.
V
V<1
First stage of undervoltage protection: Could be labeled 27-1 in ANSI terminology.
V
V<2
Second stage of undervoltage protection: Could be labeled 27-2 in ANSI terminology.
V
V>
An overvoltage element.
V
V>1
First stage of overvoltage protection: Could be labeled 59-1 in ANSI terminology.
V
V>2
Second stage of overvoltage protection: Could be labeled 59-2 in ANSI terminology.
V
V0
Zero sequence voltage: Equals one third of the measured neutral/residual voltage.
V
V1
Positive sequence voltage.
V
V2
Negative sequence voltage.
V
V2pol
Negative sequence polarizing voltage.
V
VA
Phase A voltage: Might be phase L1, red phase.. or other, in customer terminology.
V
VB
Phase B voltage: Might be phase L2, yellow phase.. or other, in customer terminology.
V
VC
Phase C voltage: Might be phase L3, blue phase.. or other, in customer terminology.
V
Vf
Theoretical maximum voltage produced if CT saturation did not occur
V
Vin
Input voltage e.g. to an opto-input
V
Vk
Required CT knee-point voltage. IEC knee point voltage of a current transformer.
V
VN
Neutral voltage displacement, or residual voltage.
V
Vn
Nominal voltage
V
Vn
The rated nominal voltage of the relay: To match the line VT input.
V
VN>1
First stage of residual (neutral) overvoltage protection.
V
VN>2
Second stage of residual (neutral) overvoltage protection.
V
Vres.
Neutral voltage displacement, or residual voltage.
V
Vs
Value of stabilizing voltage
V
662
P14D-B/G/L/Z-TM-EN-1
P14D
Appendix A - Symbols and Glossary
Symbol
Description
Units
Vx
An auxiliary supply voltage: Typically the substation battery voltage used to power the relay.
V
WI
Weak Infeed logic used in teleprotection schemes.
X
Reactance
None
X/R
Primary system reactance/resistance ratio
None
Xe/Re
Primary system reactance/resistance ratio for earth loop
None
Xt
Transformer reactance (per unit)
p.u.
Y
ittance
p.u.
Z
Impedance
p.u.
Z0
Zero sequence impedance.
Z1
Positive sequence impedance.
Z1
Zone 1 distance protection.
Z1X
Reach-stepped Zone 1X, for zone extension schemes used with auto-reclosure.
Z2
Negative sequence impedance.
Z2
Zone 2 distance protection.
ZP
Programmable distance zone that can be set forward or reverse looking.
Zs
Used to signify the source impedance behind the relay location.
Φal
Accuracy limit flux
Wb
Ψr
Remanent flux
Wb
Ψs
Saturation flux
Wb
P14D-B/G/L/Z-TM-EN-1
663
Appendix A - Symbols and Glossary
6
P14D
LOGIC TIMERS Logic symbols
Explanation
Time chart
Delay on pick-up timer, t
Delay on drop-off timer, t
Delay on pick-up/drop-off timer
Pulse timer
Pulse pick-up falling edge
Pulse pick-up raising edge
664
P14D-B/G/L/Z-TM-EN-1
P14D
Appendix A - Symbols and Glossary
Logic symbols
Explanation
Time chart
Latch
Dwell timer
Straight (non latching): Hold value until input reset signal
P14D-B/G/L/Z-TM-EN-1
665
Appendix A - Symbols and Glossary
7
P14D
LOGIC GATES
Symbol A B
&
IN
B 0 1 0 1
OUT Y 0 0 0 1
A B
1
Y
A 0 0 1 1
IN
B 0 1 0 1
S R Q Y
Standard S-R gate
B 0 0 1 1 0 0 1 1
Y
OUT Y 0 1 1 1
A B
Q0 Q1 0 0 1 1 0 0 1 0 0 1 1 1 0 0 1 1
IN
1
Y
A 0 0 1 1
IN
A B
SD R Q
Y
SD = Set Dominant
A 0 0 0 0 1 1 1 1
Y 0 1 0 0
B 0 1 0 1
B 0 0 1 1 0 0 1 1
Truth Table
OUT
B 0 1 0 1
A B
&
Y
OUT Y 1 1 0 1
A B
1
Y
S Q RD
A B
IN
OUT
B 0 1 0 1
Y 1 1 1 0
A 0 0 1 1
IN
OUT
B 0 1 0 1
Y 1 0 0 0
Truth Table
Symbol
Q0 Q1 0 0 1 1 0 0 1 0 0 1 1 1 0 1 1 1
A 0 0 1 1
Truth Table
Symbol
S – R FLIP-FLOP Symbol Truth Table
Truth Table A 0 0 0 0 1 1 1 1
&
A 0 0 1 1
Symbol
OR GATE Symbol Truth Table
Truth Table
Symbol
A B
A 0 0 1 1
Y
Symbol A B
AND GATE Truth Table Symbol
Truth Table
Y
RD = Reset Dominant
A 0 0 0 0 1 1 1 1
B 0 0 1 1 0 0 1 1
Q0 Q1 0 0 1 1 0 0 1 0 0 1 1 1 0 0 1 0
Warning: To avoid ambiguity, do not use the standard S-R gate unless specifically required
Symbol
Truth Table
A XOR Y B
A 0 0 1 1
IN
B 0 1 0 1
EXCLUSIVE OR GATE Symbol Truth Table
OUT Y 0 1 1 0
A XOR Y B
A 0 0 1 1
IN
B 0 1 0 1
Symbol
Truth Table
OUT Y 1 1 0 1
A XOR Y B
A 0 0 1 1
IN
OUT
B 0 1 0 1
Y 1 0 0 1
PROGRAMMABLE GATE Symbol
A B C
2
Y
Truth Table A 0 0 0 0 1 1 1 1
IN
B 0 0 1 1 0 0 1 1
OUT
C 0 1 0 1 0 1 0 1
Y 0 0 0 1 0 1 1 1
A B C
2
Symbol
Truth Table
Symbol
Y
A 0 0 0 0 1 1 1 1
IN
B 0 0 1 1 0 0 1 1
Truth Table
OUT
C 0 1 0 1 0 1 0 1
Y 0 1 1 1 0 0 0 1
A B C
2
Y
A 0 0 0 0 1 1 1 1
IN
B 0 0 1 1 0 0 1 1
OUT
C 0 1 0 1 0 1 0 1
Y 1 1 1 0 1 0 0 0
NOT GATE Symbol A Inverter (NOT)
Truth Table Y
IN OUT
A 0 1
Y 1 0
V02400
Figure 170: Logic Gates
666
P14D-B/G/L/Z-TM-EN-1
COMMISSIONING RECORD APPENDIX B
Appendix B - Commissioning Record
668
P14D
P14D-B/G/L/Z-TM-EN-1
P14D
Appendix B - Commissioning Record
1
TEST RECORD
1.1
ENGINEER DETAILS Item
Value
Engineer's name Commissioning date Station Circuit System Frequency VT Ratio CT Ratio
1.2
FRONT PLATE INFORMATION Item
Value
Device Model number Serial number Rated current In Rated voltage Vn Auxiliary voltage Vx
1.3
TEST EQUIPMENT Test Equipment
Model
Serial Number
Injection test set Phase angle meter Phase rotation meter Insulation tester Setting application software IEC61850 configurator software DNP3 configurator software
1.4
TESTS WITH PRODUCT DE-ENERGISED Test
Result (mark where appropriate)
Was the IED damaged on visual inspection?
Yes / No
Is the rating information correct for installation?
Yes / No
Is the case earth installed?
Yes / No
Are the current transformer shorting s closed?
Yes / No / Not checked
Is the insulation resistance >100 MOhms at 500 V DC?
Yes / No / Not tested
Wiring checked against diagram?
Yes / No
Test block connections checked?
Yes / No / N/A
P14D-B/G/L/Z-TM-EN-1
669
Appendix B - Commissioning Record
P14D
Test
Result (mark where appropriate)
N/C Watchdog s closed?
Yes / No
N/O Watchdog s open?
Yes / No
Measured auxiliary supply
……………………..V DC / AC
1.5
TESTS WITH PRODUCT ENERGISED General Tests
Result (mark where appropriate)
N/C Watchdog s open?
Yes / No
N/O Watchdog s closed?
Yes / No
LCD contrast setting used
...............................
Clock set to local time?
Yes / No
Time maintained when auxiliary supply removed?
Yes / No
Alarm (yellow) LED working?
Yes / No
Out of service (yellow) LED working?
Yes / No
Programmable LEDs working?
Yes / No
All opto-inputs working?
Yes / No
All output relays working?
Yes / No
1.6
COMMUNICATION TESTS Communications
Result (mark where appropriate)
SCADA Communication standard (Courier, DNP3.0, IEC61850, IEC60870, Modbus) Communications established?
Yes / No
Protocol converter tested?
Yes / No / N/A
1.7
CURRENT INPUT TESTS Current Inputs (if applicable)
Displayed current
Result (mark where appropriate) Primary / Secondary
Phase CT ratio (if applicable) Input CT
Applied Value
Displayed Value
IA IB IC IN ISEF (if applicable)
1.8
VOLTAGE INPUT TESTS Voltage Inputs (if applicable)
Displayed voltage
Result (mark where appropriate) Primary / Secondary
Main VT ratio (if applicable) Input VT
670
Applied Value
Displayed value
P14D-B/G/L/Z-TM-EN-1
P14D
Appendix B - Commissioning Record
Voltage Inputs (if applicable)
Result (mark where appropriate)
VAN VBN VCN
1.9
OVERCURRENT CHECKS Overcurrent Checks
Result
Overcurrent type
Directional / Non-directional
Applied voltage
V
Applied current
A
Expected operating time
s
Measured operating time
s
1.10
ON-LOAD CHECKS On-load checks
Result
Test wiring removed?
Yes / No
Voltage inputs and phase rotation OK?
Yes / No
Current inputs and polarities OK?
Yes / No
On-load test performed?
Yes / No
(If No, give reason why) … IED is correctly directionalised?
1.11
Yes / No / N/A
ON-LOAD CHECKS Final Checks
Result
All test equipment, leads, shorts and test blocks removed safely?
Yes / No
Ethernet connected ?
Yes / No / N/A
Disturbed customer wiring re-checked?
Yes / No / N/A
All commissioning tests disabled?
Yes / No
Circuit breaker operations counter reset?
Yes / No / N/A
Current counters reset?
Yes / No / N/A
Event records reset?
Yes / No
Fault records reset?
Yes / No
Disturbance records reset?
Yes / No
Alarms reset?
Yes / No
LEDs reset?
Yes / No
P14D-B/G/L/Z-TM-EN-1
671
Appendix B - Commissioning Record
672
P14D
P14D-B/G/L/Z-TM-EN-1
WIRING DIAGRAMS APPENDIX C
Appendix C - Wiring Diagrams
674
P14D
P14D-B/G/L/Z-TM-EN-1
P14D
1
Appendix C - Wiring Diagrams
APPENDIX OVERVIEW
This chapter contains the wiring diagrams for all possible situations. This chapter contains the following sections: Appendix Overview I/O Option A I/O Option A with SEF I/O Option A with Ethernet I/O Option A with Ethernet and SEF I/O Option B with 2 Rear Ports I/O Option B with 2 Rear Ports and SEF I/O Option C with TCS I/O Option C with TCS and SEF I/O Option D I/O Option D with SEF KCEG142 Retrofit I/O Option A with NVD Input
675 676 677 678 679 680 681 682 683 684 685 686 687
P14D-B/G/L/Z-TM-EN-1
675
Appendix C - Wiring Diagrams
2
P14D
I/O OPTION A
W02311
Figure 171: P14D Directional IED with 8 inputs and 8 outputs
676
P14D-B/G/L/Z-TM-EN-1
P14D
3
Appendix C - Wiring Diagrams
I/O OPTION A WITH SEF
W02312
Figure 172: P14D Directional IED with 8 inputs, 8 outputs and SEF option
P14D-B/G/L/Z-TM-EN-1
677
Appendix C - Wiring Diagrams
4
P14D
I/O OPTION A WITH ETHERNET
W02313
Figure 173: P14D Directional IED with 8 inputs, 8 outputs and Ethernet
678
P14D-B/G/L/Z-TM-EN-1
P14D
5
Appendix C - Wiring Diagrams
I/O OPTION A WITH ETHERNET AND SEF
W02314
Figure 174: P14D Directional IED with 8 inputs, 8 outputs, Ethernet and SEF option
P14D-B/G/L/Z-TM-EN-1
679
Appendix C - Wiring Diagrams
6
P14D
I/O OPTION B WITH 2 REAR PORTS
W02315
Figure 175: P14D Directional IED with 11 inputs, 12 outputs and two rear ports
680
P14D-B/G/L/Z-TM-EN-1
P14D
7
Appendix C - Wiring Diagrams
I/O OPTION B WITH 2 REAR PORTS AND SEF
W02316
Figure 176: P14D Directional IED with 11 inputs, 12 outputs, 2 rear ports and SEF option
P14D-B/G/L/Z-TM-EN-1
681
Appendix C - Wiring Diagrams
8
P14D
I/O OPTION C WITH TCS
W02317
Figure 177: P14D Directional IED with 11 inputs and 12 outputs, for Trip Circuit Supervision
682
P14D-B/G/L/Z-TM-EN-1
P14D
9
Appendix C - Wiring Diagrams
I/O OPTION C WITH TCS AND SEF
W02318
Figure 178: P14D Directional IED with 11 inputs, 12 outputs and SEF option, for trip Circuit Supervision
P14D-B/G/L/Z-TM-EN-1
683
Appendix C - Wiring Diagrams
10
P14D
I/O OPTION D
W02319
Figure 179: P14D Directional IED with 13 inputs and 12 outputs
684
P14D-B/G/L/Z-TM-EN-1
P14D
11
Appendix C - Wiring Diagrams
I/O OPTION D WITH SEF
W02320
Figure 180: P14D Directional IED with 13 inputs , 12 outputs and SEF option
P14D-B/G/L/Z-TM-EN-1
685
Appendix C - Wiring Diagrams
12
P14D
KCEG142 RETROFIT
W02321
Figure 181: P14D Directional IED with 8 inputs and 8 outputs for KCEG142 retrofit applications
686
P14D-B/G/L/Z-TM-EN-1
P14D
13
Appendix C - Wiring Diagrams
I/O OPTION A WITH NVD INPUT
W02322
Figure 182: P14D Directional IED with 8 inputs, 8 outputs and NVD input
P14D-B/G/L/Z-TM-EN-1
687
Appendix C - Wiring Diagrams
688
P14D
P14D-B/G/L/Z-TM-EN-1
Alstom Grid © - ALSTOM 2012. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited. Alstom Grid Worldwide Centre www.alstom.com/grid/centre/ Tel: +44 (0) 1785 250 070 www.alstom.com